![York MILLENNIUM YCAS Installation Operation & Maintenance Download Page 122](http://html1.mh-extra.com/html/york/millennium-ycas/millennium-ycas_installation-operation-and-maintenance_3850922122.webp)
122
YORK INTERNATIONAL
YORK INTERNATIONAL CORPORATION
MILLENNIUM SCREW CHILLER
UNIT STATUS
2:04PM 10 OCT 99
SYS 1 NO COOLING LOAD
SYS 2 COMPRESSOR RUNNING
OPTIONS
CHILLED LIQUID
WATER
AMBIENT CONTROL
STANDARD
REFRIGERANT TYPE
R-22
PROGRAM VALUES
DSCH PRESS CUTOUT
399 PSIG
DSCH PRESS UNLOAD
375 PSIG
SUCT PRESS CUTOUT
44 PSIG
HIGH AMBIENT CUTOUT
130.0 ºF
LOW AMBIENT CUTOUT
25.0 ºF
LEAVING LIQUID CUTOUT
36.0 ºF
MOTOR CURRENT UNLOAD
100 %FLA
ANTI RECYCLE TIME
600 SECS
LOCAL/REMOTE MODE
REMOTE
LEAD/LAG CONTROL
AUTOMATIC
UNIT DATA
LEAVING LIQUID TEMP
49.0 ºF
RETURN LIQUID TEMP
58.2 ºF
MIXED LIQUID TEMP
51.3 ºF
COOLING RANGE
42.0 +/- 2.0 ºF
AMBIENT AIR TEMP
74.8 ºF
LEAD SYSTEM
SYS 2
EVAPORATOR PUMP
O N
EVAPORATOR HEATER
O F F
ACTIVE REMOTE CONTROL
NONE
SOFTWARE VERSION
C.ACS.09.00
SYSTEM 1 DATA
COMPRESSORS STATUS
O F F
RUN TIME
0- 0- 0- 0 D-H-M-S
MOTOR CURRENT
0 AMPS 0 %FLA
SUCTION PRESSURE
125 PSIG
DISCHARGE PRESSURE
131 PSIG
OIL PRESSURE
130 PSIG
SUCTION TEMPERATURE
68.4 ºF
DISCHARGE TEMPERATURE
68.8 ºF
OIL TEMPERATURE
68.8 ºF
SAT SUCTION TEMP
71.8 ºF
SUCTION SUPERHEAT
3.4 ºF
SAT DISCHARGE TEMP
74.5 ºF
DISCHARGE SUPERHEAT
6.3 ºF
SLIDE VALVE STEP
0
COOLER INLET REFRIG
44.6 ºF
LIQUID LINE SOLENOID
O F F
ECONOMIZER TXV SOLENOID
O F F
CONDENSER FAN STAGE
O F F
COMPRESSOR HEATER
O N
WYE-DELTA RELAY
O F F
SYSTEM 2 DATA
COMPRESSORS STATUS
O N
RUN TIME
0- 0-15-26 D-H-M-S
MOTOR CURRENT
104 AMPS 87 %FLA
SUCTION PRESSURE
57 PSIG
DISCHARGE PRESSURE
233 PSIG
OIL PRESSURE
218 PSIG
SUCTION TEMPERATURE
42.9 ºF
DISCHARGE TEMPERATURE
145.5 ºF
OIL TEMPERATURE
102.8 ºF
SAT SUCTION TEMP
31.7 ºF
SUCTION SUPERHEAT
11.2 ºF
SAT DISCHARGE TEMP
112.1 ºF
DISCHARGE SUPERHEAT
33.4 ºF
SLIDE VALVE STEP
7 0
COOLER INLET REFRIG
23.6 ºF
LIQUID LINE SOLENOID
O N
ECONOMIZER TXV SOLENOID
O N
CONDENSER FAN STAGE
3
COMPRESSOR HEATER
O F F
WYE-DELTA RELAY
O N
DAILY SCHEDULE
S M T W T F S * = HOLIDAY
MON START=00:00AM STOP=00:00AM
TUE START=00:00AM STOP=00:00AM
WED START=00:00AM STOP=00:00AM
THU START=00:00AM STOP=00:00AM
FRI START=00:00AM STOP=00:00AM
SAT START=00:00AM STOP=00:00AM
HOL START=00:00AM STOP=00:00AM
The Local and System Data display messages for the
YCAS 3-System models follow the same format as the
YCAS 2-System Model messages as given in the pre-
ceding paragraphs. The only difference is that after the
System 2 data is completed, pressing the key displays
System 3 data before looping back to the Load/Unload
Timer Display.
YCAS 4-System Models:
YCAS 4-System models are constructed in two sec-
tions. One section contains number 1 and 2 refrigerant
systems plus their associated evaporator. The second
section contains the number 3 and 4 refrigerant sys-
tems plus their associated evaporator. Both sections have
their own control panel, but only the System 1 and 2
panel is fitted with a keypad and display.
The Local and System Data display messages for the
YCAS 4-System models follow the same format as the
YCAS 2-system model messages as given in the pre-
ceding paragraphs. The only difference is that after the
System 2 Data is completed, pressing the
á
á
á
á
á
key dis-
plays System 3 and System 4 data before looping back
to the Load/Unload Timer Display.
4.4 OPERATING DATA - REMOTE PRINTOUT
The follow text shows a typical example printout ob-
tained by pressing the Operating Data key with an op-
tional printer attached. In this case an example is shown
for a YCAS 2-system Chiller. YCAS 3-system models
and YCAS 4-system models provide similar printouts
for the appropriate number of systems:
The System Cooler Inlet Refrigerant
Temperature will be printed if the unit
is in R-407C mode.
Micropanel
Summary of Contents for MILLENNIUM YCAS
Page 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Page 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Page 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Page 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...