AF9ZP0BA - EPS-ACW REACH TRUCK - User Manual
Page - 41/90
HALF MOON.
10) FAN TEMPERATURE
Epsacw drives the fan for cooling the entire system. When the temperature in
the epsacw overtakes this setting, the fan must be switched on.
11) OUX OUT 2 D.C.
This parameter sets the max PWM (in percentage of the full conduction) on
output CNA#14.
12) SET STEER MAX
It sets the max current in the fan connected to CNA#10.
13) A10 A14 PWM KHZ
It sets the frequency of the PWM in the loads connected to CNA#10 and
CNA#14.
14) AUX VOLTAGE #1
(Factory adjusted). This is the self-acquired offset value of the stepper motor
line connected to CNA#20. The default value is 2.500 mV and can be re-
acquired by rolling the DEBUG OUTPUT to 0 (see 13.3.7.3).
15) AUX VOLTAGE #2
(Factory adjusted). This is the self-acquired offset value of the stepper motor
line connected to CNA#17. The default value is 2.500 mV and can be re-
acquired by rolling the DEBUG OUTPUT to 0 (see 13.3.7.3).