8.4 CONDENSER FAN CONTROL
The chiller is equipped with 8 or 10 condenser fans,
with 4 or 5 fans per system as given below. Fan control
is via Outside Ambient Temperature (OAT) and Dis-
charge Pressure (DP). There are six stages of fan con-
trol utilizing 3 outputs per system. The fan stages will
work according to Table 2 or Table 3 depending on the
number of fans/system. There will be a minimum 5 sec-
ond delay between all fan stages.
Condenser fan ON conditions are governed solely by
the Discharge Pressure (DP). When the DP rises above
15.2 bar, Stage 1 is activated. From here, subsequent
fan stages are activated as the DP rises in increments
of 1 bar, except stage 6, which is activated when the
DP rises over 20 bar. The system will remain at the
Fan
ON
OFF
Fan
Wire
Relay
Stage
Fans
Conditions
Conditions
Contactor
Number
Board
DP
DP & OAT
Output
1
1
>15.2 BAR
<10.3 BAR & <15.6ºC
9M
130
15
S
2
3
>16.2 BAR
<11.4 BAR & <18.3ºC
10M
131
14
Y
3
5, 7
>17.2 BAR
<12.4 BAR & <21.1ºC
11M, 12M
132
10
S
4
1, 5, 7
>18.3 BAR
<13.4 BAR & <23.9ºC
9M, 11M, 12M
130, 132
10,15
5
3, 5, 7
>19.3 BAR
<14.5 BAR & <26.7ºC
10M, 11M, 12M
131, 132
10, 14
1
6
1, 3, 5, 7
>20.0 BAR
<15.2 BAR & <29.4ºC
9M, 10M, 11M, 12M
130, 131, 132
10, 14, 15
1
2
>15.2 BAR
<10.3 BAR & <15.6ºC
15M
230
15
S
2
4
>16.2 BAR
<11.4 BAR & <18.3ºC
16M
231
14
Y
3
6, 8
>17.2 BAR
<12.4 BAR & <21.1ºC
17M, 18M
232
10
S
4
2, 6, 8
>18.3 BAR
<13.4 BAR & <23.9ºC
15M, 17M, 18M
230, 232
10,15
5
4, 6, 8
>19.3 BAR
<14.5 BAR & <26.7ºC
16M, 17M, 18M
231, 232
10, 14
2
6
2, 4, 6, 8
>20.0 BAR
<15.2 BAR & <29.4ºC
15M, 16M, 17M, 18M
230, 231, 232
10, 14, 15
TABLE 2 – CONDENSER FAN CONTROL & FAN CONTACTOR DATA FOR DXST UNITS WITH 4 FANS/SYSTEM
Fan
ON
OFF
Fan
Wire
Relay
Stage
Fans
Conditions
Conditions
Contactor
Number
Board
DP
DP & OAT
Output
1
1
>15.2 BAR
<10.3 BAR & <15.6ºC
9M
130
15
S
2
3, 5
>16.2 BAR
<11.4 BAR & <18.3ºC
10M, 11M
131
14
Y
3
7, 9
>17.2 BAR
<12.4 BAR & <21.1ºC
12M, 13M
132
10
S
4
1, 7, 9
>18.3 BAR
<13.4 BAR & <23.9ºC
9M, 12M, 13M
130, 132
10,15
5
3, 5, 7, 9
>19.3 BAR
<14.5 BAR & <26.7ºC
10M, 11M, 12M, 13M
131, 132
10, 14
1
6
1, 3, 5, 7, 9
>20.0 BAR
<15.2 BAR & <29.4ºC
9M, 10M, 11M, 12M, 13M
130, 131, 132
10, 14, 15
1
2
>15.2 BAR
<10.3 BAR & <15.6ºC
15M
230
15
S
2
4, 6
>16.2 BAR
<11.4 BAR & <18.3ºC
16M, 17M
231
14
Y
3
8, 10
>17.2 BAR
<12.4 BAR & <21.1ºC
18M, 19M
232
10
S
4
2, 8, 10
>18.3 BAR
<13.4 BAR & <23.9ºC
15M, 18M, 19M
230, 232
10,15
5
4, 6, 8, 10
>19.3 BAR
<14.5 BAR & <26.7ºC
16M, 17M, 18M, 19M
231, 232
10, 14
2
6
2, 4, 6, 8, 10
>20.0 BAR
<15.2 BAR & <29.4ºC
15M, 16M, 17M, 18M, 19M
230, 231, 232
10, 14, 15
TABLE 3 – CONDENSER FAN CONTROL & FAN CONTACTOR DATA FOR DXST UNITS WITH 5 FANS/SYSTEM
FIGURE 44 – CONDENSER FAN LAYOUT FOR DXST 2-COMPRESSOR UNITS
highest fan stage reached unless the OFF conditions
given in the next paragraph are satisfied.
Condenser fan OFF conditions are governed by both
the DP and OAT. Fan staging will be decreased from
the highest stage reached if both the DP and OAT re-
quirements are met. For example, if a system is at a fan
stage of 4, and the DP falls under 13.4 bar and the OAT
drops below 23.9ºC, the fan stage will be reduced to 3.
The OFF conditions are given in the next two tables.
The tables on the next page also present fan contactor
data for the fans involved in each fan stage. SYS 1 uses
relay board #1. SYS 2 uses relay board #2.
YCAS 0373, 0403, 0453, 0503, 0543 and 0573 models
have 4 condenser fans/system:
9
Summary of Contents for MILLENNIUM YCAS
Page 53: ...53 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM ACROSS THE LINE START 7...
Page 54: ...54 YORK INTERNATIONAL FIG 12 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 59: ...59 YORK INTERNATIONAL FORM 201 18 NM2 WIRING DIAGRAM WYE DELTA START LD03229 FIG 15 CONT D 7...
Page 60: ...60 YORK INTERNATIONAL FIG 15 CONTINUED ELEMENTARY DIAGRAM Technical Data...
Page 62: ...62 YORK INTERNATIONAL FIG 16 POWER PANEL FRONT INSIDE VIEW WYE DELTA START Technical Data...
Page 68: ...68 YORK INTERNATIONAL FIG 24 DETAIL B Technical Data...