OPTIONAL SINGLE POINT POWER SUPPLY CONNECTION TO FACTORY CIRCUIT BREAKER
(One Field Provided Power Supply Circuit to the chiller. Field Connection to Circuit Breaker in Option Panel.
No internal Branch Circuit Protection per Motor Control Center
.)
CONTROL POWER SUPPLY (UNITS WITHOUT STANDARD CONTROL CIRCUIT TRANSFORMERS)
NO. OF
CONTROL
MCA
MAX DUAL
NON-FUSED
COMPRESSORS
POWER
(MAX LOAD
ELEMENT
DISCONNECT
SUPPLY
CURRENT)
FUSE SIZE
SWITCH SIZE
2
115V-1Ø
20A
20A
30A
3 or 4
115V-1Ø
30A
30A
30A
(Non-CE 50/60Hz)
3 or 4
115V-1Ø
25A
30A
30A
(CE 50Hz)
ELECTRICAL DATA
COMPRESSOR DATA
MAXIMUM KW AND AMPERAGE VALUES FOR DXST COMPRESSORS
COMPRESSOR MODEL AND VOLTAGE CODE
DXS45LA - MOTOR CODE A
DXS36LA - MOTOR CODE A
DXS24LA - MOTOR CODE (TBD)
(B5N, B5E, B6N, B6E)
(A5N, A5E, A6N, A6E)
(C5N, C5E, C6N, C6E)
VOLTAGE CODE
-17
-28
-40
-46
-50
-58
-17
-28
-40
-46
-50
-58
-17
-28
-40
-46
-50
-58
MAX KW
150 150 150 150
113 150 150 150 150 150
113 150 105 105 105 105
80 105
MAX AMPS
492 428 259 214 193 171 492 428 259 214 193 171 338 294 178 147 135
118
FAN DATA
FAN TYPE
NOMINAL POWER
FULL LOAD AMPS
LOCKED ROTOR AMPS
(kW)
(FLA)
(LRA)
STANDARD
1, 57
4, 4
18, 0
HIGH PRESSURE
3, 7
6, 8
46, 3
Option not available for units with CE Mark.
Field Supplied Wiring
System #1
System #2
Model
Volts
MCA
1
Factory Supplied Breaker
Compressor
Fans
11, 12
Compressor
Fans
11, 12
YCAS
Rating
2
Wire Range
7
(Lugs)
RLA
X-LRA Qty FLA(ea) LRA(ea) RLA X-LRA Qty FLA(ea) LRA(ea)
0373
380
269
400
(2) 3/0-250
107.9
761
3
4.4
17.1
107.9
761
3
4.4
17.1
0403
380
291
450
(2) 3/0-250
117.7
761
3
4.4
17.1
117.7
761
3
4.4
17.1
0453
380
340
500
(2) 3/0-250
139.5
979
3
4.4
17.1
139.5
979
3
4.4
17.1
0503
380
389
600
(3) 2/0-400
161.3
979
3
4.4
17.1
161.3
979
3
4.4
17.1
0543
380
352
500
(2) 3/0-250
140.6
979
4
4.4
17.1
140.6
979
4
4.4
17.1
0573
380
413
600
(3) 2/0-400
167.9
979
4
4.4
17.1
167.9
979
4
4.4
17.1
0623
380
447
700
(3) 2/0-400
183.1
979
4
4.4
17.1
183.1
979
4
4.4
17.1
0653
380
422
600
(3) 2/0-400
167.9
979
5
4.4
17.1
167.9
979
5
4.4
17.1
Technical Data
Summary of Contents for MILLENNIUM YCAS
Page 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Page 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Page 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Page 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...