102777-YIM-E-0206
Unitary Products Group
11
NOTE: If the Millennium is VAV with ERV, add the
weight of an exhaust VFD - it will be in the unit.
.
TABLE 4: UNIT WEIGHTS
COMPONENT
25 TON
30 TON
40 TON
Basic Unit
4350
4550
4950
Gas Heat
233 MBH
180
180
180
466 MBH
320
320
320
700 MBH
-
-
450
Electric Heat
40KW
40
40
40
80KW
105
105
105
108KW
110
110
110
Hot Water Heat
1 Row Coil
70
70
70
2 Row Coil
85
85
85
Steam Heat
1 Row Coil
85
85
85
Blower
Forward Curve Fan (Std Fan)
0
0
0
FC IGV
155
155
175
Air Foil Fan
135
135
155
AF IGV
155
155
180
Motor - Supply Fan
7.5hp
110
-
-
10hp
145
145
145
15hp
200
200
200
20hp
240
240
240
25hp
-
300
300
Supply Fan Motor VFD
See Table 5
Refrigeration
Hi Cap. Evap. Coil
-
50
15
T-Coat Evap.
32
30
40
T-Coat cond.
32
30
40
Hot Gas Bypass
10
10
10
Low Ambient Head Pressure Control
208-230/380/460
5
5
5
575
25
25
25
Filters
6" Rigid
70
70
70
Exhaust
1
1.
If ERV and Supply Fan VAV are selected, add the
weight of an Exhaust VFD, Table 5.
Exhaust Type
Barometric
45
65
65
Modulated
140
275
275
Exhaust Motor
5hp
80
80
80
7.5hp
110
110
110
10hp
145
145
145
15hp
200
200
200
Exhaust Motor VFD
See Table 6
Economizer
Std. Econ.
235
235
235
Econ. w/ERV
50
50
50
Control
Disconnect
15
15
15
110V outlet
55
55
55
Optilogic
20
20
20
Roof Curb
Partial Curb
415
415
415
Full Curb
615
615
615
TABLE 5: SUPPLY FAN MOTOR VFD WEIGHTS
Supply Fan Motor VFD
230V
460V
575V
W/O Bypass
7.5hp
60
25
30
10hp
60
25
30
15hp
75
50
60
20hp
75
50
60
25hp
115
50
60
W/Bypass
7.5hp
155
90
120
10hp
155
90
120
15hp
185
140
155
20hp
185
140
155
25hp
255
140
155
TABLE 6: EXHAUST FAN MOTOR VFD WEIGHTS
Exhaust Fan Motor
230V
460V
575V
W/O Bypass
5hp
15
10
20
7.5hp
50
15
20
10hp
50
15
20
15hp
65
40
50
25hp
255
140
155
FIGURE 3 -
CENTER OF GRAVITY
1
1.
Refer to Tables 7 and 8 for A, B, C, D and X and Y data
respectively.
All panels must be secured in place when the unit is
lifted.
The condenser coils should be protected from dam-
age by the rigging cables with plywood or other suit-
able material.
An adhesive backed cover is provided over the out-
side of the combustion air inlet opening on gas fired
units to prevent moisture from entering the unit
which could cause damage to electrical compo-
nents. Allow this closure label to remain in place
until the combustion air hood is to be installed (Refer
to Figures 7, 8, & 9).
RIGHT SIDE
CENTEROF
GRAVITY
CONDENSER
COILEND
LEFT SIDE
X
Y
83"
240"
A
B
C
D
BACK
Summary of Contents for MILLENNIUM Y22
Page 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Page 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Page 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Page 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Page 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Page 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Page 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Page 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Page 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Page 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...
Page 139: ...102777 YIM E 0206 Unitary Products Group 139 ...