* Model Specific Formatting information for Result Data functions
Address
Description
40001 .................... High bytes for Accumulated odorant injected, combine with address 40002 for total.
40002 .................... 6300GE/LE = .XXXXX, 7300GE/LE = X.XXXX, 8300GE/LE = XX.XXX (lbs),
6300GM/LM = .XXXXX, 7300GM/LM = X.XXXX, 8300GM/LM = XX.XXX (kg)
Note:
Low bytes only, combine with address 40001 for total odorant injected.
40003 .................... High bytes for Accumulated flow, combine with address 40004 for total.
40004 .................... 6300GE = .XXXXX, 7300GE = X.XXXX, 8300GE = XX.XXX (MMCF/hr),
6300GM = X.XXX, 7300GM = XX.XXX, 8300GM = XXX.XX (M
3
/sec) 6300LE = XXX.XX,
7300LE = XXXX.X, 8300LE = XXXXX (gallons), 6300LM = XXX.XX, 7300LM = XXXX.X,
8300LM = XXXXX (liters), 6300/7300/8300LE (PPMV mode) = XXXXX (gallons),
6300/7300/8300LM (PPMV mode) = XXXXX (liters)
Note:
Low bytes only, combine with address 40003 for total accumulated flow.
40015 .................... High bytes only, combine with address 40016 for total odorant injected.
40016 .................... 6300 = .XXXX, 7300 = X.XXX, 8300 = XX.XX (lbs/kg)
Note:
Low bytes only, combine with address 40015 for total odorant injected.
40017 .................... Model number format: 63XX = 6300, 73XX = 7300, 83XX = 8300. XX= 11= GE,
XX=12=GM, XX=21=LE, XX=22=LM. Example: 6311 = 6300 Gas English,
7322 = 7300 Liquid Metric
40019 .................... 6300 = XX.XXX, 7300 = XXX.XX, 8300 = XXXX.X (cc)
Parameter functions
The result data functions available via Modbus are listed below. The registers are accessed using Modbus
functions 3, 6, and 16.
Note: The system must be stopped in order for any parameter changes to be accepted. An exception
response will be returned if a parameter change query is issued while the system is running. Once the
parameter changes have been made, use coil 00009 to save the updated parameters before restarting
the system.
Address
Access
Description
40101 .......... Read Only .............Current Date (Day of Month / Month) (01-31 / 01-12) – BCD
40102 .......... Read Only .............Current Date (Century / Year) (0000-9999) – BCD
40103 .......... Read Only .............Current Time (Seconds / Minutes) (00-59 / 00-59) – BCD
40104 .......... Read Only .............Current Time (Hours / Day of Week) (00-23/01-07) – BCD
40105 .......... Read/Write ............ Injection Rate - Unsigned Integer *See formatting info.
40106 .......... Read/Write ............ Pump Displacement (cc/Stroke) – Unsigned Integer *See formatting info.
40107........... Read/Write .............Odorant Density – Unsigned Integer X.XX (GE/LE = lbs/gal, GM/LM = g/cc)
40108 .......... Read/Write ............ Proportional to Time Stroke Rate X.XX (minutes) – Unsigned Integer
40109 .......... Read/Write ............ Maximum Gas Flow – Unsigned Integer *See formatting info.
40110 ........... Read/Write ............ Low Flow Shutoff (xx.x of Max Gas Flow) – Unsigned Integer
40111 ........... Read/Write ............ Flow No Signal (xx.x of Max Gas Flow) – Unsigned Integer
40112 ........... Read/Write ............ Maximum time per stroke (xxx minutes/stroke) – Unsigned Integer
40113 ........... Read/Write ............ Odorant Output (lbs/pulse) – Unsigned Integer *See formatting info.
40114 ........... Read/Write ............ Pulses per Second (xx Pulses/Seconds) – Unsigned Integer
40115 ........... Read/Write ............ Pulses per Minute / Pulses per Gallon (xx Pulses/Minute - Gas,
xx Pulses/Gal– Liquid PPMV) – Unsigned Integer