102777-YIM-E-0206
86
Unitary Products Group
Holiday Schedule
•
If the Start Time is programmed to zero, the default is all
day.
•
The Number of Days will be programmed from 0-99.
•
The Start Date is programmed by Month-Day-Year.
•
When the Start Date is 00-00-0000, that Holiday is
ignored.
•
When the Time is 00:00, the Time is equal to 12:00 a.m.,
the beginning of the day.
Full heating (all stages) is ON when RAT drops 2
°
F below the
setpoint, heating is OFF when RAT is at, or above the set-
point. (Note that in this case, the control will use all available
heating stages, regardless of setting of the programmable
parameter "Heat Stages"). Before energizing heat for Morn-
ing Warm Up the control will start the Fan and operate it for 5
minutes. The Economizer will stay closed and the Fan will
continue to run during the Morning Warm Up. The Morning
Warm Up will terminate when the Occupied period begins.
If the RAT setpoint is achieved before the MWU period
expires, Unoccupied cooling is permitted. If further heating is
needed during the Occupied period, it is controlled by a VAV
Occupied Heating algorithm (if enabled and if a Space Sen-
sor is used), or by a space thermostat.
The same algorithm is also used for VAV Occupied Heating
(see also paragraph "VAV Occupied heating" in "Option Oper-
ation" section earlier in this document). In this case, the VAV
Occupied Heating control algorithm is activated under the
control of the Space Sensor (whenever the zone temperature
sensed by the Space Sensor drops 2
°
F or more below a pro-
grammed "VAV SAT Reset Setpoint"). Once activated, the
Occupied Heating control algorithm controls RAT between
the MWU RAT Setpoint and two degrees below the setpoint
and cycles the fan the same way as the MWU algorithm.
The specified Max Morning Warm Up Time is not used to limit
the duration of VAV Occupied Heating. During heating for
Morning Warm Up, or for VAV Occupied heating function, the
VAV boxes controls will receive an override signal to open the
VAV box damper. This is accomplished by wiring the VAV
heat relay for the VAV boxes to open, and energizing it from
Heat output of the controller. Note that as the first stage of
heat cycles on / off, the VAV box heat relay will cycle with it.
UNOCCUPIED VAV HEATING / COOLING CONTROL
ALGORITHM WITH A SPACE SENSOR
In the unoccupied mode, the Space Sensor will compare the
temperature in a selected VAV zone to the programmed
Unoccupied Heating and Cooling setpoints and request heat-
ing or cooling using the following control algorithm:
OCCUPIED VAV HEATING / COOLING CONTROL ALGO-
RITHM WITH A SPACE SENSOR
In the occupied mode, the control will compare the tempera-
ture in a selected VAV zone to the programmed "VAV SAT
Reset Setpoint" and request heating or cooling using the fol-
lowing control algorithm: The transition from cooling to occu-
pied heating occurs at 2
°
F below the "VAV SAT Reset
Setpoint". There is no "satisfied", or "idle" state of the unit
between cooling and occupied heating.
The above algorithm only requests occupied cooling and
selects a SAT occupied cooling setpoint, or requests occupied
heating at a programmed "Morning Warm Up RAT Setpoint".
Once requested by this Space Sensor algorithm, the cooling
is controlled by the SAT control algorithm described in para-
graph "SAT Control Algorithm in VAV Cooling" earlier in this
TABLE 44: WEEKLY SCHEDULE
Times
Mon
Tues
Wed
Thu
Fri
Sat
Sun
Occupied 1
00:00 00:00 00:00 00:00 00:00 00:00 00:00
Unoccupied 1
00:00 00:00 00:00 00:00 00:00 00:00 00:00
Occupied 2
00:00 00:00 00:00 00:00 00:00 00:00 00:00
Unoccupied 2
00:00 00:00 00:00 00:00 00:00 00:00 00:00
TABLE 45: HOLIDAY SCHEDULE
Holiday Number
Start Month
Start Day
of Month
Start Time
Number
of Days
Holiday 1
00
00
00:00
00
Holiday 2
00
00
00:00
00
Holiday 3
00
00
00:00
00
Holiday 4
00
00
00:00
00
Holiday 5
00
00
00:00
00
Holiday 6
00
00
00:00
00
Holiday 7
00
00
00:00
00
Holiday 8
00
00
00:00
00
Holiday 9
00
00
00:00
00
Holiday 10
00
00
00:00
00
Holiday 11
00
00
00:00
00
Holiday 12
00
00
00:00
00
Holiday 13
00
00
00:00
00
Holiday 14
00
00
00:00
00
Holiday 15
00
00
00:00
00
Holiday 16
00
00
00:00
00
Holiday 17
00
00
00:00
00
Holiday 18
00
00
00:00
00
Holiday 19
00
00
00:00
00
Holiday 20
00
00
00:00
00
Summary of Contents for MILLENNIUM Y22
Page 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Page 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Page 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Page 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Page 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Page 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Page 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Page 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Page 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Page 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...
Page 139: ...102777 YIM E 0206 Unitary Products Group 139 ...