CONNECTION TYPES & SIZES
For connection sizes relevant to individual models refer
to the Technical Data Section.
COOLER CONNECTIONS
Standard chilled liquid connections on all coolers are of
the Victaulic Groove type.
Option Flanges
One of two types of flanges may be fitted depending on
the customer or local Pressure Vessel Code require-
ments. These are Victaulic-Adapter flanges, normally
supplied loose, or weld flanges which may be supplied
loose or ready fitted. Victaulic-Adapter and weld flange
dimensions are to ISO 7005 - NP10.
LD03521
FIG. 6 – VICTAULIC GROOVE
REFRIGERANT RELIEF VALVE PIPING
Coolers and oil separators are each protected against
internal refrigerant overpressure by refrigerant relief
valves. For coolers, a pressure relief valve is mounted
on each of the main refrigerant lines connecting the
cooler to the compressors. On oil separators the pres-
sure relief valve is mounted on the side near top of the
vessel body.
It is recommended that a piece of pipe is fitted to each
valve and directed so that when the valve is activated the
Weld Flange
Victaulic Adapter
LD03523
FIG. 7 – FLANGE ATTACHMENTS
release of high pressure gas and liquid cannot be a dan-
ger or cause injury. For indoor installations pressure relief
valves should be piped to the exterior of the building.
The size of any pipework attached to a relief valve must
be of sufficient diameter so as not to cause resistance
to the operation of the valve. Unless otherwise speci-
fied by local regulations, table internal diameter depends
on the length of pipe required and is given by the fol-
lowing formula:
D
5
= 1.447 x L
Where:
D =
minimum pipe internal diameter
L =
length of pipe in meters
If relief pipework is common to more than one valve its
cross sectional area must be at least the total required
by each valve. Valve types should not be mixed on a
common pipe. Precautions should be taken to ensure
that the outlet of relief valves/vent pipe remain clear of
obstructions at all times.
DUCTWORK CONNECTION
General Requirements
The following ductwork recommendations are intended
to ensure satisfactory operation of the unit. Failure to
follow these recommendations could cause damage to
the unit, or loss of performance, and may invalidate the
warranty.
When ducting is to be fitted to the fan discharge it is
recommended that the duct should be the same cross
sectional area as the fan outlet and straight for at least
1 meter (3 feet) to obtain static regain from the fan.
Ductwork should be suspended with flexible hangers to
prevent noise and vibration being transmitted to the struc-
ture. A flexible joint is also recommended between the
duct attached to the fan and the next section for the
same reason. Flexible connectors should not be allowed
to concertina.
The unit is not designed to take structural loading. No
significant amount of weight should be allowed to rest
on the fan outlet flange, deck assemblies or condenser
coil module. No more than 1 meter (3 feet) of light con-
struction ductwork should be supported by the unit.
Where cross winds may occur, any ductwork must be
supported to prevent side loading on the unit.
Installation
Summary of Contents for MILLENNIUM YCAS
Page 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Page 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Page 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Page 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...