102777-YIM-E-0206
18
Unitary Products Group
3.
Place the flue extension (Figure 9) on the flue duct of
each furnace section and attach with screws provided.
4.
Place the flue in position with the diverter angles facing
up toward the top of the unit and attach with screws pro-
vided.
5.
Place the wind shield over the louvers on the right side of
the burner access door and attach with screws provided.
6.
Refer to the Gas Furnace Operation Instructions in the
Start-up Section of this manual for further information.
ELECTRIC HEAT
Units with electric heat are fully wired and operational when
shipped. Constant volume units are designed for two equal
steps of capacity for 80 and 108 kWH heat; 40 kW heat is one
step only. VAV units are one full step at full heat capacity.
HOT WATER HEAT
The YORK Millennium units (25, 30, and 40 Ton sizes) can be
furnished with a YORK hot water coil as the heat source. One
or two row coil units will be factory installed in the heating
section.
NOTE:
The hot water control valve will not be provided. The
installer will need to purchase a hot water control
valve, to connect the hot water piping and power
wiring at the job site for the hot water heat section to
be operational.
NOTE:
For all hot water coils the entering water tempera-
ture should not exceed 200°F.
The hot water coil is located downstream of the supply air fan
and just above the supply air opening in the bottom of the
unit.
Refer to Tables 58 through 66 and Figures 36 through 49 for
flow rate and capacity.
FIGURE 10 - CLEARANCES
60"
REAR
60"
FRONT
60"
ENDS
10'
60"
ENDS
REQUIRED CLEARANCES
LEFT
RIGHT
REAR
FRONT
TOP
60"
60"
60"
60"
10'
* Right is the side with access to the Electrical / Gas Controls.
*
is the side with the Condenser Coils
NOTE: DO NOT use the unit roof to support any type of
structure or bracing.
Front
DO NOT use hot water coils as steam coils under
any circumstances.
All piping, control valves, and wiring that is field
installed must be properly insulated and conform
to all local and national codes.
Summary of Contents for MILLENNIUM Y22
Page 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Page 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Page 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Page 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Page 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Page 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Page 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Page 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Page 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Page 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...
Page 139: ...102777 YIM E 0206 Unitary Products Group 139 ...