background image

JOHNSON CONTROLS

8

FORM 150.68-EG1 (0212)

Application Data

LOCATION REQUIREMENTS

To achieve optimum performance and trouble-free service, 
it is essential that the proposed installation site meet with 
the location and space requirements for the model being 
installed.

The clearances recommended are nominal for the 
safe and effi cient operation and maintenance of the 
unit and power and control panels. Local Health and 
safety regulations, or practical considerations for service 
replacement of large components, may require larger 
clearances than those given in this manual.

OUTDOOR INSTALLATIONS

The units can be installed at ground level on a suitable at 
level foundation easily capable of supporting the weight of 
the unit, or on a suitable rooftop location. In both cases an 
adequate supply of air is required. Avoid locations where 
the sound output and air discharge from the unit may be 
objectionable.

The location should be selected for minimum sun 
exposure and away from boiler fl ues and other sources of 
airborne chemicals that could attack the condenser coils 
and steel parts of the unit.

If located in an area accessible to unauthorized persons, 
steps must be taken to prevent access to the unit by 
means of a protective fence. This will help to prevent the 
possibility of vandalism, accidental damage, or possible 
harm caused by unauthorized removal of protective 
guards or opening panels to expose rotating or electrically 
live components.

For ground level locations, the unit must be installed 
on a suitable fl at and level concrete base that extends 
to  fully support the two side channels of the unit base 
frame. A one-piece concrete slab, with footings extending 
below the frost line is recommended. To avoid noise and 
vibration transmission, the unit should not be secured to 
the building foundation.

On rooftop locations, choose a place with adequate 
structural strength to safely support the entire operating 
weight of the unit and service personnel. The unit can 
be mounted on a concrete slab, similar to ground fl oor 
locations, or on steel channels of suitable strength. The 
channels should be spaced with the same centres as 
the unit side and front base rails. This will allow vibration 
isolators to be fi tted if required. Isolators are recommended 
for rooftop locations.

LOCATION CLEARANCES

Adequate clearances around the unit(s) are required 
for the unrestricted air-fl ow for the ambient coils and to 
prevent re-circulation of discharge air back onto the coils. 
If clearances given are not maintained, air-fl ow restriction 
or re-circulation will cause a loss of unit performance, an 
increase in power consumption, and may cause the unit 
to malfunction. Consideration should also be given to the 
possibility of down drafts, caused by adjacent buildings, 
which may cause re-circulation or uneven unit air-fl ow.

For locations where signifi cant cross winds are expected, 
such as exposed roof tops, an enclosure of solid or 
louvre type is recommended to prevent wind turbulence 
interfering with the unit air-fl ow.

When units are installed in an enclosure, the enclosure 
height should not exceed the height of the unit on more 
than one side. Where accumulation of snow is likely, 
additional height must be provided under the unit to ensure 
normal air-fl ow to the unit.

Refer to the table below and the diagrams on the following 
page for location clearances.

0115SE 0145SE 0170SE

A

47

47

47

B

32

32

32

C

32

39

47

D

55

55

55

A

47

47

47

B

32

32

32

C

32

39

47

D

106

126

126

E

55

55

55

A

47

47

47

B

32

32

32

C

32

39

47

D

91

118

126

E

55

55

55

A

47

47

47

B

47

47

47

C

32

32

32

D

32

39

47

E

67

75

83

A

47

47

47

B

47

47

47

C

32

32

32

D

32

32

32

E

55

55

55

YLPA 

Arrangement 

A5

Louvres on 

2 walls

Dim.

(in)

Arrangement

A1

Solid Walls

Arrangement 

A2

Solid Walls

Arrangement 

A3

Louvres on 

2 walls

Arrangement 

A4

Solid Walls

Summary of Contents for YLPA

Page 1: ...ling Capacities 115 Tons to 170 Tons Cooling Capacities 400 kW to 600 kW Heating Capacities 1390 MBH to 2040 MBH Heating Capacities 400 kW to 600 kW 60Hz HFC 410A Model YLPA Air to Liquid Reversible S...

Page 2: ...5 6 7 8 9 10 11 12 13 14 15 BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATION REFRIGERANT VOLTAGE STARTER DESIGN DEVELOPMENT LEVEL Y York kW S Standard Unit E R 410A 4 0 X 380 3 60 B Design Series...

Page 3: ...core filter drier a sight glass with moisture indicator a cooling mode thermal expansion valve and a heat pump mode thermal expansion valve Suction lines shall be covered with closed cell insulation R...

Page 4: ...out High discharge pressure cutout Anti recycle timer compressor start cycle time Anti coincident timer delay compressor starts Displayed Data Leaving liquid temperature Air coil defrost temperatures...

Page 5: ...d mounted 2 SPRING ISOLATORS Restrained Spring Flex Mountings incorporating a rugged welded steel housing with vertical and horizontal limit stops Field mounted FLANGE KIT Provides contractor with the...

Page 6: ...es the direction of the refrigerant flow and the function of the heat exchanger to heating mode and the accumulator and enters the compressor where pressure and superheat are increased High pressure s...

Page 7: ...s 4 Compressors 8 Fans WEIGHTS AND WEIGHT DISTRIBUTION The weights and weight distribution are given below Model Shipping Operating R1 R2 R3 R4 L1 L2 L3 L4 0115SE 9811 10472 1864 1026 1414 2178 1822 2...

Page 8: ...ion On rooftop locations choose a place with adequate structural strength to safely support the entire operating weight of the unit and service personnel The unit can be mounted on a concrete slab sim...

Page 9: ...FORM 150 68 EG1 0212 9 JOHNSON CONTROLS A1 A B C D E A1 C C D D E A B C D A1 A4 A A B B A2 A3 A5 A B C D E E...

Page 10: ...changer s should be readily demountable to enable cleaning prior to operation and to facilitate visual inspection of the exchanger nozzles Each heat exchanger must be protected by a strainer preferabl...

Page 11: ...must meet the requirements detailed in the table below Water quality should be inspected before unit installation and regularly during unit operation The water quality must meet the limits above If pa...

Page 12: ...ay be wired into the unit This device should be rated at 20 amps 115V AC 15 The device should be wired into terminals L and 5 in the power panel after removing the factory fitted link CONTROL WIRING V...

Page 13: ...ction against loss of liquid flow Remote Start Stop Connect a remote switch to terminals 13 and 51 to provide remote start stop control if required Remote Mode Selection Remote mode selection can be a...

Page 14: ...13 15 13 20 13 21 13 50 13 51 A A STATUS SYSTEM STATUS SYSTEM 1 ALARM STAT 2 ALARM STAT P START CONTA ODE INDICATIO VERY OPTION O E START STOP FLOW SWITCH D INHIBIT N OPTION ONLY D FOR HEATING AGE LOA...

Page 15: ...0212 15 JOHNSON CONTROLS Water Pressure Drop Refrigerant to Water Heat Exchanger Pressure Drop Graph Pressure Drop ft H 2 O 100 Flow Rate gpm 200 300 600 400 1000 800 3 5 10 15 20 30 40 50 60 80 0170S...

Page 16: ...5 123 2 11 7 129 3 129 5 10 8 145 14 8 180 7 133 2 14 4 175 9 139 5 13 5 171 0 146 4 12 6 165 9 153 8 11 7 160 7 161 6 10 8 170 14 2 205 9 158 5 13 8 200 6 166 1 12 9 195 0 174 4 12 0 189 2 183 3 11 1...

Page 17: ...0 0 15 6 25 0 34 7 20 5 55 0 17 4 25 0 17 1 Displ Ambient F TONS COMP KW EER LOAD EER 100 0 146 3 157 3 95 0 10 1 100 0 10 1 80 0 126 6 112 2 86 9 11 8 75 0 13 1 60 0 100 0 73 6 76 0 13 8 50 0 15 8 40...

Page 18: ...73 7 206 7 3 4 115 1389 3 142 2 2 9 1474 9 142 8 3 0 1545 7 143 1 3 2 1616 4 143 3 3 3 145 1730 7 175 9 2 9 1837 3 176 5 3 0 1925 4 176 9 3 2 2013 6 177 2 3 3 170 2036 9 211 1 2 8 2162 4 211 9 3 0 226...

Page 19: ...5V 3 60Hz nominal 6 to 15 0170SE 0145SE 0115SE 95 to 131 YLPA 39 to 59 6 to 15 Cooling Mode 32 to 115 1 0115SE 0145SE 0170SE Number of refrigerant circuits Refrigerant Charge 1 System 1 System 2 lb 13...

Page 20: ...ressor RLA each compressor A 54 5 54 5 54 5 Compressor LRA each compressor A 310 310 310 Compressor Heater Supply V Hz 115 1 60 115 1 60 115 1 60 Compressor Heater Load W 600 750 900 Number of Fans Sy...

Page 21: ...6 1 1 5 4 7 Dimensions 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat e...

Page 22: ...7 1 2 3 Dimensions continued 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to...

Page 23: ...6 1 1 5 4 7 1 2 3 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat excha...

Page 24: ...FORM 150 68 EG1 0212 Subject to change without notice Revision 0 ALL RIGHTS RESERVED www johnsoncontrols com...

Reviews: