PREMIER AD INSTALLATION MANUAL.
Software:PANEL:R1107 & LOOP:R1062
Approved Document No: GLT.MAN-105A
PAGE 29
Issue : 2.02 Authorised: GH Date: 16/07/2007
16. STANDBY BATTERY REQUIREMENTS
The Following Table shows the Quiescent, Fault & alarm currents of the main parts of a Premier AD
Fire Alarm System
Device
Product Code
I
q
(mA)
I
flt
(mA)
I
alm
(mA)
Max
per
Loop
Max
per
System
PREMIER AD FIRE ALARM CONTROL PANEL
NPAD
150 200 250 N/A 1
PREMIER AD REPEATER PANEL
REP-AD
200 220 220 N/A 4*
Fyreye Addressable Ionisation Smoke Detector
FEAI2000
0.6 N/A 2 126 252
Fyreye Addressable Optical Smoke Detector
FEAO2000
0.6 N/A 2 126 252
Fyreye Addressable Heat Detector
FEAH2000
0.6 N/A 2 126 252
Fyreye Addressable High Temperature Heat Detector
FEAHH2000
0.6 N/A 2 126 252
Fyreye Addressable Multi-point Detector
FEAOH2000
0.6 N/A 2 126 252
Fyreye Addressable Carbon Monoxide Detector
FEAHH2000
0.6 N/A 2 126 252
Fyreye Addressable Sounder Base
FEA-SB
0 N/a
10 32
64
Zeta Addressable Call Point (EN54)
ZT-CP2/AD
0.5 N/a 3 126 252
Zeta Addressable Call Point
ZT-MCP/AD
0.4 N/a 13 126 252
Zeta Weatherproof Addressable Call Point
ZT-MCP/AD/WP
0.4 N/a 13 126 252
Zeta Input Unit
ZIU
2 2 2.5
126
252
Zeta Input Output Unit
ZIOU
2 2 10 16
32
Zeta Sounder Control Module
ZSCC
2 2 10 16
32
Zone Monitor Unit
ZT-ZM
6 8-30
22 10
20
Fyreye Addressable Beam Detector (5-50m)
ZTA-FR50
t.b.c.
t.b.c.
t.b.c.
t.b.c.
t.b.c.
Fyreye Addressable Beam Detector (50-100m)
ZTA-FR100
t.b.c.
t.b.c.
t.b.c.
t.b.c.
t.b.c.
Fyreye Plus Addressable Aspiration Detector
FE+50/AD
t.b.c.
t.b.c.
t.b.c.
t.b.c.
t.b.c.
Zeta Addressable Maxitone Sounder
ZAMT
1.5 N/a 9 32 64
Zeta Addressable Miditone Sounder
ZAMD
1.5 N/a
9 32
64
Zeta Addressable Securetone Sounder
ZAST
1.5 N/a
9 32
64
Zeta Addressable Remote LED Indicator
ZTA/LE2
1.5 N/a
10 32 64
Zeta Conventional Maxitone Sounder
ZMT/8
0 N/a
15 N/a
N/a
Zeta Conventional Miditone Sounder
ZMD/8
0 N/a
15 N/a
N/a
Zeta Conventional Securetone Sounder
ZST/8
0 N/a
15 N/a
N/a
Zeta Conventional Megatone Sounder
ZIDC
0 N/a
200 N/a
N/a
Zeta Conventional Flasher
ZFL2RR
0 N/a
90 N/a
N/a
Zeta Conventional Sounder Flasher
ZLT/8RR
0 N/a
110 N/a
N/a
Zeta Conventional 6” Bells
ZTB6B/24
0 N/a
25 N/a
N/a
Zeta Conventional 8” Bells
ZTB8B
0 N/a
35 N/a
N/a
Conventional Detectors (via a Zone Monitor)
Fyreye Conventional Optical Detector
FEO2000
0.06 N/a
25 N/a
N/a
Fyreye Conventional Heat Detector (A1R)
FEHR2000
0.04 N/a
25 N/a
N/a
Fyreye Conventional Heat Detector (CS)
FEFH2000
0.04 N/a
25 N/a
N/a
* The Premier AD can only power 1 repeater. Any subsequent ones will need a separate power