9.6.4
Curve for Maximum Ventilation
Maximum curve
Maximum curve
Factory setting max. curve active = ON, if curve program is switched on.
This curve can be deactivated = OFF if necessary
Max. start
Max. start
Setting range: 50...100 %
Factory setting: 75 %
Increase program Maximum
Day
[%]
31.10.2008
v_max_kurve.VSD
S
0
Start
Knickpunkt1
Break-point1
Knickpunkt2
Break-point2
Endpunkt
Final day
1
2
E
[%]
Maximum Ventilation in %
S
Max. start
1
Max. knick1
2
Max. knick2
E
Max.
fi
nal
Max. knick1
Max. knick1
Setting range: 50...100 %
Factory setting: 80 %
Max. knick2
Max. knick2
Setting range: 50...100 %
Factory setting: 90 %
Max.
fi
nal
Max.
fi
nal
Setting range: 50...100 %
Factory setting: 100 %
9.6.5
Curve for Heating1
Heating1 curve
Heating1 curve
Factory setting heating1 curve active = ON, if curve program is switched
on.
This curve can be deactivated = OFF if necessary
Function only when using the temperature sensor in the stall
“
Installation
”
-
“
Heating 1
”
= H1 input =
|
0
|
.
The set offset values refer to the setpoint of the ventilation (+/-)
Heating1 start
Heating1 start
Setting range:
-10.0...+10.0 K
Factory setting: 0.0 K
Increase program Heating1
Day
[K]
31.10.2008
v_heizung1_kurve.VSD
S
0
Start
Knickpunkt1
Break-point1
Knickpunkt2
Break-point2
Endpunkt
Final day
1
2
E
[K]
Heating offset in K
S
Heating1 start
1
Heating1 knick1
2
Heating1 knick2
E
Heating1
fi
nal
Heating1 knick1
Heating1 knick1
Setting range:
-10.0...+10.0 K
Factory setting: -1.0 K
Heating1 knick2
Heating1 knick2
Setting range:
-10.0...+10.0 K
Factory setting: -1.5 K
Heating1
fi
nal
Heating1
fi
nal
Setting range:
-10.0...+10.0 K
Factory setting: -2.0 K
9.6.6
Curve for Heating2
Heating2 curve
Heating2 curve
Factory setting curve for
“
Heating2
”
not active = OFF.
This curve can be activated = ON if necessary
Function only when using the temperature sensor on
“
E2
”
,
“
E3
”
or via bus
from the master device
“
Installation
”
-
“
Heating 2
”
-
“
H2 input
”
=
|
1
|
,
|
2
|
or
|
3
|
. The settings are absolute values in
°
C
Operating Instructions
Fcontrol
–
model series FTET4/6/10AHMQ-L
Settings for operation
L-BAL-E139-GB 2022/03 Index 006