351579-YTS-B-0608

Johnson Controls Unitary Products

7

ANALOG INPUTS (AI)

Analog inputs require parameters that define the input’s 
characteristics. Attributes of an AI include the linear range, 
alarm limits, alarm differential, change of state (COS) enable, 
and filter weight. The input values may be overridden by a 
external system command or by using the input buttons on 
the 

Simplicity

®

 board. This is useful to override current 

conditions to test certain control functions or modes.

BAS 

- Economizer override; if this option is enabled, an 

external BAS system will control the economizer 2-10 VDC 
signal through this pair of terminals.

ST 

- Space Temperature sensor is a field installed sensor 

(PN: 025-38928-000 - w/ Override Button). The sequence of 
control for space temperature is different depending on 
whether the system is a VAV or CAV. See chapter on 
Sequence of Operation for a detailed description of the ST 
control modes. 

SSA

 - Space Temperature Adjust is field installed. It is a slide 

adjustment located on a space sensor (PN: 025-38927-000) 
with a slide bar potentiometer. It is used to offset the space 
temperature setpoint. This slide-bar is a 10K ohm 
potentiometer. The programmable range for the Setpoint 
adjust is +/- 5 °F. For example, if the Space Temperature 
setpoint is set to 74 °F, the SSA is programmed to +/- 3 °F and 
the SSA is adjusted fully to the + position, the new controlling 
space setpoint will be 78 °F.

OAT 

- The outside air temperature sensor (PN: 031-01916-

000A) is a factory-installed 10 K NTC sensor. Its linear 
ranging is from -50 °F to 250 °F.

OAH 

- Outside Air Humidity (PN: 031-09127-000-A) is a 

factory-installed sensor manufactured by MAMAO. The OAH 
sensor, installed only with enthalpy economizer, provides a 0-
10 VDC signal to the controller over a range of 0 to 100% 
relative humidity. This input is used for the economizer 
calculation to determine whether free cooling is available and 
to switch between minimum outside air and using outside air 
as the first stage of cooling.

SAT 

- Supply Air Temperature sensor (PN: 031-01915-000A) 

is a factory-installed -50 °F to 250 °F, 10 K NTC sensor.

RAT 

- Return Air Temperature sensor (PN: 031-01917-000A) 

is a factory-installed -50 °F to 250 °F, 10 K NTC sensor.

RAH

 

- Return Air Humidity (PN: 031-09127-000-A) is a 

factory-installed sensor manufactured by MAMAO, installed 
only with dual enthalpy economizer. The control will calculate 
the return air enthalpy using the relative humidity and return 
temperature inputs.

LOW VOLTAGE DETECTION 

- This input monitors the 24 

VAC for low voltage conditions. The input has two thresholds, 
one at 16 VAC and one at 19.2 VAC. If the control needs to 
turn on a contactor, it will look to see if the voltage is 
above19.2 VAC before it will turn it on. If the voltage is not 
above 19.2 VAC, it will hold off the contactor and flash the 
appropriate flash code. This flash code is not an alarm. If the 
control already has contactors pulled in, it will monitor the 

voltage and drop the contactors and shut down if the voltage 
drops below 16 VAC and flash the appropriate flash code.

REMOTE

 

- the control will use 0-10 VDC from third-party 

BAS to control SAT setpoints. Thermostat inputs override if in 
conflict with Remote Control voltage input.

SPC TEMP

 

- offset value from the space sensor offset 

potentiometer.

CV/VAV

 

- resistive value across terminals, to determine 

which supply fan rules the control will follow.

Demand Ventilation / IAQ 

- Indoor Air Quality. The IAQ 

expects a 0-10 VDC signal to the control from a field supplied 
and installed Carbon Dioxide (CO

2

) sensor. Indoor air quality 

is monitored for adequate ventilation. In Demand Ventilation 
Mode, as the CO

2

 

levels in the building rise above the 

programmed setpoint, more fresh air must be brought in. The 
economizer is therefore adjusted to a more open position as 
necessary. The linear ranging for IAQ sensor input is from 0 
to 10,000 ppm. The Demand Ventilation setpoint is adjustable 
from 0 to 2000 ppm and is set at the factory at 1000 ppm.

DPS 

- Duct Pressure Sensor is monitored by a factory-

installed 0-5 VDC transducer (PN: 031-01209-000A). The 
high-pressure port sensing tube is installed in the field. The 
sense tube should be located approximately two thirds of the 
way down the duct plenum. To prevent an unstable signal 
due to air turbulence, there should be no obstructions, turns 
or VAV terminal boxes up or down-stream of the sense tube 
location for at least 6 to 10 times the diameter of the duct. 
The sensor is located in the control box just below the 
Millennium

®

 

Simplicity

®

 control.

BPS 

- The Building Pressure Sensor (PN: 031-01262-000A) is 

a factory-installed Johnson Controls DPT-2640-522 transducer 
that provides a 0 to 5 VDC signal to the controller over a range 
from -0.25”WC to +0.25”WC. The transducer is located in the 
control box just below the Millennium

®

 

Simplicity

®

 control. The 

sense tubes are field installed with the outside pressure being 
sensed external to the unit. To avoid an erratic pressure 
reading, the building pressure sense tube should be mounted 
in an area away from the return air grill, discharge diffusers, 
doors and windows.

BINARY INPUTS (BI)

APS 

- Supply Fan status is monitored by an Air Proving 

Status switch (PN: 024-27557-000A) installed at the factory. 
The APS monitors the difference in pressure between the 
suction and discharge of the fan.

FOVR 

- Monitoring loop through the supply fan overload 

module or VFD over torque indication.

HPS1-4

LPS1-4 

- The refrigerant high pressure (HP) and low 

pressure (LP) safety switches, are independently monitored 
by the Millennium

®

 

Simplicity

®

. If any switch opens, the 

control voltage from the control binary output is interrupted 
and the status is monitored by the control.

G, OCC, P 

- These signals represent Fan (G), Building 

Occupancy (OCC), and Building Purge (P) calls from the 

Summary of Contents for MILLENIUM SIMPLICITY ELITE Series

Page 1: ...ntrols These procedures are the same for all 25 40 Ton Millennium Rooftop units in this series except as noted This manual covers Simplicity controls only for unit installation information please refe...

Page 2: ...ATING WITH W1 W2 AND W3 INPUTS 30 SENSOR OPERATION 30 TYPES OF SPACE SENSORS 31 VAV OPERATION 32 SUPPLY DUCT PRESSURE CONTROL ALGORITHM 34 MORNING WARM UP VAV OCCUPIED HEATING CONTROL ALGORITHM 34 CON...

Page 3: ...e clock function with minimum of ten hours Time of day retention with unit power off The Millennium Simplicity control is resistor configured for Constant Volume CV units or Variable Air Volume VAV un...

Page 4: ...nsed input value s start up ramp time initial start value maximum output control value a status point to initiate the control action i e a fan ON status Direct or Reverse Controlling Action and severa...

Page 5: ...ODBUS communication protocol A communication protocol is simply a set of rules that determine how two systems communicate with each other over some medium such as a pair of wires phone line radio wave...

Page 6: ...C1O 4O Table 1 Acronyms Inputs Description APS Air Proving Switch IAQ Air Quality CO2 Sensor BAS Economizer Passes BAS economizer command through to Economizer output BPS Building Pressure Sensor C1O...

Page 7: ...actor and flash the appropriate flash code This flash code is not an alarm If the control already has contactors pulled in it will monitor the voltage and drop the contactors and shut down if the volt...

Page 8: ...D and Heating water valves Since these outputs are analog they are continuous between 2 and 10 Volts and are proportional to the 0 to 100 drive position of the device ECO Economizer Actuator The modul...

Page 9: ...cuit 2 24 VAC sense LPS3 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 3 24 VAC sense LPS4 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 4 24 VAC sense Limit Switch 1 18 30 VAC On Of...

Page 10: ...ts Heat 1 contactor output Relay Contacts 24 VAC 120 VAC H2 Class 1 Relay Contacts Heat 2 contactor output Relay Contacts 24 VAC 120 VAC H3 Class 1 Relay Contacts Heat 3 contactor output Relay Contact...

Page 11: ...l Also if there are field changes i e a modulating power exhaust option the control configuration will need to be modified for the new option METRIC OPERATION ENGLISH The factory default for this opti...

Page 12: ...cond Stage Setpoint 50 F This tells the control what Supply Air Temperature to maintain for a call for second stage of cooling This is used only during Constant Volume cooling mode with Economizer ope...

Page 13: ...e SAT Setpoint for Cooling 60 F The control will maintain this SAT when operating in VAV mode with a thermostat that is calling for first stage cooling This parameter may be adjusted from 40 F to 70 F...

Page 14: ...is operating the Fan it will close the Economizer fully until the freeze condition is over If the fan is off and the RAT drops below 40 F the Hot Water Valve will turn on 100 Supply AirTemp SAT Alarm...

Page 15: ...1 000 ppm Demand Ventilation Setpoint 1000 ppm This Setpoint is the maximum Indoor Air Quality IAQ level that the control will allow It is adjustable from 700 ppm to 1500 ppm IAQ Sensor Range 5 000 pp...

Page 16: ...80 180 150 21 Hydronic Heating Reverse Actuated Valve ON OFF ON OFF OFF 22 Remote Control ON OFF ON OFF OFF 23 VAV Upper Cooling SAT F 40 70 60 24 VAV Lower Cooling SAT F 40 70 55 25 VAV SAT Reset Set...

Page 17: ...180 Read Only Read Only 66 RAT Return Air Temp F 40 to 180 Read Only Read Only 67 OAT Outside Air Temp F 40 to 180 Read Only Read Only 68 ST Space Temp F 40 to 180 Read Only Read Only 69 OAH Outside A...

Page 18: ...y holidays In addition to the programmed schedule the space sensor allows a single key press to provide up to a 4 hour unoccupied override into the occupied mode OCCUPIED MODE The supply fan operates...

Page 19: ...ops below 180 psi R22 300 psi R410a condenser fan 4 contactor 9M is brought on by PS6 monitoring discharge pressure on compressor 2 4 A control call for Compressor 2 powers contactor 2M through termin...

Page 20: ...s listed below Dry Bulb The control relies on the RAT OAT and SAT readings connected to those terminals on the control Free cooling will be available until the outdoor tempera ture rises above the ind...

Page 21: ...de the duct pres sure controller if that option is installed is activated the optional power exhaust system is activated power is applied to the airflow proving switch APS and to the sup ply fan motor...

Page 22: ...ed The optional power exhaust system is activated In heat mode cooling is disabled and the optional econo mizer outside air dampers are closed This operation is maintained until the space temperature...

Page 23: ...wo stage ignition control For faster heat exchanger warm up the ICB will automatically run each module on high fire for 30 seconds given a low fire only call for heat Because the use of two stage modu...

Page 24: ...65 73 On On On Off On Off 10 426 664 341 331 80 On On On On On Off 11 495 997 396 798 93 On On On Off On On 12 533 330 426 664 100 On On On On On On Gas Heat Module Step Input Output of Total Output L...

Page 25: ...ntrol calculates a 2 10VDC signal to the inlet guide vane actuator 17 Duct Pressure Control VFD Variable Frequency Drive Option The duct pressure controls are powered with a call for the supply fan On...

Page 26: ...ed and are not modulated The BPS signal is proportional with the dif ference between outside ambient pressure and build ing pressure The VFD is set for a minimum speed of 33 and a maximum of 100 The V...

Page 27: ...g and very little peripheral hardware This reduces the costs associated with manufacturing and servicing equipment with this level of interacting features but you can t see the status of interlocked r...

Page 28: ...the ventilation air temperature is trimmed to be within the specified SAT control band Comfort Ventilation mode terminates when there is a call for heating or cooling from the space temperature contro...

Page 29: ...cycling between a satisfied and a heating state under control of a zone thermostat or zone sensor In its OFF state the control algorithm continues monitoring the SAT and performs calculations necessa...

Page 30: ...case G ON The operation of the thermostat s G signal is determined by the thermostat s fan mode switch NOTE During Economizer operation using Economizer First Stage Setpoint for SAT control one or mo...

Page 31: ...zone heating demand of 1 5 F will generate a request for first stage heat A zone heating demand of 2 0 F will generate a request for second stage heat A zone heating demand of 2 5 F will generate a r...

Page 32: ...ne thermostat The setpoint setting should prevent a possibility of cooling turned off while other zone s in the system still have a cooling demand VAV OPERATION WITH A ZONE SENSOR The Space Sensor is...

Page 33: ...the Space Sensor algorithm requests heating no heating all heating stages OFF when the Space Sensor algorithm is satisfied note that in this case the control will use all available heating stages rega...

Page 34: ...ekly schedule MWU Morning Warm Up is initiated upon all transitions from Unoccupied to Occupied mode The system clock is used to identify for the Morning Warm Up a 1 hour period before actual occupanc...

Page 35: ...owing control algorithm OCCUPIED VAV HEATING COOLING CONTROL ALGORITHM WITH A SPACE SENSOR In the occupied mode the control will compare the temperature in a selected VAV zone to the programmed VAV SA...

Page 36: ...ition setting represents the minimum opening of the outdoor air damper open This setting will be maintained any time the unit is in Occupied mode The minimum position setting will be determined by an...

Page 37: ...2 F and 1 BTU LB differentials respectively on both sides of these limits This is similar to the Outside Enthalpy method except instead of a programmed Enthalpy Number an actually sensed return air e...

Page 38: ...for several compressors exists the compressors will turn on with a delay between compressors Economizer Loading Option This is a programmable option The user has the ability to turn this function off...

Page 39: ...heating controls SAT to a fixed temperature deadband of programmed Econo mizer Loading Setpoint in Heating and 5 F below this setpoint the setpoint is programmable between 100 F 195 F default is 160...

Page 40: ...10 open whichever is greater Default Setpoint settings for the EF to turn ON at Economizer 60 open turn OFF at Economizer 20 open The EF has a minimum run time of 10 seconds and a minimum off time of...

Page 41: ...quency drive speed signal Where a unit has both ERV and an economizer the ERV will stop wheel rotation when the economizer dampers open far enough to trigger the user settable switch in the damper act...

Page 42: ...this stage of heating 18 Third stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the contro...

Page 43: ...automatically terminate when the sensor is again detected as reliable If the unit is shut down as a result of a sensor failure the alarm must be reset after the sensor problem has been corrected by re...