102777-YIM-E-0206
68
Unitary Products Group
GAS FURNACE OPERATING
INSTRUCTIONS
TO LIGHT THE MAIN BURNERS
1.
Turn off electric power to unit.
2.
Turn space temperature sensor to lowest setting.
3.
Turn gas valve knobs to on position (Refer to Figure 27).
4.
Turn on electric power to unit.
5.
On Constant Volume units, set space setpoint to warmer
or cooler as desired. (If sensor set point temperature is
above room temperature, the main burners will ignite). If
a second stage of heat is called for, the main burners for
second stage heat will ignite for the second stage heat.
For VAV units set morning warm-up thermostat far above
the return air temperature and cycle the time clock OFF,
then ON.
TO SHUT DOWN
1.
Turn off electric power to unit.
2.
Depress knob of gas valve while turning to off position.
(Refer to Figure 27).
POST-START CHECKLIST (GAS)
After the entire control circuit has been energized and the
heating section is operating, make the following checks:
1.
Check for gas leaks in the unit piping as well as the sup-
ply piping.
2.
Check for correct manifold gas pressures. See Checking
Gas Input.
3.
Check the supply gas pressure. It must be within the lim-
its shown on rating nameplate. Supply pressure should
be checked with all gas appliances in the building at full
fire. At no time should the standby gas pressure exceed
13 inches, nor the operating pressure drop below 6
inches. If gas pressure is outside these limits, contact the
local gas utility for corrective action.
MANIFOLD GAS PRESSURE ADJUSTMENT
Small adjustments to the gas flow may be made by turning
the pressure regulator adjusting screw on the automatic gas
valve. Refer to Figure 27.
Adjust as follows:
1.
Remove the cap on the regulator. It's located next to the
push-on electrical terminals.
2.
To decrease the gas pressure, turn the adjusting screw
counterclockwise.
3.
To increase the gas pressure, turn the adjusting screw
clockwise.
NOTE:
The correct manifold pressure for each furnace
module is 3.50 IWG 0.3.
TABLE 40: DRIVE ADJUSTMENT FOR POWER EXHAUST - 30 & 40 TON
7.5 HP Motor & 852 RPM Drive
10 HP Motor & 976 RPM Drive
15 HP Motor & 1069 RPM Drive
% RPM
& CFM
REQ’D
PD (in)
Browning
2B5V_ _
% RPM
& CFM
REQ’D
PD (in)
Browning
2B5V_ _
% RPM
& CFM
REQ’D
PD (in)
Browning
2B5V_ _
96.4
5.3
52
93.7
5.9
58
94.2
6.5
64
100.0
(Std.) 5.5
54
96.8
6.1
60
97.1
6.7
66
103.6
5.7
56
100.0
(Std.) 6.3
62
100.0
(Std.) 6.9
68
107.3
5.9
58
103.2
6.5
64
102.9
7.1
70
110.9
6.1
60
106.3
6.7
66
108.7
7.5
74
114.5
6.3
62
109.5
6.9
68
117.4
8.1
80
Each furnace module is equipped with an auto-
matic re-ignition system. DO NOT attempt to man-
ually light the burners.
Summary of Contents for MILLENNIUM Y22
Page 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Page 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Page 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Page 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Page 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Page 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Page 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Page 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Page 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Page 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...
Page 139: ...102777 YIM E 0206 Unitary Products Group 139 ...