![background image](http://html1.mh-extra.com/html/york/ylpa/ylpa_manual_4248590018.webp)
JOHNSON CONTROLS
18
FORM 150.68-EG1 (0212)
PERFORMANCE DATA - HEATING
Rated in accordance with AHRI Standard 550/590 based on sea level altitude, evaporator fouling factor of 0.0001°F-ft²h/
Btu, evaporator temperature drop of 10°F, and 2 pass evaporator confi guration.
MBH
COMP
KW
COP
MBH
COMP
KW
COP
MBH
COMP
KW
COP
MBH
COMP
KW
COP
115
1419.5
118.8
3.5
1501.9
118.8
3.7
1567.0
118.9
3.9
1632.0
118.9
4.0
145
1768.2
146.9
3.5
1871.0
147.0
3.7
1952.0
147.0
3.9
2033.0
147.0
4.1
170
2081.1
176.3
3.5
2202.0
176.4
3.7
2297.3
176.5
3.8
2392.7
176.5
4.0
115
1411.1
125.3
3.3
1494.4
125.5
3.5
1561.1
125.6
3.6
1627.7
125.7
3.8
145
1757.8
154.9
3.3
1861.6
155.2
3.5
1944.6
155.3
3.7
2027.6
155.4
3.8
170
2068.8
186.0
3.3
2191.0
186.3
3.4
2288.7
186.4
3.6
2386.3
186.6
3.7
115
1402.7
131.8
3.1
1486.9
132.1
3.3
1555.1
132.3
3.4
1623.4
132.5
3.6
145
1747.4
163.0
3.1
1852.3
163.4
3.3
1937.2
163.6
3.5
2022.2
163.8
3.6
170
2056.5
195.7
3.1
2180.0
196.2
3.3
2280.0
196.4
3.4
2380.0
196.7
3.5
115
1394.4
138.3
3.0
1479.4
138.8
3.1
1549.2
139.0
3.3
1619.0
139.3
3.4
145
1736.9
171.0
3.0
1842.9
171.6
3.1
1929.9
171.9
3.3
2016.8
172.2
3.4
170
2044.3
205.3
2.9
2169.0
206.0
3.1
2271.3
206.4
3.2
2373.7
206.7
3.4
115
1389.3
142.2
2.9
1474.9
142.8
3.0
1545.7
143.1
3.2
1616.4
143.3
3.3
145
1730.7
175.9
2.9
1837.3
176.5
3.0
1925.4
176.9
3.2
2013.6
177.2
3.3
170
2036.9
211.1
2.8
2162.4
211.9
3.0
2266.1
212.3
3.1
2369.9
212.8
3.3
115
1386.0
144.8
2.8
1471.9
145.4
3.0
1543.3
145.7
3.1
1614.7
146.0
3.2
145
1726.5
179.1
2.8
1833.6
179.8
3.0
1922.5
180.2
3.1
2011.4
180.6
3.3
170
2032.0
215.0
2.8
2158.0
215.9
2.9
2262.7
216.3
3.1
2367.3
216.8
3.2
115
1375.9
151.5
2.7
1464.4
152.1
2.8
1537.4
152.5
3.0
1610.4
152.8
3.1
145
1713.9
187.3
2.7
1824.2
188.0
2.8
1915.1
188.5
3.0
2006.0
189.0
3.1
170
2017.2
224.8
2.6
2147.0
225.8
2.8
2254.0
226.3
2.9
2361.0
226.9
3.0
115
1364.2
160.8
2.5
1453.7
161.6
2.6
1527.5
161.8
2.8
1601.4
162.1
2.9
145
1699.4
198.8
2.5
1810.8
199.8
2.7
1902.8
200.1
2.8
1994.8
200.4
2.9
170
2000.1
238.6
2.5
2131.3
239.9
2.6
2239.5
240.2
2.7
2347.8
240.6
2.9
115
1352.6
170.1
2.3
1442.9
171.1
2.5
1517.6
171.2
2.6
1592.3
171.3
2.7
145
1684.9
210.3
2.3
1797.5
211.5
2.5
1890.5
211.7
2.6
1983.5
211.8
2.7
170
1983.0
252.4
2.3
2115.5
254.0
2.4
2225.0
254.1
2.6
2334.5
254.3
2.7
NOTES:
1. COMP kW = Compressor Input Power
2. COP = Heat Pumps COP (includes power from compressors, fans, and the control panels 0.8 kW)
3. LHWT = Leaving Hot Water Temperature
120
125
130
95
100
105
110
113
115
LHWT
(°F)
YLPA
MODEL
AIR TEMPERATURE ON - CONDENSER (°F)
44
50
55
60
Ratings - continued