7.10
|
Installation
|
Exhaust system
◄
Exhaust system
↑
|
ESC
|
P
↓
Settings in the exhaust air system are necessary in
single exhaust air systems with more than one
additional group
(peak load function is not enough) or
in central exhaust air systems
.
The total exhaust air is regulated by one or more 1~ fans or ETAvent fans. In accordingly large stalls
or in a central exhaust air system another regulated fan or up to four unregulated asynchronous fans
(in groups) can be connected.
Exhaust mode
Exhaust mode
For single exhaust air systems
with an additional group of fans the settings are made
in the menu
–
Installation
–
Ventilation
–
Peak Load
. For systems with more than one
additional group via relays the settings are made in the exhaust air system (Exhaust air
mode 2 = relation to stall ventilation).
For central exhaust air systems
the exhaust air mode
“
1
”
is set for relation to
|
central
exhaust air total
|
on the master. If the stall of the master contains a
“
second group
”
this
can be programmed in the menu
–
Installation
–
Ventilation
–
Peak Load. The neces-
sary inputs and outputs must be assigned in the IO Setup menu.
Factory setting Exhaust mode switched off
= OFF (no Grop control)
To activate the exhaust air mode, this must be set to:
|
1
|
: Group control for relation to central exhaust air total
|
2
|
: group control for relation to stall ventilation.
Exhaust min.
Exhaust min.
Absolute minimum for the group control
Setting range: 0...100 %
Factory setting: 10 %
Group version
Group version
OFF: (factory setting) no group variant
1. two regulated fans (groups) of the same size:
- fan 1 (group 1) directly by the regulator
- fan 2 (group 2) e.g. via 0 - 10 V output 1 and additional power unit
2. one regulated fan e.g. directly by the regulator and max. four other unregulated
groups (connected via relays)
3. two regulated fans (groups) of different sizes:
- fan 1 (group 1) directly by the regulator
- fan 2 (group 2) e.g. via 0 - 10 V output 1 and additional power unit
Functional description in the following!
Group count
Group count
number of groups of which the ventilation system consists
•
In variant 1+3 (with 0 - 10V control) max. 2 groups. Settings by
“
2
”
possible, (are
ignored by the device, corresponds to number of 2 groups).
•
In variant 2 (relay control) max. 5 groups
Setting range: 2 - 3 - 4 - 5
Factory setting: 2
Group1 100%
Group1 100%
Switch-on value (related to the total air volume of the system) or value at which group 1
is operated with maximum control.
Useful in connection with a heat exchanger. Here, you can have the fan group
“
run up
”
,
so to speak, via the HE to improve its ef
fi
ciency.
Setting range: 0...100 % (of controlled group)
Factory setting: 45 %
Off group2
Off group2
Switch-off value for Group2
Setting range: 0 - 100 %
Factory setting: 45 %
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
The Installation menu
L-BAL-E139-GB 2022/03 Index 006
Part.-No.