MINiBOX 45 v2/MINiBOX 25 v2
Technical Support:
7
Inputs (3)
: input ports for the insertion of the stripped cables of external
elements such as switches / motion detectors / temperature probes, etc. One
of the two cables of each element need to be connected to one of the slots
labelled
“1” to “6”, while the other cable should be connected to the slot labelled
as “C”. Note that all the external input devices share the “C” slot for one of the
two cables. Please secure the connection by means of the on-board screws.
To get detailed information about the technical features of this device, as well as on the
installation and security procedures, please refer to the corresponding
Datasheet
,
bundled with the original package of the device and also available at
1.3
START-UP AND POWER LOSS
During the start-up of the device, the Test/Prog. LED will blink in blue colour for a few
seconds before the device is ready. External orders will not be executed during this time,
but afterwards.
Depending on the configuration, some specific actions will also be performed during the
start-up. For example, the integrator can set whether the output channels should switch
to a particular state and whether the device should send certain objects to the bus after
the power recovery. Please consult the next sections of this document for further details.
On the other hand, when a bus power failure takes place, the device will interrupt any
pending actions, and will save its state so it can be recovered once the power supply is
restored. For safety reasons, all
shutter channels
will be stopped (i.e., the relays will
open) if a power loss takes place, while the individual outputs and fan coil contacts will
switch to the specific state configured in ETS (if any).