OUTDOOR UNIT
PIPE CONNECTION
9
Installation Of The Outdoor Unit
The outdoor unit must be firmly fixed to avoid falling in strong wind.
Install on the cement base the drawing below.
If it will be installed at seaside or at a place high above the ground and with strong wind, the AC should be
installed against the wall to ensure the normal operation of the fan and the blocking plate should be used.
If it will be installed in lift type, the structure of the monuting surface should be made of solid stick, cement
or materials with equivalent strength, and be of enough bearing capacity. Otherwise, measures such as
reinforcement, support or vibration damping should be adopted.
Installation Outdoor Unit Bolt
Air outlet
Outdoor Unit
Left installation feet
Right installation feet
Air inlet
Pipe Connection
Connect the pipe to the indoor unit:
fasten the connection screw and then by wrench until it is tightly fastened, The fastening direction is in the following
picture.
The size of pipe
Torque
Liquid pipe 6.35mm
ĭ
Air pipe 9.52mm
ĭ
Air pipe 12.7mm
ĭ
ĭ
Air pipe 15.88mm
18N . m
42N . m
55N . m
75N . m
Indoor Unit
Connection screw Pipe
Wrench
Torque wrench
Wrench the screw to the end unit you hear the “Click” sound.
Fasten the screw symmetrically with strenth.
( Refer the direction to the picture )
Outdoor Unit
Side liquid pipe
Side air pipe
Torque wrench
Outdoor Unit Size of Shape (mm)
800X300X690(590)
760X260X540
600X250X490
900X330X860
A (mm)
B (mm)
390
290
539
287
540
326
606
354