3=Economy
4=Building Protection
17, 55, 93, 131
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00° - 670760.00°
[Tx] Setpoint
Thermostat Setpoint Input
2 Bytes
I
C - - W -
DPT_Value_Temp
-273.00° - 670760.00°
[Tx] Basic Setpoint
Reference Setpoint
18, 56, 94, 132
1 Bit
I
C - - W -
DPT_Step
0/1
[Tx] Setpoint Step
0 = Decrease Setpoint; 1 = Increase
Setpoint
19, 57, 95, 133
2 Bytes
I
C - - W -
DPT_Value_Tempd
-670760.00° -
670760.00°
[Tx] Setpoint Offset
Float Offset Value
20, 58, 96, 134
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00° - 670760.00°
[Tx] Setpoint Status
Current Setpoint
21, 59, 97, 135
2 Bytes
O
C T R - -
DPT_Value_Temp
-273.00° - 670760.00°
[Tx] Basic Setpoint Status
Current Basic Setpoint
22, 60, 98, 136
2 Bytes
O
C T R - -
DPT_Value_Tempd
-670760.00° -
670760.00°
[Tx] Setpoint Offset Status
Current Setpoint Offset
23, 61, 99, 137
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Setpoint Reset
Reset Setpoint to Default
1 Bit
I
C - - W -
DPT_Reset
0/1
[Tx] Offset Reset
Reset Offset
24, 62, 100, 138
1 Bit
I
C - - W -
DPT_Heat_Cool
0/1
[Tx] Mode
0 = Cool; 1 = Heat
25, 63, 101, 139
1 Bit
O
C T R - -
DPT_Heat_Cool
0/1
[Tx] Mode Status
0 = Cool; 1 = Heat
26, 64, 102, 140
1 Bit
I
C - - W -
DPT_Switch
0/1
[Tx] On/Off
0 = Off; 1 = On
27, 65, 103, 141
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] On/Off Status
0 = Off; 1 = On
28, 66, 104, 142
1 Bit
I/O
C - R W -
DPT_Switch
0/1
[Tx] Main System (Cool)
0 = System 1; 1 = System 2
29, 67, 105, 143
1 Bit
I/O
C - R W -
DPT_Switch
0/1
[Tx] Main System (Heat)
0 = System 1; 1 = System 2
30, 68, 106, 144
1 Bit
I
C - - W -
DPT_Enable
0/1
[Tx] Enable/Disable Secondary System (Cool)
0 = Disable; 1 = Enable
31, 69, 107, 145
1 Bit
I
C - - W -
DPT_Enable
0/1
[Tx] Enable/Disable Secondary System (Heat)
0 = Disable; 1 = Enable
32, 38, 70, 76, 108,
114, 146, 152
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] [Sx] Control Variable (Cool)
PI Control (Continuous)
33, 39, 71, 77, 109,
115, 147, 153
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] [Sx] Control Variable (Heat)
PI Control (Continuous)
1 Byte
O
C T R - -
DPT_Scaling
0% - 100%
[Tx] [Sx] Control Variable
PI Control (Continuous)
34, 40, 72, 78, 110,
116, 148, 154
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Cool)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Cool)
PI Control (PWM)
35, 41, 73, 79, 111,
117, 149, 155
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Heat)
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] Control Variable (Heat)
PI Control (PWM)
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] Control Variable
2-Point Control
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] Control Variable
PI Control (PWM)
36, 42, 74, 80, 112,
118, 150, 156
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] PI State (Cool)
0 = PI Signal 0%; 1 = PI Signal
Greater than 0%
37, 43, 75, 81, 113,
119, 151, 157
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] PI State (Heat)
0 = PI Signal 0%; 1 = PI Signal
Greater than 0%
1 Bit
O
C T R - -
DPT_Switch
0/1
[Tx] [Sx] PI State
0 = PI Signal 0%; 1 = PI Signal
Greater than 0%