background image

JOHNSON CONTROLS

10

FORM 150.68-EG1 (0212)

INSTALLATION OF VIBRATION ISOLATORS

An optional set of vibration isolators can be supplied loose 
with each unit.

PIPEWORK CONNECTION

The following piping recommendations are intended to 
ensure satisfactory operation of the unit. Failure to follow 
these recommendations could cause damage to the unit, 
or loss of performance, and may invalidate the warranty.

A fl ow switch must be installed in the customer pipework 
at the outlet of the heat exchanger as shown in the 
arrangement diagrams, and wired back to the control 
panel using screened cable. This is to prevent damage 
to the heat exchanger caused by inadequate liquid fl ow. 
To prevent turbulent fl ow, there must be straight pipework 
either side of the fl ow switch equal in length to at least 5 
times the diameter of the pipe.

The fl ow switches used must have gold plated contacts 
for low voltage/current operation

Alternatively, a differential pressure switch fi tted  across 
an orifi ce plate may be used, preferably of the high/low 
limit type.

The liquid pumps installed in the pipework systems should 
discharge directly into the unit heat exchanger sections of 
the system. The pumps require an auto-starter (by others) 
to be wired to the control panel.

Pipework and fi ttings must be separately supported to 
prevent any loading on the heat exchanger(s). Flexible 
connections are recommended which will also minimize 
transmission of vibrations to the building. Flexible 
connections must be used if the unit is mounted on anti-
vibration mounts as some movement of the unit can be 
expected in normal operation.

Pipework and fittings immediately next to the heat 
exchanger(s) should be readily demountable to enable 
cleaning prior to operation, and to facilitate visual 
inspection of the exchanger nozzles.

Each heat exchanger must be protected by a strainer, 
preferably of 20 mesh, fi tted as close as possible to the 
liquid inlet connection, and provided with a means of local 
isolation.

The heat exchanger(s) must not be exposed to fl ushing 
velocities or debris released during flushing. It is 
recommended that a suitably sized by-pass and valve 
arrangement be installed to allow fl ushing of the pipework 
system. The by-pass can be used during maintenance to 
isolate the heat exchanger(s) without disrupting fl ow  to 
other units.

Thermometer and pressure gauge connections should 
be provided on the inlet and outlet connections of each 
heat exchanger.

Drain and air vent connections should be provided at all 
low and high points in the pipework to permit drainage of 
the system, and to vent any air in the pipes.

Liquid systems at risk of freezing, due to low ambient 
temperatures, should be protected using insulation and 
heater tape and/or a suitable glycol solution. The liquid 
pumps must also be used to ensure liquid is circulated 
when the ambient temperature approaches freezing 
point. Insulation should also be installed around the heat 
exchanger nozzles.

Heater tape under the insulation is recommended, 
supplied independantly and controlled by an ambient 
temperature thermostat set to switch on at approximately 
4ºF above the freezing temperature of the chilled liquid.

The heat exchanger is protected by a heater mat placed 
under the insulation, which are powered from the unit 
control system power supply. During cold weather when 
there is a risk of freezing, chiller power should be left 
switched on to provide the freeze protection function 
unless the liquid systems have been drained.

Application Data  - continued

Summary of Contents for YLPA

Page 1: ...ling Capacities 115 Tons to 170 Tons Cooling Capacities 400 kW to 600 kW Heating Capacities 1390 MBH to 2040 MBH Heating Capacities 400 kW to 600 kW 60Hz HFC 410A Model YLPA Air to Liquid Reversible S...

Page 2: ...5 6 7 8 9 10 11 12 13 14 15 BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATION REFRIGERANT VOLTAGE STARTER DESIGN DEVELOPMENT LEVEL Y York kW S Standard Unit E R 410A 4 0 X 380 3 60 B Design Series...

Page 3: ...core filter drier a sight glass with moisture indicator a cooling mode thermal expansion valve and a heat pump mode thermal expansion valve Suction lines shall be covered with closed cell insulation R...

Page 4: ...out High discharge pressure cutout Anti recycle timer compressor start cycle time Anti coincident timer delay compressor starts Displayed Data Leaving liquid temperature Air coil defrost temperatures...

Page 5: ...d mounted 2 SPRING ISOLATORS Restrained Spring Flex Mountings incorporating a rugged welded steel housing with vertical and horizontal limit stops Field mounted FLANGE KIT Provides contractor with the...

Page 6: ...es the direction of the refrigerant flow and the function of the heat exchanger to heating mode and the accumulator and enters the compressor where pressure and superheat are increased High pressure s...

Page 7: ...s 4 Compressors 8 Fans WEIGHTS AND WEIGHT DISTRIBUTION The weights and weight distribution are given below Model Shipping Operating R1 R2 R3 R4 L1 L2 L3 L4 0115SE 9811 10472 1864 1026 1414 2178 1822 2...

Page 8: ...ion On rooftop locations choose a place with adequate structural strength to safely support the entire operating weight of the unit and service personnel The unit can be mounted on a concrete slab sim...

Page 9: ...FORM 150 68 EG1 0212 9 JOHNSON CONTROLS A1 A B C D E A1 C C D D E A B C D A1 A4 A A B B A2 A3 A5 A B C D E E...

Page 10: ...changer s should be readily demountable to enable cleaning prior to operation and to facilitate visual inspection of the exchanger nozzles Each heat exchanger must be protected by a strainer preferabl...

Page 11: ...must meet the requirements detailed in the table below Water quality should be inspected before unit installation and regularly during unit operation The water quality must meet the limits above If pa...

Page 12: ...ay be wired into the unit This device should be rated at 20 amps 115V AC 15 The device should be wired into terminals L and 5 in the power panel after removing the factory fitted link CONTROL WIRING V...

Page 13: ...ction against loss of liquid flow Remote Start Stop Connect a remote switch to terminals 13 and 51 to provide remote start stop control if required Remote Mode Selection Remote mode selection can be a...

Page 14: ...13 15 13 20 13 21 13 50 13 51 A A STATUS SYSTEM STATUS SYSTEM 1 ALARM STAT 2 ALARM STAT P START CONTA ODE INDICATIO VERY OPTION O E START STOP FLOW SWITCH D INHIBIT N OPTION ONLY D FOR HEATING AGE LOA...

Page 15: ...0212 15 JOHNSON CONTROLS Water Pressure Drop Refrigerant to Water Heat Exchanger Pressure Drop Graph Pressure Drop ft H 2 O 100 Flow Rate gpm 200 300 600 400 1000 800 3 5 10 15 20 30 40 50 60 80 0170S...

Page 16: ...5 123 2 11 7 129 3 129 5 10 8 145 14 8 180 7 133 2 14 4 175 9 139 5 13 5 171 0 146 4 12 6 165 9 153 8 11 7 160 7 161 6 10 8 170 14 2 205 9 158 5 13 8 200 6 166 1 12 9 195 0 174 4 12 0 189 2 183 3 11 1...

Page 17: ...0 0 15 6 25 0 34 7 20 5 55 0 17 4 25 0 17 1 Displ Ambient F TONS COMP KW EER LOAD EER 100 0 146 3 157 3 95 0 10 1 100 0 10 1 80 0 126 6 112 2 86 9 11 8 75 0 13 1 60 0 100 0 73 6 76 0 13 8 50 0 15 8 40...

Page 18: ...73 7 206 7 3 4 115 1389 3 142 2 2 9 1474 9 142 8 3 0 1545 7 143 1 3 2 1616 4 143 3 3 3 145 1730 7 175 9 2 9 1837 3 176 5 3 0 1925 4 176 9 3 2 2013 6 177 2 3 3 170 2036 9 211 1 2 8 2162 4 211 9 3 0 226...

Page 19: ...5V 3 60Hz nominal 6 to 15 0170SE 0145SE 0115SE 95 to 131 YLPA 39 to 59 6 to 15 Cooling Mode 32 to 115 1 0115SE 0145SE 0170SE Number of refrigerant circuits Refrigerant Charge 1 System 1 System 2 lb 13...

Page 20: ...ressor RLA each compressor A 54 5 54 5 54 5 Compressor LRA each compressor A 310 310 310 Compressor Heater Supply V Hz 115 1 60 115 1 60 115 1 60 Compressor Heater Load W 600 750 900 Number of Fans Sy...

Page 21: ...6 1 1 5 4 7 Dimensions 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat e...

Page 22: ...7 1 2 3 Dimensions continued 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to...

Page 23: ...6 1 1 5 4 7 1 2 3 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat excha...

Page 24: ...FORM 150 68 EG1 0212 Subject to change without notice Revision 0 ALL RIGHTS RESERVED www johnsoncontrols com...

Reviews: