Minimum extra
Minimum extra
While the set point is increased, an (adjustable) tolerance is added to the ventilation
minimum (normal).
As long as the compartment temperature is greater than the increased set point, this
results in a higher ventilation minimum (summer minimum).
If the compartment temperature falls under the increased setpoint, the tolerance
function is reduced until, with undercutting of the
“
normal setpoint
”
, the tolerance is
reduced to
“
0
”
. Thus, an overly-great amount of chilling is prevented during extreme
temperature drops, but at the same time a good degree of minimal ventilation is
feasible.
Setting range: 0...100 %
Factory setting: 50 %
Information
Function explanation
Ventilation
–
set point derating
7.7
|
Installation
|
Sensor adjust
◄
Sensor adjust
↑
|
ESC
|
P
↓
Adjustment E1
Adjustment E1
Sensor adjustment for
“
E1
”
with a comparator. Enter the difference to the temperature
here.
Setting range: -10.00...+10.00 K
Factory setting: 0.0 K
Adjustment E2
Adjustment E2
Sensor adjustment for
“
E2
”
with a comparator. Enter the difference to the temperature
here.
Setting range: -10.00...+10.00 K
Factory setting: 0.0 K
E3
Adjustment E3
Sensor adjustment for
“
E3
”
with a comparator. Enter the difference to the temperature
here.
Setting range: -10.00...+10.00 K
Factory setting: 0.0 K