JOHNSON CONTROLS
116
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
SECTION 7 – UNIT CONTROLS
TABLE 14 -
COOLING SETPOINTS PROGRAMMABLE LIMITS AND DEFAULTS
SETPOINT VALUE
LOW LIMIT
HIGH LIMIT
DEFAULT
Discharge Air Temp. Setpoint
45.0 °F
70.0°F
44.0°F
7.2°C 21.1°C 12.7°C
Discharge Air Temp. Range
3.0°F 10.0°F 5.0°F
1.7°C 5.6°C 2.8°C
Suction Pressure Setpoints
102 PSIG
155 PSIG
122 PSIG
7.03 BARS
10.7 BARS
8.4 BARS
Suction Pressure Range
3 PSIG
16 PSIG
5 PSIG
0.21 BARS
1.1 BARS
0.34 BARS
Max EMS - PWM Remote Temp. Reset
2°F
40°F 20°F
1°C 22°C 11°C
TABLE 15 -
PROGRAM KEY LIMITS AND DEFAULTS
* The minimum discharge pressure allowed is 160 PSIG. The fan differential Off Pressure will be lowered to prevent going below 235 PSIG
based on where the fan control On Pressure is programmed.
PROGRAM VALUE
MODE
LOW LIMIT
HIGH LIMIT
DEFAULT
DISCHARGE PRESSURE CUTOUT
--
325 PSIG
575 PSIG
570 PSIG
22.4 BARG
39.6 BARG
39.3 BARG
SUCTION PRESSURE CUTOUT
800 PSIG
120.0 PSIG
80.0 PSIG
5.52 BARG
8.27 BARG
5.52 BARG
LOW AMBIENT TEMP. CUTOUT
STANDARD AMBIENT
25.0°F
60.0°F
25.0°F
-3.9°C
15.6°C
-3.9°C
LOW AMBIENT
0°F
60.0°F
25.0°F
-17.8°C
15.6°C
-3.9°C
ANTI-RECYCLE TIMER
--
300 SEC.
600 SEC.
600 SEC.
FAN CONTROL ON PRESSURE
--
360 PSIG
485 PSIG
385 PSIG
24.8 BARG
33.4 BARG
26.5 BARG
FAN DIFFERENTIAL OFF PRESSURE
--
80 PSIG
160 PSID*
125 PSID
5.51 BARG
11.03 BARG*
8.0 BARG
TOTAL NUMBER OF COMPRESSORS
SINGLE SYSTEM
2
3
3
TWO SYSTEMS
4
6
6
NUMBER OF FANS PER SYSTEM
YLUA0096 -
YLUA0140 ONLY
3
4
3
UNIT/SYSTEM TRIP VOLTS
CURRENT FEEDBACK
OPTION ENABLED
ONE PER UNIT
0.5 VOLTS
4.5 VOLTS
2 VOLTS
REMOTE UNIT ID
--
0
7
0
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...