Fire alarm system 

EBL128 

4550 

 

EBL128

, an intelligent analog addressable fire alarm system for up to 128 addresses 

 

Auto generation of the Site Specific Data for easier c.i.e. programming 

Analog addressable system 

EBL128

  is  an  intelligent,  analog  and 

addressable 

Control  and  Indicating  Equip-

ment for fire detection and fire alarm systems 
for buildings

, which conforms to the EN54-2 

and the EN54-4 standards.  It meets the most 
stringent requirements in order to secure real 
fire alarms and to reduce nuisance alarms. 

Features / functions 

A user-friendly PC software 

Win128

 is used 

to  create,  edit,  download  and  upload 
(backup) the Site Specific Data (SSD).   

An 

SSD  Auto  generation  function

  is 

included  in  Win128.    The  units  that  are 
connected  to  EBL128  can  be  identified  and 
the  SSD  can  be  auto  generated  with  default 
settings and be edited before the download. 

Some other features / functions: 

 

Compensation

 

for  contamination

,  i.e. 

analog  smoke  detectors  have  constant 
sensitivity in spite of any contamination.  

Service  signal

  will  be  given  when  a 

detector has to be replaced. 

 

Advanced  alarm  algorithms

  are  used 

to  filter  the  nuisance  alarms  from  the 
real  fire  alarms  and  one  algorithm  is 
used for detection of smouldering fires. 

 

User related functions

, e.g. Test mode, 

Disablements,  Alert  annunciation,  Fire 
door  closing,  Interlocking  combinations 
of outputs & inputs, Time channels, Co-
incidence  alarm,  User  definable  text 
message for each alarm point, etc. 

 

Programmable inputs and outputs.

  In 

the  c.i.e.  and/or  via  I/O  units  on  the 

COM  loop.    A  large  number  of  trigger 
conditions are available. 

 

Outputs  for  routing  equipment.

    Fire 

alarm, Fault and Power supply. 

 

Socket

 

for 

an 

optional 

RS485 

transceiver  component  to  provide  an 
interface for up to four ext. Fire Brigade 
Panels,  Ext.  Presentation  Units  and/or 
Alert Annunciation Units. 

 

Interface

 (RS232) for a PC (Win128) 

 

Interface

 (RS232) and power supply for 

Web-server 1598. 

Optional  RS485  transceiver  4552,  provides 
an interface for up to four display units. 

Optional expansion boards 458x mounted in 
an  exp.  board  holder  4551  provides  8  zone 
line inputs and 8 relay outputs respectively. 

Up to 128 addresses 

The  EBL128  c.i.e.  has  one  COM  loop  for 
connection  of  the  loop  units  (address  001-
127).  Each loop unit uses one address.  

Some 

loop units 

that can be connected:  

 

Analog heat & smoke detectors  

 

Addressable manual call points 

 

Addressable short circuit isolators 

 

Addressable  input  and  output  units  (to 
which  e.g.  conventional  detectors  and 
manual call points can be connected) 

 

Addressable sirens & sounder bases 

 

Addressable external power supply units 

Miscellaneous 

The  cabinet  has  a  space  for  two  sealed 
Lead-Acid batteries (2x12 V, 16-18 Ah). 

EBL128 is intended for indoor use and in 
dry premises. 