18.09.2008
v_waertau_cte_pte_x.VSD
-
-
1
2
4
3
5
6
Abluft
exhaust air
Außenluft
external air
Zuluftklappe
Supply air shutter
Zentral Zuluft
central supply air
Bypassklappe
bypass shutter
Kanal
duct
1
Exhaust air
2
Ambient air
3
Freshairshutter
4
Central supply air
5
Bypass shutter
6
Channel
7.9
|
Installation
|
bypass shutter
◄
Freshairshutter
↑
|
ESC
|
P
↓
ZK Mode
Freshairshutter Mode
The supply air function is switched = OFF at the factory.
To activate the supply air shutter function, the
“
Freshairshutter Mode
”
function must be
set to
|
1
|
or
|
2
|
:
1: for reference to central exhaust air total (via bus)
2: for reference to stall ventilation
Freshair linear
Freshairshutter Linear = OFF
The supply air shutter is only controlled
“
OPEN
”
or
“
CLOSED
”
by means of a relay.
Hereby,
“
Freshairshutter Start
”
is the closing point and
“
Freshairshutter 100 %
”
the
opening point.
ON
The supply air shutter is controlled linearly by means of the 0
–
10 V output. The shutter
between
“
Freshairshutter Start
”
and
“
Freshairshutter 100 %
”
opens.
Freshairshutter Linear = ON
Setting range: 0...100 %
Factory setting: 75 %
Freshairshutter 100 %
Setting range: 0...100 %
Factory setting: 90 %
FAS Start
ZK 100 %
Changeover temp.
Changeover temp.
At the switching temperature the supply air shutter is forced to open fully.
Application: Supply air in the aisle or switching roof / outside air
setting range: 0.0..70.0
°
C
Factory setting: 10.0
°
C
FA min-HE off
Freshairshutter minimal Heatexchange off
Minimum position of the supply air shutter when heat exchanger
“
OFF
”
Setting range: OFF - 1 - 100 %
Factory setting: OFF
Appropriate allocations for the outputs must be made
IO Setup (Code
|
12
|
supply air shutter)!
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
The Installation menu
L-BAL-E139-GB 2022/03 Index 006