FORM 150.68-EG1 (0212)
19
JOHNSON CONTROLS
Technical Data
OPERATING LIMTATIONS
PHYSICAL DATA
Min.
Max.
Min.
Max.
Min.
Max.
Liquid Outlet Temperature (Water)
°F
Liquid Outlet Temperature Range (
T)
°F
Air Temperature - Standard Unit
°F
Liquid Outlet Temperature (Water)
°F
Liquid Outlet Temperature Range (
T)
°F
Air Temperature - Standard Unit
°F
gpm
181
700
181
700
200
850
ftH
2
O
5.4
43.0
5.4
43.0
3.4
55.4
psi
psi
V
(1) Unit may operate unloaded up to 125ºFdepending on model size and site conditions.
(2) Tol/-10%
Power Supply Voltage
(2)
Heating
Mode
Maximum Refrigerant Side Pressure
Heat Exchanger Flow Rate
Maximum Water Side Pressure
Heat Exchanger Presssure Drop
14 to 95
150
650
200V 3Ø, 60Hz (nominal)
230V 3Ø, 60Hz (nominal)
380V 3Ø, 60Hz (nominal)
460V 3Ø, 60Hz (nominal)
575V 3Ø, 60Hz (nominal)
6 to 15
0170SE
0145SE
0115SE
95 to 131
YLPA
39 to 59
6 to 15
Cooling
Mode
32 to 115
(1)
0115SE
0145SE
0170SE
Number of refrigerant circuits
Refrigerant Charge
(1)
System 1 / System 2
lb
130 / 137
181 / 132
181 / 181
Oil Charge
System 1 / System 2
lb
24.2 / 24.2
37.4 / 24.2
37.4 / 37.4
Number of compressors
2 / 2
3 / 2
3 / 3
Type
Number
Type
Water Volume
l
600
Water Connections
inch
Number of Fans (circuit 1 / circuit 2)
4 / 4
6 / 4
6 / 6
Total Air Flow - Standard Models
m
3
/s
47
58
70
Length
inch
194.4
230.5
274.4
Width
inch
88.4
88.4
88.4
Height
inch
94.1
94.1
94.1
Shipping Weight
lb
9811
11243
12124
Operating Weight
lb
10472
11904
13447
(1) Liquid sub-cooling measured at the liquid line should be between 47.3 and 52.0°F at circuit full load.
Sub-cooling is determined by the level of refrigerant charge in each system
Ambient Coils Fans
Dimensions
Basic Unit Weight
YLPA
Compressor
Refrigerant to Liquid
Heat Exchanger
8
2
Scroll
1
Shell and Tubes
300