SECTION 9 – SERVICE AND TROUBLESHOOTING
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
9
TROUBLESHOOTING (CONT’D)
CONT’D
PROBLEM
CAUSE
SOLUTION
“LOW SUCTION PRESSURE
FAULT”
1. Improper suction pressure cut-
outs adjustments.
2. Low refrigerant charge.
3. Fouled Filter Dryer.
4. TXV defective.
5. Reduced air flow.
6. Defective Suction Pressure
Transducer/Low Pressure
Switch or wiring.
7. LLSV defective.
1. Adjust per recommended set-
tings.
2. Repair leak if necessary and
add refrigerant.
3. Change Dryer/Core.
4. Replace TXV.
5. Check air flow.
6. Replace Transducer/Low Pres-
sure Switch or faulty wiring.
sure/voltage formula.
7. Replace LLSV.
“HIGH DISCHARGE PRESSURE”
FAULT
1. Condenser fans not operating
or operating backwards.
2. Too much refrigerant.
3. Air in refrigerant system.
4. Defective Discharge Pressure
Transducer.
1. Check Fan Motor, and Con-
tactors. Assure Fan blows air
upward.
2. Remove refrigerant.
3. Evacuate and recharge system.
4. Replace discharge pressure.
See S
ection 9 – SERVICE AND
TROUBLESHOOTING for pres-
sure/voltage formula.
“MP / HPCO” FAULT
1. Compressor Internal Motor
Protector (MP) open.
2. External overload tripped.
3. HPCO Switch open.
4. Defective HPCO Switch.
5. Defective CR Relay.
1. Verify refrigerant charge is not
low. Verify superheat setting of
10° F - 15° F (5.6° C - 8.3° C).
Verify compressor is not over
loaded.
2. Determine cause and reset.
3.
See “High Press. Disch.” Fault.
4. Replace HPCO Switch.
5. Replace Relay.
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...