CAUTION:
No Controls (relays, etc.)
should be mounted in the
Smart Panel enclosure or con-
nected to power supplies in the
control panel. Additionally,
control wiring not connected
to the Smart Panel should not
be run through the cabinet.
This could result in nuisance
faults.
CAUTION:
Any inductive devices (relays)
wired in series with the flow
switch for start/stop, into the
Alarm circuitry, or pilot relays
for pump starters wired
through motor contactor aux-
iliary contacts must be sup-
pressed with YORK P/N 031-
00808-000 suppressor across
the relay/contactor coil.
Any contacts connected to flow
switch inputs or BAS inputs on
terminals 13 - 19 or TB3, or any
other terminals, must be sup-
pressed with a YORK P/N 031-
00808-000 suppressor across
the relay/contactor coil.
CAUTION:
Control wiring connected to
the control panel should never
be run in the same conduit with
power wiring.
UNIT
CONTROL
M
IN
MAX DUAL
NON-FUSED
VOLTAGE
POWER
CI
RCUIT
ELEMENT
DISC.
SUPPLY
AMP.
FUSE
SIZE
SWITCH
SIZE
ALL
MODELS
115-1-50/60
20
A
20A
250V
30A
240V
W/O
TRANS.
CONTR
OL PO
WER SUPPL
Y
ELEMENTARY DIAGRAM
7
Summary of Contents for MILLENNIUM YCAS
Page 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Page 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Page 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Page 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...