Display as long as no digital input is assigned in IO Setup:
|
- - - - -
|
S:21.8
°
KL:76%
Example of overview display for currently calculated setpoint
The setpoint is set to 20.0
°
C (see Setpoint menu item).
The moon symbol indicates the active
“
Setpoint 2
”
.
The actual value is 23.4
°
C.
The currently active setpoint is 21.8
°
C due to the linear change.
Information
With growth program switched on, the
“
setpoint
”
,
“
Minimal ventilation
”
and
“
Maximal ventilation
”
is
calculated by the growth program (
growth program).
Settings of these functions under
“
Ventilation
”
are then not possible! Display:
|
- - - - -
|
Example
nM
50 %
100 %
I
Min.
Min. 0 %
Max. = 100 %
Min. 35 %
Max. = 85 %
20 °C
S
10 K
R
30 °C
09.05.2007
v_tempcontrol_cool_nmotor.vsd
(idealized principle diagram)
nM
Fanlevel Ventilation
S
Setpoint
R
Pband
I
Actual value
9.3.2
For throttle shutter control
The shutter function is used to control one throttle shutter in the chimney above or below the fan.
Shutter offset
Shutter offset
Setpoint for throttle shutter (on 0 - 10 V output
“
Shutter
”
) = setpoint
±
offset
Setting range: -10.0...+10.0 K
Factory setting: -1.0 K
If the output is to operate independently on another temperature source (
Installation
- Shutter), an independent
“
shutter setpoint
”
in
°
C must be entered alternatively.
Setting range: -10.0...+40.0 K
Factory setting: -10.0 K
Shutter Pband
Shutter Pband
Control range
“
Pband
”
for shutter
Narrow control range = Short control times
Wide control range = Longer control times and more stable control
Setting range: 0.1..10.0 K
Factory setting: 2.5 K
Shutter Min.
Shutter Minimal
Setting range: 0...100 %
Factory setting: 0 %
Shutter max.
Shutter Maximal
Setting range: 100...0 %
Factory setting: 100 %
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
Settings for operation
L-BAL-E139-GB 2022/03 Index 006
Part.-No.
59/92