European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e2s.com             Fax: +44 (0)208 740 4200 
Document No. D211-00-471-IS-SC           Issue A          27-11-19                         Sheet 1 of 8

 

INSTRUCTION MANUAL 

D2xB1LD3 LED Beacons (Visual Fire Alarm)

 

For use in Hazardous Locations

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

1)  Warnings 

 DO NOT OPEN WHEN AN EXPLOSIVE 

ATMOSPHERE IS PRESENT 

 DO NOT OPEN WHEN ENERGISED 

 POTENTIAL ELECTROSTATIC CHARGING 

HAZARD - CLEAN ONLY WITH A DAMP 
CLOTH 

 DO NOT PAINT 

 

Avertissement: 

 NE PAS OUVRIR UN PRESENCE 

D’ATMOSPHERE EXPLOSIVE 

 NE PAS OUVRIR ENERGIE 

 DANGER POTENTIEL CHARGE 

ÉLECTROSTATIQUE - NETTOYER 
UNIQUEMENT AVEC UN CHIFFON HUMIDE 

 NE PAS PENINTURER 

 

2)  Rating & Marking Information 

 

2.1 Public Mode Fire Alarm Ratings 

 
The  D2xB1LD3DC024  is  certified  for  use  as  a  public  mode 
visual alarm device in accordance with UL1971 Third Edition 
and UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition. 
 
For light output ratings see section 12. 
 
For  use  in  public-mode  fire  alarm  systems  the  beacon  must 
be installed without the wire guard or plastic lens cover. 
 
Testing  of  synchronization  requirements  of  UL1971  & 
UL1638 / CAN/ULC-S526 were conducted by UL using a total 
of  6  units  connected  to  the  same  wire  run.  Auto-
synchronization does not require the use of any external sync 
modules  or  protocols.  Providing  the  correct  cable  has  been 
selected  (see  section  6)  an  unlimited  number  of  units  will 
remain synchronized when powered from the same source. 
 

2.2 Private Mode Fire Alarm Ratings 
 

All models are approved for use as a Visual Appliance for use 
in  Private  Mode  Fire  Alarm  Systems  in  accordance  with 
UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition. 

 
For use in private-mode fire alarm systems the beacon must 
be installed without the wire guard or plastic lens cover. 
For light output ratings see section 12.

 

 
2.3 NEC & CEC Class / Division Ratings for US / Canada 

 
The  D2xB1LD3  LED  beacon  complies  with  the  following 
standards: 
 

UL1971 Ed. 3 2018 

 

UL1638 Ed. 5 2017 / CAN/ULC-S526 Ed. 4 
CSA C22.2 No. 205-17 
ANSI/ISA 12.12.01-2015 
CSA C22.2 No. 213-16 

 
The D2xB1LD3 LED beacon is rated as follows: 
 

Class I Div 2 ABCD T4 Ta -40°C to +50°C 
Class II Div 2 FG T6 Ta -40°C to +50°C 
Class III Div 1&2 Ta -40°C to +50°C 

 
The certification approval has validated continuous use up to 
38°C and are for transient use up to 50°C ambient. 

 

Installation must be carried out in compliance with the 
National Electric Code / Canadian Electric Code

 

 
2.4 NEC Class / Zone ratings US 

 
The  D2xB1LD3  LED  beacon  complies  with  the  following 
standards: 
 

UL 60079-0-2017 
UL 60079-15-2017 
UL 60079-31-2015 

 
The D2xB1LD3 LED beacon is rated as follows: 
 
Class I Zone 2 AEx nA IIC Gc T4 Ta -40°C to +50°C 
AEx tc IIIC 75°C Dc Ta -40°C to +50°C 
 
Installation must be carried out in compliance with the 
National Electric Code. 
 

2.5 CEC Class / Zone ratings Canada 

 
The  D2xB1LD3  LED  beacon  complies  with  the  following 
standards: 
 

CAN/CSA C22.2 No. 60079-0:2015 
CAN/CSA C22.2 No. 60079-15:2016 
CAN/CSA C22.2 No. 60079-31:2015 

 
The D2xB1LD3 LED beacon is rated as follows: 
 
Ex nA IIC Gc X T4 Ta -40°C to +50°C 
Ex tc IIIC 75°C Dc X Ta -40°C to +50°C 
 
Installation must be carried out in compliance with the 
Canadian Electric Code 

 
 
 
 

Summary of Contents for D2xB1LD3DC024

Page 1: ...when powered from the same source 2 2 Private Mode Fire Alarm Ratings All models are approved for use as a Visual Appliance for use in Private Mode Fire Alarm Systems in accordance with UL1638 Fifth...

Page 2: ...79 10 2 Explosive atmospheres Classification of areas Explosive dust atmospheres 2 7 Ingress Protection Ratings The product is rated for ingress Protection as follows IP rating IP66 Type rating per UL...

Page 3: ...th of the cable runs The cable size selected must have the necessary capacity to provide the input current to all of the sounders connected to the line When selecting the cable size consideration must...

Page 4: ...erminals 8 2 Line Monitoring DC reverse line monitoring can be used if required All beacons have a blocking diode fitted in their supply input lines An end of line monitoring resistor can be connected...

Page 5: ...Flashing 1 33Hz 11 Maintenance Overhaul Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant stand...

Page 6: ...0 15 15 30 45 60 75 90 90 30 45 60 75 Fig 9 Horizontal dispersion angles for wall mounting Table 2 Horizontal Light Output Dispersion for Wall Mounting Viewing Angle of Rating Intensity cd at 1Hz fla...

Page 7: ...rate 0 100 80 1 77 1 77 3 82 1 5 90 72 1 69 4 69 5 73 9 10 90 72 1 69 4 69 5 73 9 15 90 72 1 69 4 69 5 73 9 20 90 72 1 69 4 69 5 73 9 25 90 72 1 69 4 69 5 73 9 30 75 60 1 57 8 58 0 61 6 35 75 60 1 57...

Page 8: ...om operating current Max operating current D2xB1LD3DC024 24Vdc Regulated 16 33Vdc 1Hz 60fpm 153mA 465mA 1 33Hz 80fpm 189mA 488mA 1 5 Hz 90fpm 203mA 456mA 2Hz 120fpm 248mA 528mA For Public Mode or priv...