102777-YIM-E-0206
112
Unitary Products Group
TABLE 52: SETTABLE SYSTEM PARAMETERS
ADDRESS
FUNCTION
UNIT
RANGE
DEFAULT
YOUR SETTINGS
1
Run test
ON-OFF
OFF
2
Fan on delay-Heating
Sec
0-30
30
3
Fan off delay-Heating
Sec
0-255
60
4
Fan on delay-Cooling
Sec
0-30
0
5
Fan off delay-Cooling
Sec
0-255
30
6
Factory setting
-
-
1
Do not change
7
Suspend Cont Fan when starting
Heating
ON-OFF
OFF
8
Construction Mode
-
ON-OFF
OFF
9
Unoccupied Override Time Period
Minutes
0-240
60
10
Occupied Cooling Setpoint
°F
45-99
72
11
Occupied Heating Setpoint
°F
45-99
68
12
Unoccupied Cooling Setpoint
°F
45-99
85
13
Unoccupied Heating Setpoint
°F
45-99
60
14
SAT Control-Cooling
ON-OFF
ON-OFF
ON
15
Cooling SAT Control Setpoint
°F
40-65
50
16
SAT Control for Heating
ON-OFF
ON-OFF
ON
17
Heating SAT Control Setpoint
°F
100-180
135
18
Hydronic Heating
ON-OFF
ON-OFF
OFF
19
First Stage Hydronic Heating SAT
Setpoint
°F
80-180
120
20
Second Stage Hydronic Heating SAT
Setpoint
°F
80-180
150
21
Hydronic Heating Reverse Actuated
Valve
ON-OFF
ON-OFF
OFF
22
Remote Control
ON-OFF
ON-OFF
OFF
23
VAV Upper Cooling SAT
°F
40-70
60
24
VAV Lower Cooling SAT
°F
40-70
55
25
VAV SAT Reset Setpoint
°F
40-85
72
26
VAV Occupied Setpoint
ON-OFF
ON-OFF
OFF
27
VAV Occupied Heating Setpoint
°F
40-85
68
28
Morning Warm-Up
ON-OFF
ON-OFF
ON
29
Morning Warm-Up RAT
°F
50-85
70
30
Duct Static Setpoint
" H2O
0 – 5”
1.5”
31
Building Pressure Setpoint
" H2O
neg .25 to .25
.1”
32
Economizer
ON-OFF
ON-OFF
ON
33
Economizer First Stage
°F
40-65
55
34
Economizer Second Stage
°F
40-65
50
35
Economizer Minimum Position
Percent
0 to 100%
20
36
Outside Air Humidity Sensor
ON-OFF
ON-OFF
OFF
37
Economizer Outside Air Enthalpy
Setpoint
BTUs Per Pound
10-50
27
38
Return Air Humidity Sensor
ON-OFF
ON-OFF
OFF
39
Economizer OAT Enable
°F
40-80
55
Summary of Contents for MILLENNIUM Y22
Page 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Page 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Page 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Page 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Page 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Page 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Page 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Page 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Page 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Page 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...