background image

FORM 150.68-EG1 (0212)

13

JOHNSON CONTROLS

Alarm Contacts

Each refrigerant system has a voltage-free normally open 
contact that will close when control power is applied to 
the panel, if no fault conditions are present. When a fault 
occurs which locks a system out, or there is a power 
failure the contact opens. To obtain a system alarm signal, 
connect the alarm circuit to terminals 29 and 30 for No. 1 
system and terminals 31 and 32 for No. 2 system.

Control Wiring - System Inputs

All wiring to the control terminal block (nominal 30 Vdc) 
must be run in screened cable, with the screen earthed at 
the panel end only. Run screened cable separately from 
mains cable to avoid electrical noise pick-up. 

The voltage free contacts must be suitable for 30 Vdc (gold 
contacts recommended). If the voltage free contacts form 
part of a relay or contactor, the coil of the device must be 
suppressed using a standard RC suppressor. The above 
precautions must be taken to avoid electrical noise that 
could cause a malfunction or damage to the unit and its 
controls.

Flow Switch

A chilled liquid flow switch of suitable type must be 
connected to terminals 13 and 14 to provide adequate 
protection against loss of liquid fl ow.

Remote Start/Stop

Connect a remote switch to terminals 13 and 51 to provide 
remote start/stop control if required.

Remote Mode Selection

Remote mode selection can be accomplished by 
connecting a contact between terminals 13 and 50. With 
the contact open the unit is in the cooling mode, with the 
contact closed the unit is in the heating mode.

Remote Reset of Chilled Liquid Setpoint

The PWM input (terminals 13 and 20) allows reset of 
the chilled liquid setpoint by supplying a ‘timed’ contact 
closure.

Remote Load Limiting

Load limiting prevents the unit from loading beyond a 
desired value. The unit % load limit depends on the 
number of compressors on the unit. The load limit inputs 
to terminals 13 and 21 work in conjunction with the PWM 
input to terminals 13 and 20.

Fan Full Speed Inhibit

To reduce unit noise the fans can be limited to run at a 
maximum step of all fans in star (reduced speed) i.e. fan 
full speed is inhibited. Connect a customer voltage free 
contact to terminals 13 & 15.

EMS Analogue Input

Provides a means of resetting the leaving chilled or hot 
liquid temperature from the BAS/EMS. Accepts 4 to 20 
mA, 0 to 20 mA, 0 to 10 Vdc or 2-10 Vdc. Connect to 
terminal A+ and A-.

Modbus, BACnet MS/TP and N2

Enable communications with building protocol systems 
using Modbus, BACnet or N2 protocol. Connect through 
standard RS485 port.

Summary of Contents for YLPA

Page 1: ...ling Capacities 115 Tons to 170 Tons Cooling Capacities 400 kW to 600 kW Heating Capacities 1390 MBH to 2040 MBH Heating Capacities 400 kW to 600 kW 60Hz HFC 410A Model YLPA Air to Liquid Reversible S...

Page 2: ...5 6 7 8 9 10 11 12 13 14 15 BASE PRODUCT TYPE NOMINAL CAPACITY UNIT DESIGNATION REFRIGERANT VOLTAGE STARTER DESIGN DEVELOPMENT LEVEL Y York kW S Standard Unit E R 410A 4 0 X 380 3 60 B Design Series...

Page 3: ...core filter drier a sight glass with moisture indicator a cooling mode thermal expansion valve and a heat pump mode thermal expansion valve Suction lines shall be covered with closed cell insulation R...

Page 4: ...out High discharge pressure cutout Anti recycle timer compressor start cycle time Anti coincident timer delay compressor starts Displayed Data Leaving liquid temperature Air coil defrost temperatures...

Page 5: ...d mounted 2 SPRING ISOLATORS Restrained Spring Flex Mountings incorporating a rugged welded steel housing with vertical and horizontal limit stops Field mounted FLANGE KIT Provides contractor with the...

Page 6: ...es the direction of the refrigerant flow and the function of the heat exchanger to heating mode and the accumulator and enters the compressor where pressure and superheat are increased High pressure s...

Page 7: ...s 4 Compressors 8 Fans WEIGHTS AND WEIGHT DISTRIBUTION The weights and weight distribution are given below Model Shipping Operating R1 R2 R3 R4 L1 L2 L3 L4 0115SE 9811 10472 1864 1026 1414 2178 1822 2...

Page 8: ...ion On rooftop locations choose a place with adequate structural strength to safely support the entire operating weight of the unit and service personnel The unit can be mounted on a concrete slab sim...

Page 9: ...FORM 150 68 EG1 0212 9 JOHNSON CONTROLS A1 A B C D E A1 C C D D E A B C D A1 A4 A A B B A2 A3 A5 A B C D E E...

Page 10: ...changer s should be readily demountable to enable cleaning prior to operation and to facilitate visual inspection of the exchanger nozzles Each heat exchanger must be protected by a strainer preferabl...

Page 11: ...must meet the requirements detailed in the table below Water quality should be inspected before unit installation and regularly during unit operation The water quality must meet the limits above If pa...

Page 12: ...ay be wired into the unit This device should be rated at 20 amps 115V AC 15 The device should be wired into terminals L and 5 in the power panel after removing the factory fitted link CONTROL WIRING V...

Page 13: ...ction against loss of liquid flow Remote Start Stop Connect a remote switch to terminals 13 and 51 to provide remote start stop control if required Remote Mode Selection Remote mode selection can be a...

Page 14: ...13 15 13 20 13 21 13 50 13 51 A A STATUS SYSTEM STATUS SYSTEM 1 ALARM STAT 2 ALARM STAT P START CONTA ODE INDICATIO VERY OPTION O E START STOP FLOW SWITCH D INHIBIT N OPTION ONLY D FOR HEATING AGE LOA...

Page 15: ...0212 15 JOHNSON CONTROLS Water Pressure Drop Refrigerant to Water Heat Exchanger Pressure Drop Graph Pressure Drop ft H 2 O 100 Flow Rate gpm 200 300 600 400 1000 800 3 5 10 15 20 30 40 50 60 80 0170S...

Page 16: ...5 123 2 11 7 129 3 129 5 10 8 145 14 8 180 7 133 2 14 4 175 9 139 5 13 5 171 0 146 4 12 6 165 9 153 8 11 7 160 7 161 6 10 8 170 14 2 205 9 158 5 13 8 200 6 166 1 12 9 195 0 174 4 12 0 189 2 183 3 11 1...

Page 17: ...0 0 15 6 25 0 34 7 20 5 55 0 17 4 25 0 17 1 Displ Ambient F TONS COMP KW EER LOAD EER 100 0 146 3 157 3 95 0 10 1 100 0 10 1 80 0 126 6 112 2 86 9 11 8 75 0 13 1 60 0 100 0 73 6 76 0 13 8 50 0 15 8 40...

Page 18: ...73 7 206 7 3 4 115 1389 3 142 2 2 9 1474 9 142 8 3 0 1545 7 143 1 3 2 1616 4 143 3 3 3 145 1730 7 175 9 2 9 1837 3 176 5 3 0 1925 4 176 9 3 2 2013 6 177 2 3 3 170 2036 9 211 1 2 8 2162 4 211 9 3 0 226...

Page 19: ...5V 3 60Hz nominal 6 to 15 0170SE 0145SE 0115SE 95 to 131 YLPA 39 to 59 6 to 15 Cooling Mode 32 to 115 1 0115SE 0145SE 0170SE Number of refrigerant circuits Refrigerant Charge 1 System 1 System 2 lb 13...

Page 20: ...ressor RLA each compressor A 54 5 54 5 54 5 Compressor LRA each compressor A 310 310 310 Compressor Heater Supply V Hz 115 1 60 115 1 60 115 1 60 Compressor Heater Load W 600 750 900 Number of Fans Sy...

Page 21: ...6 1 1 5 4 7 Dimensions 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat e...

Page 22: ...7 1 2 3 Dimensions continued 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to...

Page 23: ...6 1 1 5 4 7 1 2 3 1 Distance between anti vibration mounts 2 Power cable entry via gland plate 3 Control cable entry 4 Water inlet connection to heat exchanger 5 Water outlet connection to heat excha...

Page 24: ...FORM 150 68 EG1 0212 Subject to change without notice Revision 0 ALL RIGHTS RESERVED www johnsoncontrols com...

Reviews: