background image

JOHNSON CONTROLS

12

FORM 150.68-EG1 (0212)

ELECTRICAL CONNECTION

The following connection recommendations are intended 
to ensure safe and satisfactory operation of the unit. 
Failure to follow these recommendations could cause 
harm to persons, or damage to the unit, and may invalidate 
the warranty. 

No additional controls (relays, etc.) should be mounted in 
the control panel. Power and control wiring not connected 
to the control panel should not be run through the control 
panel. If these precautions are not followed it could lead 
to a risk of electrocution. In addition, electrical noise could 
cause malfunctions or damage the unit and its controls.

POWER WIRING

These units are suitable for 460 V, 3-phase, 60Hz nominal 
supplies only.

All electrical wiring should be carried out in accordance 
with local regulations. Route properly sized cables to the 
cable entries in the bottom of the power panel.

It is the responsibility of the user to install over current 
protection devices between the supply conductors and 
the power supply terminals on the unit. 

To ensure that no eddy currents are set up in the power 
panel, the cables forming each 3 phase power supply 
must enter via the same cable entry. 

All sources of supply to the unit must be taken via a 
common point of isolation (not supplied by JCI).

SINGLE POINT POWER SUPPLY WIRING

All models require one fi eld provided 460 V, 3Ø, 60 Hz 
+ PE (Protected Earth) supply to the unit with circuit 
protection. 

Connect the 3-phase supply to the non-fused disconnect 
switch located in the power panel using M12 lugs. 

Connect the earth wire to the main protective earth 
terminal located in the power panel using a M10 lug.

CONTROL CIRCUIT TRANSFORMER

The control circuit transformer providing the 115 V, 
1Ø, 50Hz supply to the unit control system is fi tted in a 
separate enclosure.

REMOTE EMERGENCY STOP DEVICE

If required, a remote emergency stop device may be wired 
into the unit. This device should be rated at 20 amps, 115V, 
AC-15. The device should be wired into terminals L and 
5 in the power panel after removing the factory fi tted link.

CONTROL WIRING - VOLTAGE FREE CONTACT

All wiring to the voltage free contact terminal block requires 
a supply provided by the customer maximum voltage 
115Vac, 24 Vdc. 

The customer must take particular care deriving the 
supplies for the voltage free terminals with regard to a 
common point of isolation. Thus, these circuits when 
used must be fed via the common point of isolation so the 
voltage to these circuits is removed when the common 
point of isolation to the unit is opened. This common point 
of isolation is not supplied by JCI.

It is recommended that the customer wiring to these 
terminals uses orange wires. This will ensure that circuits 
not switched off by the units supply disconnecting device 
are distinguished by colour, so that they can easily be 
identifi ed as live even when the unit disconnecting devices 
are off. The YORK voltage free contacts are rated at 125 
VA. 

All inductive devices (relays) switched by the YORK 
voltage free contacts must have their coil suppressed 
using standard RC suppressors. If these precautions are 
not followed, electrical noise could cause malfunctions or 
damage to the unit and its controls.

Chilled Liquid Pump Starter

Terminals 23 and 24 close to start the liquid pump. This 
contact is closed if there is a ‘Leaving Liquid Temperature 
Cutout’ or any of the compressors are running or the 
daily schedule is not calling for a shutdown with the unit 
switch on. 

The contact must be used to ensure that the pump is 
running in the event of a ‘Leaving Liquid Temperature 
Cutout’. 

The pump contact will not close to run the pump if the unit 
has been powered up for less than 30 seconds, or if the 
pump has run in the last 30 seconds, to prevent pump 
motor overheating.

Run Contacts

Terminals 25 and 26 close to indicate that refrigerant 
system 1 is running and terminals 27 and 28 close to 
indicate that refrigerant system 2 is running.

Application Data  - continued

Summary of Contents for YLPA

Page 1: ...ling Capacities 115 Tons to 170 Tons Cooling Capacities 400 kW to 600 kW Heating Capacities 1390 MBH to 2040 MBH Heating Capacities 400 kW to 600 kW 60Hz HFC 410A Model YLPA Air to Liquid Reversible S...

Page 2: ...5 6 7 8 9 10 11 12 13 14 15 BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATION REFRIGERANT VOLTAGE STARTER DESIGN DEVELOPMENT LEVEL Y York kW S Standard Unit E R 410A 4 0 X 380 3 60 B Design Series...

Page 3: ...core filter drier a sight glass with moisture indicator a cooling mode thermal expansion valve and a heat pump mode thermal expansion valve Suction lines shall be covered with closed cell insulation R...

Page 4: ...out High discharge pressure cutout Anti recycle timer compressor start cycle time Anti coincident timer delay compressor starts Displayed Data Leaving liquid temperature Air coil defrost temperatures...

Page 5: ...d mounted 2 SPRING ISOLATORS Restrained Spring Flex Mountings incorporating a rugged welded steel housing with vertical and horizontal limit stops Field mounted FLANGE KIT Provides contractor with the...

Page 6: ...es the direction of the refrigerant flow and the function of the heat exchanger to heating mode and the accumulator and enters the compressor where pressure and superheat are increased High pressure s...

Page 7: ...s 4 Compressors 8 Fans WEIGHTS AND WEIGHT DISTRIBUTION The weights and weight distribution are given below Model Shipping Operating R1 R2 R3 R4 L1 L2 L3 L4 0115SE 9811 10472 1864 1026 1414 2178 1822 2...

Page 8: ...ion On rooftop locations choose a place with adequate structural strength to safely support the entire operating weight of the unit and service personnel The unit can be mounted on a concrete slab sim...

Page 9: ...FORM 150 68 EG1 0212 9 JOHNSON CONTROLS A1 A B C D E A1 C C D D E A B C D A1 A4 A A B B A2 A3 A5 A B C D E E...

Page 10: ...changer s should be readily demountable to enable cleaning prior to operation and to facilitate visual inspection of the exchanger nozzles Each heat exchanger must be protected by a strainer preferabl...

Page 11: ...must meet the requirements detailed in the table below Water quality should be inspected before unit installation and regularly during unit operation The water quality must meet the limits above If pa...

Page 12: ...ay be wired into the unit This device should be rated at 20 amps 115V AC 15 The device should be wired into terminals L and 5 in the power panel after removing the factory fitted link CONTROL WIRING V...

Page 13: ...ction against loss of liquid flow Remote Start Stop Connect a remote switch to terminals 13 and 51 to provide remote start stop control if required Remote Mode Selection Remote mode selection can be a...

Page 14: ...13 15 13 20 13 21 13 50 13 51 A A STATUS SYSTEM STATUS SYSTEM 1 ALARM STAT 2 ALARM STAT P START CONTA ODE INDICATIO VERY OPTION O E START STOP FLOW SWITCH D INHIBIT N OPTION ONLY D FOR HEATING AGE LOA...

Page 15: ...0212 15 JOHNSON CONTROLS Water Pressure Drop Refrigerant to Water Heat Exchanger Pressure Drop Graph Pressure Drop ft H 2 O 100 Flow Rate gpm 200 300 600 400 1000 800 3 5 10 15 20 30 40 50 60 80 0170S...

Page 16: ...5 123 2 11 7 129 3 129 5 10 8 145 14 8 180 7 133 2 14 4 175 9 139 5 13 5 171 0 146 4 12 6 165 9 153 8 11 7 160 7 161 6 10 8 170 14 2 205 9 158 5 13 8 200 6 166 1 12 9 195 0 174 4 12 0 189 2 183 3 11 1...

Page 17: ...0 0 15 6 25 0 34 7 20 5 55 0 17 4 25 0 17 1 Displ Ambient F TONS COMP KW EER LOAD EER 100 0 146 3 157 3 95 0 10 1 100 0 10 1 80 0 126 6 112 2 86 9 11 8 75 0 13 1 60 0 100 0 73 6 76 0 13 8 50 0 15 8 40...

Page 18: ...73 7 206 7 3 4 115 1389 3 142 2 2 9 1474 9 142 8 3 0 1545 7 143 1 3 2 1616 4 143 3 3 3 145 1730 7 175 9 2 9 1837 3 176 5 3 0 1925 4 176 9 3 2 2013 6 177 2 3 3 170 2036 9 211 1 2 8 2162 4 211 9 3 0 226...

Page 19: ...5V 3 60Hz nominal 6 to 15 0170SE 0145SE 0115SE 95 to 131 YLPA 39 to 59 6 to 15 Cooling Mode 32 to 115 1 0115SE 0145SE 0170SE Number of refrigerant circuits Refrigerant Charge 1 System 1 System 2 lb 13...

Page 20: ...ressor RLA each compressor A 54 5 54 5 54 5 Compressor LRA each compressor A 310 310 310 Compressor Heater Supply V Hz 115 1 60 115 1 60 115 1 60 Compressor Heater Load W 600 750 900 Number of Fans Sy...

Page 21: ...6 1 1 5 4 7 Dimensions 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat e...

Page 22: ...7 1 2 3 Dimensions continued 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to...

Page 23: ...6 1 1 5 4 7 1 2 3 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat excha...

Page 24: ...FORM 150 68 EG1 0212 Subject to change without notice Revision 0 ALL RIGHTS RESERVED www johnsoncontrols com...

Reviews: