background image

TROUBLESHOOTING GUIDE

y

d

e

m

e

R

e

s

u

a

c

e

l

b

a

b

o

r

P

m

e

l

b

o

r

P

A. The air conditioner does not

run.

1. Power failure.
2. Fuse blown or circuit breaker

open.

3. Voltage is too low.
4. Faulty contactor or relay.
5. Electrical connections loose.
6. Thermostat adjustment too low

(in heating mode) or too high (in
cooling mode).

7. Faulty capacitor.
8. Incorrect wiring, terminal loose.
9. Pressure switch tripped.

1. Wait for power resume.
2. Replace the fuse or reset the

breaker.

3. Find the cause and  ?x it.
4. Replace the faulty component.
5. Retighten the connection.
6. Check thermostat setting.
7. Find the cause then replace 

capacitor.

8. Check and retighten.
9. Find the cause before reset.

B. The outdoor fan runs but the

compressor will not start.

1. Motor winding cut or grounded.

2. Faulty capacitor.

1. Check the wiring and the

compressor winding resistance.

2. Find the cause then replace 

capacitor.

C. There is insuf ?cient heating or

cooling.

1. There is a gas leak.
2. Liquid and gas line insulated 

together.

3. The room was probably very hot

(cool) when you started the 

system.

1. Remove charge, repair,

evacuate and recharge.

2. Insulate them separately.
3. Wait while unit has enough time

to cool the room.

D. The compressor runs 

continuously.

1. Thermostat adjustment too low

(in heating mode) or too high 

(in cooling mode).

2. Faulty fan.
3. Refrigerant charge too low, leak.
4. Air or incondensables in refriger-

ant circuit.

1. Check thermostat setting.

2. Check condenser air circulation.
3. Find leak, repair and recharge.
4. Remove charge, evacuate and

recharge.

E. The compressor starts but shuts

down quickly.

1. Too much or too little refrigerant. 
2. Faulty compressor.
3. Air or incondensables in 

refrigerant circuit.

4. Changeover valve damaged or

blocked open (heat pump unit).

1. Remove charge, evacuate and

recharge.

2. Determine the cause and 

replace compressor.

3. Remove charge, evacuate and

recharge.

4. Replace it.

F. Clicking sound is heard from the

air conditioner.

In heating or cooling operation any
plastic parts may expand or shrink
due to a sudden temperature change
in this event, a clicking sound may
occur.

In heating or cooling operation any
plastic parts may expand or shrink
due to a sudden temperature change
in this event, a clicking sound may
occur.

J440-EN.indd   26

2/14/08   1:27:04 PM

17

Summary of Contents for YHCA-YHHA07FSAADK

Page 1: ...and operation Make sure that it is well kept for later reference Read this manual before installation and operation Make sure that it is well kept for later reference High Wall Air Conditioner INSTALL...

Page 2: ...eration tips 14 Troubleshooting guide 17 Please read this installation manualcarefullybeforestarting the installation It will tell you necessary information Quality POLICY Wewillcontinuouslystriveto s...

Page 3: ...lation and maintenance of this air conditioning system should only be car ried out by trained and qualified personnel After unpacking please check the unit carefully for possible damage Before underta...

Page 4: ...louver 6 Vertical louver Inner 7 Air filter 8 Pipe protection ring 9 Drain pipe Outdoor Unit 10 Refrigerant gas liquid piping 11 Service valve 12 Air outlet Indication light and signal receiver Power...

Page 5: ...direction up down The air conditioner automatically adjust the vertical air flow direction in accordance withthe operating mode Note Adjust the vertical air flow direction by remote controller Whenyo...

Page 6: ...BEFORE INSTALLATION Before doing any work check the interior power supply cord and the main breaker capacity are sufficient and the installation area is sufficient and complies with the requirements C...

Page 7: ...n exposure make sure that heat rediation from the condenser is not restricted Don t place animals or plants near the installation location because the cold and hot air out will affect them Make sure t...

Page 8: ...achine to wards the left down and right down side of the installation board until the hangers enters tightly the grooves it produces Click sound Bolt Vertical airflow direction plate Bolt Front frame...

Page 9: ...port or vibration damping should be adopted Installation Outdoor Unit Bolt Air outlet Outdoor Unit Left installation feet Right installation feet Air inlet Pipe Connection Connect the pipe to the indo...

Page 10: ...with tape alongside the wall and fix them to the wall with clips These steps are usually adopted when outdoor unit is installed below the indoor unit In case that you want to have additional drain pip...

Page 11: ...shippedcompletewithachargeofR 22 R407C R410A refrigerant that will be sufficient for an interconnecting piping length of 3 6 meters Liquid Cooling GAS Cooling suction Low pressure High pressure Manifo...

Page 12: ...rew take off the control panel cover from the unit Connect the cable to their terminals according to their number The grounded wire connection 1 loosen the grounded screw of electrical shelf 2 Connect...

Page 13: ...r and disconnect power Remove the batteries from the remote controller 3 The outdoor unit requires periodic maintenance and cleaning Do not attempt to do this yourself Contact your dealer or servicer...

Page 14: ...damage tothe air conditioneror to the other persons safety and property In order to properly use the air conditioner please follow theWorking condition in the instructions otherwise it may activate th...

Page 15: ...its orioiginal position when power is first turned on Dust is blown out from the indoor unit This is a normal condition when the air conditioner has not been used for a long time or during first use o...

Page 16: ...g out but the cooling heating effect is bad The wind blowing out but it doesnot refrigerate Power supply failure The power switch is released The fuse is burnt The battery is exhusted it doesn t reach...

Page 17: ...ool when you started the system 1 Remove charge repair evacuate and recharge 2 Insulate them separately 3 Wait while unit has enough time to cool the room D The compressor runs continuously 1 Thermost...

Page 18: ...e container using a refrigerant reclaim or recovery unit This refrigerant may then be reused if appropriate or returned to the manufacturer for disposal Under No circumstances should refrigerant be ve...

Page 19: ...www johnsoncontrols com Form No 035A00005 000 2009 Johnson Controls Inc Johnson Controls reserve the right to change product features without prior notice...

Reviews: