102777-YIM-E-0206
12
Unitary Products Group
RIGGING AND HANDLING
This unit is
not
designed to be handled with a fork-truck.
Exercise care when moving the unit. Do not remove any
packaging until the unit is near the place of installation. Rig
the unit by attaching chain or cable slings to the holes pro-
vided in lifting lugs. Spreaders MUST be used across the top
of the unit. Refer to Figure 2.
•
Rig with six cables and spread with four 95-inch spread-
ers across width and two spreaders of length equal to A
+ B.
•
Refer to Tables 4 and 7 for unit weight.
•
Center of gravity includes economizer, exhaust or return
air fan and inlet guide vanes (Refer to Table 8).
NOTES: Basic Unit = cooling only, 10hp FC fan.
+ Econ = +235lb
+ Heat = single stage gas, 180 lb
+ Power Exhaust = modulating 7.5hp
CLEARANCES
All units require certain clearances for proper operation and
service. Installer must make provisions for adequate combus-
tion and ventilation air in accordance with section 5.3, Air for
Combustion and Ventilation of the National Fuel Gas Code
ANSI Z223.1 or Sections 7.2, 7.3 or 7.4 of CAN/CGA B149
installation codes-Latest Edition and/or applicable provisions
of the local building codes. Refer to Figure 10 for clearances
required for combustible construction, servicing, and proper
unit operation.
TABLE 7: UNIT CORNERWEIGHT
UNIT
DESCRIPTION
25 TON
30 TON
40 TON
A
B
C
D
A
B
C
D
A
B
C
D
Basic Unit
1033
1033
1215
1215
1079
1053
1269
1294
1131
1131
1417
1417
Basic Unit With
Economizer
1112
1112
1253
1253
1185
1157
1280
1308
1205
1205
1460
1460
Basic Unit With
Economizer and
Gas or Electric Heat
1162
1162
1293
1293
1209
1155
1346
1400
1255
1224
1500
1531
Basic Unit With
Economizer and
Gas or Electric Heat
and Power Exhaust
1284
1284
1296
1296
1359
1298
1389
1449
1416
1384
1532
1563
TABLE 8: UNIT CENTER OF GRAVITY
MODEL
25 TON
30 TON
40 TON
X
Y
X
Y
X
Y
Basic Unit
99”
46”
98”
45”
93”
46"
Basic Unit With
Econ.
110”
46”
108”
45”
97”
46"
Basic Unit With
Econ. & Gas or
Elect. Heat,
Steam or Hot
Water Heat
104”
45”
102”
44”
96”
45"
Basic Unit With
Econ. & Gas or
Elect. Heat, &
Power Exhaust
118”
45”
112”
44”
108”
45"
(COOLING OPERATION) Do not permit overhang-
ing structures or shrubs to obstruct condenser air
discharge outlet, combustion air inlet or vent out-
lets.
Summary of Contents for MILLENNIUM Y22
Page 47: ...102777 YIM E 0206 Unitary Products Group 47 FIGURE 20 ALTITUDE TEMPERATURE CONVERSION FACTOR ...
Page 50: ...102777 YIM E 0206 50 Unitary Products Group FIGURE 21 FAN PERFORMANCE 25 TON ...
Page 53: ...102777 YIM E 0206 Unitary Products Group 53 FIGURE 22 FAN PERFORMANCE 30 TON ...
Page 56: ...102777 YIM E 0206 56 Unitary Products Group FIGURE 23 FAN PERFORMANCE 40 TON ...
Page 126: ...102777 YIM E 0206 126 Unitary Products Group FIGURE 52 TYPICAL CONTROL WIRING ...
Page 127: ...102777 YIM E 0206 Unitary Products Group 127 FIGURE 53 LEGEND ...
Page 128: ...102777 YIM E 0206 128 Unitary Products Group FIGURE 54 TYPICAL 25 TON POWER WIRING ...
Page 129: ...102777 YIM E 0206 Unitary Products Group 129 FIGURE 55 TYPICAL 30 40 TON POWER WIRING ...
Page 130: ...102777 YIM E 0206 130 Unitary Products Group FIGURE 56 TYPICAL GAS HEAT WIRING ...
Page 134: ...102777 YIM E 0206 134 Unitary Products Group FIGURE 58 25 TON CHARGING CURVE ...
Page 139: ...102777 YIM E 0206 Unitary Products Group 139 ...