JOHNSON CONTROLS
140
FORM 150.73-NM2
ISSUE DATE: 09/07/2020
SECTION 9 – SERVICE AND TROUBLESHOOTING
Discharge Air Temperature Sensor
J6-5
=
+5 VDC regulated supply to sensor.
J6-8
=
VDC input signal to the microboard.
See Table 31 for voltage readings that
correspond to specific discharge tem
-
peratures.
J6-2
=
drain (shield connection = 0 VDC)
Analog Inputs – Pressure
Refer to the unit wiring diagram.
Pressure inputs are
connected to the microboard on plugs J7 and J9. These
analog
inputs represent varying dc signals correspond-
ing to varying pressures. All voltages are in reference
to the unit case (ground).
System 1 discharge and suction pressures will be con-
nected to J7 of the microboard. System 2 discharge and
suction pressure transducers will be connected to J9 of
the microboard.
The discharge transducers are optional on all units. If
the discharge transducers are not installed, no connec-
tions are made to the microboard and the discharge
pressure readout on the display would be zero.
The suction pressure transducers are standard on all
YLUA’s. The suction pressure transducers have a
range of 0 to 400 PSIG. The output will be linear from
0.5VDC to 4.5VDC over the 400 PSIG (27.5 barg)
range.
The discharge transducers have a range from 0 to
650 PSIG. The output will be linear from 0.5VDC to
4.5VDC over the 650 PSIG (41.25 barg) range. Fol-
lowing is the formula that can be used to verify the
voltage output of the transducer. All voltage reading
are in reference to ground (unit case).
TABLE 29 -
DISCHARGE AIR TEMP. SENSOR
TEMPERATURE/VOLTAGE/
RESISTANCE CORRELATION
TEMP °F VOLTAGE RESISTANCE
TEMP °C
0
1.71
25619
-18
2
1.78
24046
-17
4
1.85
22580
-16
6
1.93
21214
-14
8
2.00
19939
-13
10
2.07
18749
-12
12
2.15
17637
-11
14
2.22
16599
-10
16
2.30
15629
-9
18
2.37
14721
-8
20
2.45
13872
-7
22
2.52
13077
-6
24
2.59
12333
-4
26
2.67
11636
-3
28
2.74
10982
-2
30
2.81
10370
-1
32
2.88
9795
0
34
2.95
9256
1
36
3.02
8750
2
38
3.08
8276
3
40
3.15
7830
4
42
3.21
7411
6
44
3.27
7017
7
46
3.33
6647
8
48
3.39
6298
9
50
3.45
5970
10
52
3.51
5661
11
54
3.56
5370
12
56
3.61
5096
13
58
3.67
4837
14
60
3.72
4593
16
62
3.76
4363
17
64
3.81
4145
18
66
3.86
3941
19
68
3.90
3747
20
70
3.94
3564
21
72
3.98
3392
22
74
4.02
3228
23
76
4.06
3074
24
78
4.10
2928
26
80
4.13
2790
27
Summary of Contents for YLUA0248 Series
Page 4: ...JOHNSON CONTROLS 4 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 10: ...JOHNSON CONTROLS 10 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 14: ...JOHNSON CONTROLS 14 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 30: ...JOHNSON CONTROLS 30 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 44: ...JOHNSON CONTROLS 44 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 55: ...JOHNSON CONTROLS 55 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 57: ...JOHNSON CONTROLS 57 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 59: ...JOHNSON CONTROLS 59 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 61: ...JOHNSON CONTROLS 61 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 63: ...JOHNSON CONTROLS 63 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 67: ...JOHNSON CONTROLS 67 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 73: ...JOHNSON CONTROLS 73 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 77: ...JOHNSON CONTROLS 77 SECTION 5 TECHNICAL DATA FORM 150 73 NM2 ISSUE DATE 09 07 2020 5 5 ...
Page 94: ...JOHNSON CONTROLS 94 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...
Page 124: ...JOHNSON CONTROLS 124 FORM 150 73 NM2 ISSUE DATE 09 07 2020 THIS PAGE INTENTIONALLY LEFT BLANK ...