TEMPERATURES AND FLOWS
NOTES:
1. For leaving brine temperature below 4.4°C, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
MODEL
LEAVING WATER
COOLER FLOW
AIR ON
NUMBER
TEMPERATURE (°C)
(L/S)
3
CONDENSER (°C)
YCAS
MIN.
1
MAX.
2
MIN.
MAX.
MIN.
MAX
0373
4.4
13.0
9.3
37.8
-17.7
51.7
0403
4.4
13.0
10.7
37.8
-17.7
51.7
0453
4.4
13.0
11.5
37.8
-17.7
51.7
0503
4.4
13.0
11.5
37.8
-17.7
51.7
0543
4.4
13.0
12.8
47.1
-17.7
51.7
0573
4.4
13.0
12.8
47.1
-17.7
51.7
0623
4.4
13.0
12.8
47.1
-17.7
51.7
0653
4.4
13.0
12.8
47.1
-17.7
51.7
WATER PRESSURE DROP
FIG. 10 – FLOW RATE AND PRESSURE DROP CHARTS
MODEL NUMBER YCAS
COOLER
0373, 0403, 0453, 0503
A
0543, 0573, 0623, 0653
B
7
A
B
100
10
1
1
Water Flow (l/s)
Cooler Water Pressure Drop
A = 0.1737 (l/s)^1.82
B = 0.1393 (l/s)^1.80
10
100
1000
Pressure Drop (kPa)
LD05121
Summary of Contents for MILLENNIUM YCAS
Page 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Page 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Page 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Page 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...