background image

 

 

 

MINiBOX 45 v2/MINiBOX 25 v2

 

http://www.zennio.com

 

              

Technical Support:

 

http://support.zennio.com

 

 

22 

its  on-off  state,  which  will  be  reported  to  the  KNX  bus  through  the 

corresponding status object, if enabled. 

 

Shutter  Channel

:  when  the  button  is  pressed,  the  device  will  act  over  the 

output according to the length of the button press and to the current state. 

  A 

long  press

  makes  the  shutter  start  moving  (upwards  or  downwards, 

depending on the button being pressed). The LED will light in green until the 

end of the motion. If the button gets pressed being the shutter already at the 

top or bottom positions, nothing will happen (the LED will not light). 

  A 

short press

 will make the shutter drive stop (if in motion), as it normally 

does when a step/stop order is received from the KNX bus. In case of not 

being the shutter in motion, pressing the button does not cause any action, 

unless  slats/lamellas  have  been  parameterized 

–  in  such  case,  a  step 

movement (up/down, depending on the button pressed) will take place. The 

status objects will be sent to the bus when corresponding.  

 

Fan Coil module

: the behaviour will depend on whether a fan-labelled 

 or a 

valve-labelled 

 button is pressed: 

 

Fan

: for this type of buttons, it must be taken into account that there are two 

types of control for the fan speed: 

 

Switching control

: a short or long press will switch the relays to set the 

selected speed, unless it matches the current speed 

– in such case all 

the relays will be opened (speed 0). The associated LEDs will indicate 

the state of the fan speed control relays (on = relay closed;  off = relay 

open). 

 

Accumulation  control: 

a  short  or  long  press  switch  to  the  selected 

speed, closing the relay associated with that speed, and also the relays 

assigned to the lower speeds, unless it matches the current speed 

– in 

such case all the relays will be opened (speed 0). The associated LEDs 

will indicate the state of the fan speed control relays (on = relay closed; 

off = relay open). 

Note

the behaviour of the relays will depend on the parameterisation, i.e., 

on the number of fan speeds, and on the delay between switches.

 

Summary of Contents for MINiBOX 45v2

Page 1: ...MINiBOX 45 v2 MINiBOX 25 v2 Multifunction Actuator with 4 or 5 Outputs and 5 Inputs ZIOMN45V2 USER MANUAL ZIOMN25V2 Application program version 1 1 User manual edition 1 1 _a www zennio com...

Page 2: ...2 MINiBOX 45 v2 4 1 2 Installation 6 1 3 Start Up and Power Loss 7 2 Configuration 8 2 1 General 8 2 2 Inputs 11 2 2 1 Binary Input 11 2 2 2 Temperature Probe 11 2 2 3 Motion Detector 11 2 3 Outputs 1...

Page 3: ...45 v2 MINiBOX 25 v2 http www zennio com Technical Support http support zennio com 3 DOCUMENT UPDATES Version Changes Page s 1 1_a Changes in the application program of MINiBOX 45 25 v2 Internal optim...

Page 4: ...e as Up to 4 2 individual ON OFF output Up to 2 1 independent shutter channels with or without slats Up to 1 two pipe fan coil modules where both the fan speed control and the valve control are perfor...

Page 5: ...p www zennio com Technical Support http support zennio com 5 Manual operation supervision of the 2 or 4 relay outputs through the on board pushbuttons and LEDs Heartbeat or periodical still alive noti...

Page 6: ...although entirely analogous The main elements of the device are described next Test Prog Pushbutton 6 a short press on this button sets the device into the programming mode making the associated LED 5...

Page 7: ...zennio com 1 3 START UP AND POWER LOSS During the start up of the device the Test Prog LED will blink in blue colour for a few seconds before the device is ready External orders will not be executed...

Page 8: ...e is General From this screen it is possible to activate deactivate all the required functionality Figure 2 Default screen Inputs disabled enabled 1 enables o disables the Inputs tab on the left menu...

Page 9: ...r more details Sending of Indication Objects 0 and 1 on Bus Voltage Recovery disabled enabled this parameter lets the integrator activate two new communication objects Reset 0 and Reset 1 which will b...

Page 10: ...of up to 255 seconds to prevent bus overload The following sendings match the period set Show Relay Switches Counter Objects disabled enabled enables two communication objects to keep track of the nu...

Page 11: ...ual Binary Inputs available in the MINiBOX 45 25 v2 product section at the Zennio website www zennio com 2 2 2 TEMPERATURE PROBE Please refer to the specific user manual Temperature Probe available in...

Page 12: ...cally to the corresponding product section to obtain the aforementioned document Motion detectors with references ZN1IO DETEC and ZN1IO DETEC N are not compatible with MINiBOX 45 25 v2 may report inac...

Page 13: ...ndent shutter channels respectively Fan Coil modules which allow the control of the fan and the valve of two pipe fan coil units it is possible to control one independent fancoil block only in MINiBOX...

Page 14: ...execution of each function can depend on a configurable condition which will be evaluated every time the function is triggered through specific parameterizable communication objects The result after...

Page 15: ...v2 implements four Zennio thermostats which can be enabled and configured independently Please refer to the specific Zennio Thermostat user manual available in the MINiBOX 45 25 v2 product section at...

Page 16: ...r order a thermostat setpoint or mode switch order a constant value a scene Only the trigger object and the twelve status objects are required to be binary on off The most typical scenario for this Ma...

Page 17: ...f the above state objects with such value Otherwise i e if none of them has a value of 1 it will be sent with a value of 0 Trigger Value 0 1 0 1 sets the value that will trigger when received through...

Page 18: ...HVAC thermostat mode value configurable in Value Auto Comfort Standby Economy Building Protection whenever the general switch off takes off Note the above options are not mutually exclusive it is pos...

Page 19: ...for that output or that channel such temporisation will be interrupted and only the delay and the action of the new scene will be executed ETS PARAMETERISATION Prior to setting the scene temporisation...

Page 20: ...coil module Note In the configuration of a scene of an output shutter channel fan coil it is possible to parameterize several scenes with the same scene number This means that several delay parameters...

Page 21: ...y switching to the Test On mode unless disabled by parameter needs to be done by long pressing the Prog Test button for at least three seconds until the LED is no longer red and turns yellow From that...

Page 22: ...vement up down depending on the button pressed will take place The status objects will be sent to the bus when corresponding Fan Coil module the behaviour will depend on whether a fan labelled or a va...

Page 23: ...ding on whether the output has been parameterised as an individual output as part of a shutter channel or a fan coil block the reactions to the button presses will differ Individual output short or lo...

Page 24: ...tatus is carried out when exiting this mode so that any change in the alarm status or blocking of the outputs while Test ON mode is active is taken into account when exiting this mode and is updated w...

Page 25: ...nabled object Manual Control Lock turns visible as well as two more parameters Value 0 Lock 1 Unlock 0 Unlock 1 Lock defines whether the manual control lock unlock should take place respectively upon...

Page 26: ...x Temperature Source 1 External Sensor Temperature 7 45 83 121 2 Bytes I C W DPT_Value_Temp 273 00 670760 00 Tx Temperature Source 2 External Sensor Temperature 8 46 84 122 2 Bytes O C T R DPT_Value_T...

Page 27: ...O C R W DPT_Switch 0 1 Tx Main System Cool 0 System 1 1 System 2 29 67 105 143 1 Bit I O C R W DPT_Switch 0 1 Tx Main System Heat 0 System 1 1 System 2 30 68 106 144 1 Bit I C W DPT_Enable 0 1 Tx Ena...

Page 28: ...ilding Protection ML Courtesy Switch On HVAC mode Auto Comfort Standby Economy Building Protection 180 184 188 192 196 2 Bytes O C T R DPT_Value_Temp 273 00 670760 00 Ix Current Temperature Temperatur...

Page 29: ...8 191 Ix Short Press Run Scene Sending of 0 63 1 Byte C T DPT_SceneControl 0 63 128 191 Ix Short Press Save Scene Sending of 128 191 1 Bit I O C T R W DPT_Switch 0 1 Ix Switch Sensor Edge Sending of 0...

Page 30: ...ress Darker Long Pr Darker Release Stop 4 Bit C T DPT_Control_Dimming 0x0 Stop 0x1 Dec by 100 0x7 Dec by 1 0x8 Stop 0xD Inc by 100 0xF Inc by 1 Ix Long Press Brighter Darker Long Pr Brighter Darker Re...

Page 31: ...on Ix Presence State HVAC Auto Comfort Standby Economy Building Protection 247 276 305 334 363 1 Bit O C T R DPT_Occupancy 0 1 Ix Presence State Binary Binary Value 1 Bit O C T R DPT_Ack 0 1 Ix Presen...

Page 32: ...Bit I C W DPT_Enable 0 1 Ox Lock 0 Unlock 1 Lock 420 431 442 453 1 Bit I C W DPT_Start 0 1 Ox Timer 0 Switch Off 1 Switch On 421 432 443 454 1 Bit I C W DPT_Start 0 1 Ox Flashing 0 Stop 1 Start 422 43...

Page 33: ...1 Cx Sunshine Shadow 0 Shadow 1 Sunshine 501 529 1 Bit I C T W U DPT_Heat_Cool 0 1 Cx Cooling Heating 0 Heating 1 Cooling 1 Bit I C T W U DPT_Heat_Cool 0 1 Cx Cooling Heating 0 Cooling 1 Heating 502 5...

Page 34: ...trol S0 0 S1 1 584 1 Byte O C T R DPT_Value_1_Ucount 0 255 FCx Fan Speed Enumeration Status S0 0 S1 1 S2 2 S3 3 1 Byte O C T R DPT_Value_1_Ucount 0 255 FCx Fan Speed Enumeration Status S0 0 S1 1 S2 2...

Page 35: ...Bit O C T R DPT_Bool 0 1 FCx Control Value Error 0 No Error 1 Error 598 2 Bytes I C W U DPT_Value_Temp 273 00 670760 00 FCx Ambient Temperature Ambient Temperature 599 2 Bytes I C W U DPT_Value_Temp 2...

Page 36: ...2147483648 2147483647 LF Function x Result 4 Byte Signed 1 Byte O C T R DPT_Scaling 0 100 LF Function x Result 1 Byte Percentage 2 Bytes O C T R DPT_Value_2_Count 32768 32767 LF Function x Result 2 By...

Page 37: ...n and send us your inquiries about Zennio devices http support zennio com Zennio Avance y Tecnolog a S L C R o Jarama 132 Nave P 8 11 45007 Toledo Spain Tel 34 925 232 002 www zennio com info zennio c...

Reviews: