PREMIER AD INSTALLATION MANUAL.
Software Version :PANEL-R1578 & LOOP-R1062
Approved Document No: GLT.MAN-105A
PAGE 3
Issue : 2.02 Authorised: GH Date: 16/07/2007
2.PREMIER AD OVERVIEW
2.1 PANEL DESCRIPTION & DESIGN CONCEPT
The Premier AD is a 2-loop analogue addressable fire alarm control panel designed to EN54 part 2 &
4. It has 2 addressable loops, each capable of having 126 devices.
The Premier AD has 4 conventional sounder circuits, which are always configured as common
sounders. They will activate with an alarm from any zone.
The loop sounder outputs (loop powered sounders, & sounder circuit controllers) can be set up as
zonal, or common.
If the sounder is in a zone that contains a detector or input module, then that sounder will be zonal,
and will only activate with an alarm in that zone.
If the sounder is in a zone that only contains output devices, then it will be common, and will activate
with any alarm.
The exception to this rule is a priority Call Point, which will start all sounders, even if they are set up
as zonal.
It has been designed to give the advantages of an addressable system, with the simplicity of a
conventional system. To help achieve this, the Premier AD uses default values to cut out many of the
programming steps normally associated with addressable panels. It also uses its LEDs as the
Primary source of information, so in most cases, there is no reason to look at the screen, or access
any menus. The screen is simply there to identify loop device fault locations, and to help in setting up
the panel.
2.2 ADVANTAGES OF AN ADDRESSABLE FIRE ALARM SYSTEM
The table below lists the main advantages of addressable systems, and how our panels use them.
FEATURE
PREMIER AL
PREMIER AD
SIMPLICITY
UNIQUE ALARM
IDENTIFICATION
PANEL, LOOP &
ADDRESS
LOOP & ADDRESS
LOOP & ADDRESS
DEVICE LABEL
20 CHARACTERS
20 CHARACTERS
20 CHARACTERS
PREALARM PROGRAMMABLE
LEVEL
PRESET @ 45
PRESET @ 45
DETECTOR
SENSITIVITY
PROGRAMMABLE
(INCLUDING
DAY/NIGHT
SENSITIVITY)
PRESET @ 55
PRESET @ 55
ZONE ALLOCATION PROGRAMMABLE
SET BY DEVICE
ADDRESS
SET BY DEVICE
ADDRESS
PROGRAMMING FULL
PROGRAMMABILITY
ZONAL ALARM OR
COMMON ALARM ONLY
COMMON
OPERATION ONLY
EVENT LOG
YES (200 EVENTS)
YES (2048 EVENTS)
YES (2048 EVENTS)
While all options are programmable on our larger Premier AL panel, the Premier AD uses
preconfigured settings for most options.
Device sensitivity and pre-alarm levels are preset.
To simplify configuration, there is no zone allocation programming. Instead each loop is split into 8
zones, and each device is assigned to a zone by the address set with its 8 way dip switch.
The loop sounder operation is either common or zonal depending on the sounders address.
This leaves only the device label to be programmed by the installer.
Address 1-16
Zone 1 (Zone 9 on loop 2)
Address 17-32
Zone 2 (Zone 10 on loop 2)
Address 33-48
Zone 3 (Zone 11 on loop 2)
Address 49-64
Zone 4 (Zone 12 on loop 2)
Address 65-80
Zone 5 (Zone 13 on loop 2)
Address 81-96
Zone 6 (Zone 14 on loop 2)
Address 97-112
Zone 7 (Zone 15 on loop 2)
Address 113-126
Zone 8 (Zone 16 on loop 2)