PREMIER AD INSTALLATION MANUAL.
Software:PANEL:R1107 & LOOP:R1062
Approved Document No: GLT.MAN-105A
PAGE 31
Issue : 2.02 Authorised: GH Date: 16/07/2007
17. PCB TERMINATION CONNECTIONS.
LIVE NEUT- EARTH
RAL
M
AIN
S F
US
E
3A
HB
C
C
ER
A
MI
C
47W
/7
47W
/7
47W
/7
47W
/7
47
W
/7
47W
/7
CONN19 CONN12 CONN20 CONN13 CONN21 CONN14 CONN22 CONN18 CONN15 CONN16 CONN17 CONN28
CONN24 CONN25 CONN23
CONN27
CONN4
CONN6
CONN29
CONN30 CONN2
CONN27
LOOP 1A
- +
SND 1
- +
LOOP 1B
- +
SND 2
- +
LOOP 2A
- +
SND 3
- +
LOOP 2B
- +
SND 4
- +
FIRE RELAY
NO CM NC
SERIAL REPAETER
- + - +
AUX SUP
- +
CLASS CH
- +
FAULT RELAY
NO CM NC
+ -
BATTERY
AC AC
FS1
FS2
FS3
FS4 FS5 FS6 FS7
1 2 3 4 5 6 7 8
9
10 11
12
13
14
20
15
16
19 18 17
17.1 CONNECTIONS
Connection No Description
Use
1
LOOP 1A +&-
Connect to loop 1 side A
2
SND 1 +&-
Connect to sounder circuit 1 (sirens/bells)
3
LOOP 1B +&-
Connect to loop 1 side B
4
SND 2 +&-
Connect to sounder circuit 2 (sirens/bells)
5
LOOP 2A +&-
Connect to loop 2 side A
6
SND 3 +&-
Connect to sounder circuit 3 (sirens/bells)
7
LOOP 2B +&-
Connect to loop 2 side B
8
SND 4 +&-
Connect to sounder circuit 4 (sirens/bells)
9
FIRE RELAY NO/CM/NC
Activates on fire (including test mode)
10
FAULT RELAY NO/CM/NC
Normally powered ie NO is closed with no fault
11
CLASS CHANGE
Join terminals to activate sounders
12
SERIAL RE&-
Connect to RS485 Repeater (2 or 4 cores)
13
AUX SUP +&-
24 volt supply for repeater
14
CONN 27
EARTH connection to display PCB & SCREEN TAG
15
CONN 6
MAINS TERMINAL BLOCK
16
CONN 29
Filtered mains to transformer
17
AC AC
Connected to transformer secondary (30VAC)
18
THERMISTOR
Thermistor to prevent thermal overcharge
19
B & -
Connect 2 x 12V SLA batteries in SERIES (ie 24V)
20
CONN 3
50 way ribbon cable to display PCB
17.2 FUSES
FUSE NO
DESCRIPTION
RATING
FS1
Charger Fuse
2.5A time delay 5 x 20mm glass
FS2
Battery Fuse
2.5A time delay 5 x 20mm glass
FS3
Aux Supply
200mA time delay 5 x 20mm glass
FS4
Sounder circuit 1
250mA time delay 5 x 20mm glass
FS5
Sounder circuit 2
250mA time delay 5 x 20mm glass
FS6
Sounder circuit 3
250mA time delay 5 x 20mm glass
FS7
Sounder circuit 4
250mA time delay 5 x 20mm glass
INLET FUSE
Mains Protection Fuse
3.15A Quick Blow HBC 5 x 20mm ceramic
Summary of Contents for NPAD 2
Page 1: ...INSTALLATION MANUAL...