Smart Connect
Single Loop Touch Screen Panel
Doc: GLT-229-7-1
51
Issue: 3
Date: 12/05/2017
1.
After selecting the input cause(s), the panel Displays a
screen to select the effect options.
2.
Panel Address: Leave as zero if the output effect is on
this panel, otherwise set to the network address of
the destination panel.
3.
Output Retrigger: this defines whether the sounders
will resound from a new alarm if they had been
previously silenced.
4.
The options are:-
5.
Never
resound
6.
Resound on an alarm from a
New zone
7.
Always
resound for any new alarm.
Select the output type (Point, Local I/O, zone or Panel)
Depending on the OUTPUT type chosen, the panel will display a
list of sub options. For a point OUTPUT the options are:-
Day Delay (seconds)
Night Delay (seconds) This is the delay used if Day/Night timer is
not set
Point Effects:
All On Emergency
Alarm + Beacon Flasher
Alert + Beacon All Off
Eme Beacon Enable
Alarm Disable
Alert
Loop number
Point Address
For a local I/O OUTPUT the options are:-
Day Delay (seconds)
Night Delay (seconds)
Local I/O Effects:
Alarm
Alert
Sounder Off
Enable
Disable
Local I/O start
Local I/O end
For a Zone OUTPUT, the options are:-
Day Delay (seconds)
Night Delay (seconds)
Zone Effects:
All On S Beacon Off
Alarm + Beacon Relay On
Alert + Beacon Relay Off
Eme Beacon All Off
Alarm Disable Sounders
Alert Enable Sounders
Emergency Disable Relays
Beacon Enable Relays
Zone Start
Zone End