119
YORK INTERNATIONAL
FORM 201.18-NM2
SWITCH 3 : Refrigerant
Open:
The R-407C Mode MUST be selected for models using
refrigerant R-407C. Incorrect selection of this switch
may cause serious damage to the chiller.
Closed:
The R-22 Mode MUST be selected for models using
refrigerant type R-22. Incorrect selection of this switch
may cause serious damage to the chiller.
SUMMARY OF SETTINGS
The following table gives a summary of Modes (dis-
played messages) which can be selected using the Open
and Closed positions for each of the eight SW1 Dip
Switches.
SWITCH
SWITCH “OPEN”
SWITCH “CLOSED”
SETTING
SETTING
1
Water Cooling
Brine Cooling
2
Standard Ambient
Low Ambient
Control
Control
3
Refrigerant R-407C
Refrigerant R-22
4
Spare
Spare
5
Spare
Spare
6
Spare
Spare
7
Spare
Spare
8
Spare
Spare
S 1 - 3
R E F R I G E R A N T
R - 4 0 7 C
S 1 - 3
R E F R I G E R A N T
R - 2 2
Dip Switch Physical Location and Setting
FIG. 43 – ENLARGED PHOTOGRAPH OF DIP
SWITCHES ON MICROPROCESSOR BOARD
LD03511A
LD03511B
“OPEN” Position:
Left side of switch
pushed in
“CLOSED” Position:
Right side of switch
pushed in
3.8 FUNCTION KEY
Pressing the Function key only displays the same message
as pressing the Status key. Pressing the Function key
followed by another display key will scroll through all
the data available under that key once. E.g., pressing
the Function key followed by the System 1 Data key
will result in scrolling through the 5 displays shown in
Section 3.3 without the need to press the System 1 Data
key to scroll to the next display. After scrolling through
the data, the display returns to the status message.
The following keys can be scrolled using the Function
Key: Chilled Liquid Temps, System # Data, Motor
Current and Options.
9
Summary of Contents for MILLENNIUM YCAS
Page 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Page 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Page 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Page 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...