JOHNSON CONTROLS
149
SECTION 10 – MAINTENANCE
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
10
TABLE 33 – ISN TRANSMITTED DATA (CONT’D)
ISN CONTROL (CON’T)
ISN
PAGE
CHARACTER
TYPE
DATA
P38
110
Digital Evaporator Heater
Status
P39
111
Digital Evaporator Pump
Status
P40
112
Digital SYS 1
Comp. 2 Run
P41
113
Digital SYS 2
Comp. 2 Run
P42
114
Digital
SYS 1 Liquid Line
Solenoid Valve or
EEV Pilot Solenoid
P43
115
Digital SYS 1 Hot Gas
Bypass Valve
P44
116
Digital SYS 1
Comp. 2 Run
P45
117
Digital SYS 2
Comp. 2 Run
P46
118
Digital
SYS 2 Liquid Line
Solenoid Valve or
EEV Pilot Solenoid
P47
119
Digital Lead System
(0=SYS 1, 1=SYS 2)
P48
120
Digital SYS 1
Comp.3 Run
P49
121
Digital SYS 2
Comp. 3 Run
P50
122
Digital Chilled Liquid Type
(0=Water, 1=Glycol)
P51
123
Digital
Ambient Control Mode
(0=Std. Ambient,
1=Low Ambient)
P52
124
Digital
Local/Remote
Control Mode
(0=Local,
1=Remote)
P53
125
Digital Units
(0=Imperial, 1= SI)
P54
126
Digital
Lead/Lag Control
Mode
(0=Manual,1= Remote)
P55
127
Digital
----
P56
128
Coded * SYS 1
Operational Code
P57
129
Coded * SYS 1
Fault Code
P58
130
Coded * SYS 2
Operational Code
P59
131
Coded * SYS 2
Fault Code
ISN
PAGE
CHARACTER
TYPE
DATA
P60
132
Coded
----
P61
133
Coded SYS 1 Condenser
Fan Stage
P62
134
Coded
----
P63
135
Coded SYS 2 Condenser
Fan Stage
P64
136
Coded
----
P65
137
Coded
Unit Control Mode
(0=Leaving Water,
1=Return Water,
2=Discharge Air,
3=Suction Press.,
4=Cooling
5=Heating)
P66
138-141
Analog Anti-Recycle Timer
P67
142-145
Analog Leaving Chilled Liquid
Temp. Cutout
P68
146-149
Analog Low Ambient
Temp. Cutout
P69
150-153
Analog
----
P70
154-157
Analog Low Suction
Pressure Cutout
P71
158-161
Analog High Discharge
Pressure Cutout
P72
162-165
Analog Setpoint
P73
166-169
Analog Cooling Range
P74
170-173
Analog
----
P75
174-177
Analog
----
P76
178-181
Analog
SYS 1 Discharge
Temp.
(EEV Only-Optional)
P77
182-185
Analog
SYS 1 Discharge
Superheat
(EEV Only- Optional)
P78
186-189
Analog
SYS 2 Discharge
Temp.
(EEV Only- Optional)
P79
190-193
Analog
SYS 2 Discharge
Superheat
(EEV Only- Optional)
P80
194
Digital
----
P81
195
Digital
----
P82
196
Digital
----
P83
197
Digital
----
P84
198
Digital
----
* The operational and fault codes sent to ISN pages 56 through 59 are defined in Table 35. Note that this table of fault and operational codes
is for all DX products.
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...