351579-YTS-B-0608

22

Johnson Controls Unitary Products

(optional) are disabled, so cooling is disabled and the 
optional economizer outside air dampers are closed.

3.

When the return air temperature climbs above the MWUP 
setpoint, heating is disabled, VAV and the economizer are 
enabled.

4.

A call for first stage cooling initiates the cooling sequence. 
The optional economizer is enabled, and drives the 
damper to the minimum open position. If free cooling is 
available, dampers open to satisfy setpoints. If there is no 
economizer, the control powers terminal C1 to energize 
compressor 1.

The control provides a minimum of 30 seconds between 
each cooling stage call [see Lead-Lag], a 4 minute mini-
mum ON time for each cooling stage and a 5 minute mini-
mum OFF time for each cooling stage.

5.

A call for Compressor 1 powers the high pressure safety 
switch (HPS1), the low pressure switch (LPS1), the coil of 
contactor 6M (condenser fan 1), and the coil of contactor 
7M (contactor, condenser fan 2) through condenser fan 
cycling switch PS5 (PS5 disables condenser fan 2 opera-
tion based upon the discharge pressure of the Compressor 
1). If the system pressures are within HPS1 (high refriger-
ant pressure) and LPS1 (low refrigerant pressure) switch 
settings is not tripped, contactor 1M is engaged to start 
scroll Compressor 1.

6.

A call for Compressor 2 powers contactor 2M (contactor, 
compressor 2) if HPS2 and LPS2 (high and low refrigerant 
pressure) contacts are closed.

7.

30 and 40 ton only (all R410a)

: A call for Compressor 3 

powers the coils of contactors 8M (contactor, condenser 
fan 3) and 9M (contactor, condenser fan 4 - 40 ton only). If 
HPS3 and LPS3 (high and low refrigerant pressure) con-
tacts are closed, power is applied to the coil of Contactor 
3M, which starts compressor 3.

8.

40 Ton Only (all R410a)

: A call for Compressor 4 powers 

the coils of contactor 4M if HPS4 and LPS4 (high and low 
refrigerant pressure) contacts are closed.

9.

When the internal time clock matches the setting in the hol-
iday and daily schedules, the unit enters Unoccupied 
mode. The control disables the supply fan, the optional 
power exhaust, cooling, heating, and the economizer. The 
optional outside air dampers are closed with the optional 
inlet guide vanes.

10. When the space temperature falls below the heating set-

point, the control powers contactor 5M from terminal FAN 
to engage the supply fan motor. If the supply fan operates 
correctly (proper rotation) the pressure difference between 
the heating section and the supply fan section increases 
and APS closes to enable heating operation. If heat safe-
ties are satisfied, the VAV speed signal (VFD or Inlet Guide 
Vanes) goes to maximum flow [the customer-installed con-
nection will drive the VAV boxes to full open]. The control 
engages unit heat (optional) at full capacity. Until heat is 

energized, duct pressure control is activated. The optional 
power exhaust system is activated.

In heat mode, cooling is disabled and the optional econo-
mizer outside air dampers are closed. This operation is 
maintained until the space temperature rises above the 
heating setpoint or Occupied mode is engaged.

11.

Gas Heat Single Stage Module

: Each module installed 

has it own ignition control and its own set of safeties. When 
there is a call for heat from the unit control board (UCB) for 
each module, the ignition control board (ICB) for that mod-
ule checks the state of the flame sense, the roll out switch, 
the pressure switch and the primary temperature limit 
switch circuits for that module. If they are in the expected 
state, then the ICB energizes the draft motor and verifies 
that the pressure switch closes. After the pressure switch 
closes, a 30 second heat exchanger purging period is com-
pleted. After this purging period, the ICB will energize the 
gas valve and the ignition coil for 10 seconds. Once the 
flame sensor senses a flame is present, the ignition coil is 
de-energized. The ICB monitors flame stability for 10 sec-
onds. The ICB will retry 3 times to obtain a stable flame. If 
the furnace fails to light 3 times during the same call for 
heat, then the ICB will lock out operation of that module 
until the next call for heat exists. The ICB monitors the 
module's safety devices during that module's operation. 
When the UCB de-energizes the call for heat for a given 
module, the ICB closes the gas valve for that module and 
performs a 30 second purging of the heat exchanger by 
continuing the operation of the draft motor. 

Gas Heat Operation Errors

 - During furnace operation, 

the ICB monitors the flame sense circuit, the pressure 
switch, the primary limit switch and the roll out switch. If 
a signal from any of the inputs moves to a fault state, 
then the ICB immediately closes the main gas valve. 
The ICB will determine the device that is signaling a fault 
and flash a code for that device (Table 7). A primary limit 
trip, pressure switch trip or flame sense fault triggers a 
temporary lock out. A roll out switch trip requires manual 
reset. Some UCB's installed on Millennium also monitor 
the primary limit and/or gas valve for fault conditions to 
set warning flags.

Temperature Limits

 - The primary limit is located such 

that a temperature sensitive switch can sense the tem-
perature of the heat exchanger tubes. The limit is 
mounted just above the inlet of the heat exchanger 
tubes on the left side. If a primary limit fault occurs (the 
primary limit opens due to excessive heat exchanger 
temperature), then the ICB will flash the appropriate 
code (Table 7) and monitor the primary limit. The ICB will 
energize the draft motor during the time the primary limit 
is open. When the primary limit closes and the call for 
heat still exists, the ICB will start the ignition sequence 
over.

Gas Valve

 - The gas valve is of the redundant type such 

that if either one of two valves inside the gas valve fails 
to shut off the gas flow then the other valve will shut off 
the flow.

Summary of Contents for MILLENIUM SIMPLICITY ELITE Series

Page 1: ...ntrols These procedures are the same for all 25 40 Ton Millennium Rooftop units in this series except as noted This manual covers Simplicity controls only for unit installation information please refe...

Page 2: ...ATING WITH W1 W2 AND W3 INPUTS 30 SENSOR OPERATION 30 TYPES OF SPACE SENSORS 31 VAV OPERATION 32 SUPPLY DUCT PRESSURE CONTROL ALGORITHM 34 MORNING WARM UP VAV OCCUPIED HEATING CONTROL ALGORITHM 34 CON...

Page 3: ...e clock function with minimum of ten hours Time of day retention with unit power off The Millennium Simplicity control is resistor configured for Constant Volume CV units or Variable Air Volume VAV un...

Page 4: ...nsed input value s start up ramp time initial start value maximum output control value a status point to initiate the control action i e a fan ON status Direct or Reverse Controlling Action and severa...

Page 5: ...ODBUS communication protocol A communication protocol is simply a set of rules that determine how two systems communicate with each other over some medium such as a pair of wires phone line radio wave...

Page 6: ...C1O 4O Table 1 Acronyms Inputs Description APS Air Proving Switch IAQ Air Quality CO2 Sensor BAS Economizer Passes BAS economizer command through to Economizer output BPS Building Pressure Sensor C1O...

Page 7: ...actor and flash the appropriate flash code This flash code is not an alarm If the control already has contactors pulled in it will monitor the voltage and drop the contactors and shut down if the volt...

Page 8: ...D and Heating water valves Since these outputs are analog they are continuous between 2 and 10 Volts and are proportional to the 0 to 100 drive position of the device ECO Economizer Actuator The modul...

Page 9: ...cuit 2 24 VAC sense LPS3 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 3 24 VAC sense LPS4 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 4 24 VAC sense Limit Switch 1 18 30 VAC On Of...

Page 10: ...ts Heat 1 contactor output Relay Contacts 24 VAC 120 VAC H2 Class 1 Relay Contacts Heat 2 contactor output Relay Contacts 24 VAC 120 VAC H3 Class 1 Relay Contacts Heat 3 contactor output Relay Contact...

Page 11: ...l Also if there are field changes i e a modulating power exhaust option the control configuration will need to be modified for the new option METRIC OPERATION ENGLISH The factory default for this opti...

Page 12: ...cond Stage Setpoint 50 F This tells the control what Supply Air Temperature to maintain for a call for second stage of cooling This is used only during Constant Volume cooling mode with Economizer ope...

Page 13: ...e SAT Setpoint for Cooling 60 F The control will maintain this SAT when operating in VAV mode with a thermostat that is calling for first stage cooling This parameter may be adjusted from 40 F to 70 F...

Page 14: ...is operating the Fan it will close the Economizer fully until the freeze condition is over If the fan is off and the RAT drops below 40 F the Hot Water Valve will turn on 100 Supply AirTemp SAT Alarm...

Page 15: ...1 000 ppm Demand Ventilation Setpoint 1000 ppm This Setpoint is the maximum Indoor Air Quality IAQ level that the control will allow It is adjustable from 700 ppm to 1500 ppm IAQ Sensor Range 5 000 pp...

Page 16: ...80 180 150 21 Hydronic Heating Reverse Actuated Valve ON OFF ON OFF OFF 22 Remote Control ON OFF ON OFF OFF 23 VAV Upper Cooling SAT F 40 70 60 24 VAV Lower Cooling SAT F 40 70 55 25 VAV SAT Reset Set...

Page 17: ...180 Read Only Read Only 66 RAT Return Air Temp F 40 to 180 Read Only Read Only 67 OAT Outside Air Temp F 40 to 180 Read Only Read Only 68 ST Space Temp F 40 to 180 Read Only Read Only 69 OAH Outside A...

Page 18: ...y holidays In addition to the programmed schedule the space sensor allows a single key press to provide up to a 4 hour unoccupied override into the occupied mode OCCUPIED MODE The supply fan operates...

Page 19: ...ops below 180 psi R22 300 psi R410a condenser fan 4 contactor 9M is brought on by PS6 monitoring discharge pressure on compressor 2 4 A control call for Compressor 2 powers contactor 2M through termin...

Page 20: ...s listed below Dry Bulb The control relies on the RAT OAT and SAT readings connected to those terminals on the control Free cooling will be available until the outdoor tempera ture rises above the ind...

Page 21: ...de the duct pres sure controller if that option is installed is activated the optional power exhaust system is activated power is applied to the airflow proving switch APS and to the sup ply fan motor...

Page 22: ...ed The optional power exhaust system is activated In heat mode cooling is disabled and the optional econo mizer outside air dampers are closed This operation is maintained until the space temperature...

Page 23: ...wo stage ignition control For faster heat exchanger warm up the ICB will automatically run each module on high fire for 30 seconds given a low fire only call for heat Because the use of two stage modu...

Page 24: ...65 73 On On On Off On Off 10 426 664 341 331 80 On On On On On Off 11 495 997 396 798 93 On On On Off On On 12 533 330 426 664 100 On On On On On On Gas Heat Module Step Input Output of Total Output L...

Page 25: ...ntrol calculates a 2 10VDC signal to the inlet guide vane actuator 17 Duct Pressure Control VFD Variable Frequency Drive Option The duct pressure controls are powered with a call for the supply fan On...

Page 26: ...ed and are not modulated The BPS signal is proportional with the dif ference between outside ambient pressure and build ing pressure The VFD is set for a minimum speed of 33 and a maximum of 100 The V...

Page 27: ...g and very little peripheral hardware This reduces the costs associated with manufacturing and servicing equipment with this level of interacting features but you can t see the status of interlocked r...

Page 28: ...the ventilation air temperature is trimmed to be within the specified SAT control band Comfort Ventilation mode terminates when there is a call for heating or cooling from the space temperature contro...

Page 29: ...cycling between a satisfied and a heating state under control of a zone thermostat or zone sensor In its OFF state the control algorithm continues monitoring the SAT and performs calculations necessa...

Page 30: ...case G ON The operation of the thermostat s G signal is determined by the thermostat s fan mode switch NOTE During Economizer operation using Economizer First Stage Setpoint for SAT control one or mo...

Page 31: ...zone heating demand of 1 5 F will generate a request for first stage heat A zone heating demand of 2 0 F will generate a request for second stage heat A zone heating demand of 2 5 F will generate a r...

Page 32: ...ne thermostat The setpoint setting should prevent a possibility of cooling turned off while other zone s in the system still have a cooling demand VAV OPERATION WITH A ZONE SENSOR The Space Sensor is...

Page 33: ...the Space Sensor algorithm requests heating no heating all heating stages OFF when the Space Sensor algorithm is satisfied note that in this case the control will use all available heating stages rega...

Page 34: ...ekly schedule MWU Morning Warm Up is initiated upon all transitions from Unoccupied to Occupied mode The system clock is used to identify for the Morning Warm Up a 1 hour period before actual occupanc...

Page 35: ...owing control algorithm OCCUPIED VAV HEATING COOLING CONTROL ALGORITHM WITH A SPACE SENSOR In the occupied mode the control will compare the temperature in a selected VAV zone to the programmed VAV SA...

Page 36: ...ition setting represents the minimum opening of the outdoor air damper open This setting will be maintained any time the unit is in Occupied mode The minimum position setting will be determined by an...

Page 37: ...2 F and 1 BTU LB differentials respectively on both sides of these limits This is similar to the Outside Enthalpy method except instead of a programmed Enthalpy Number an actually sensed return air e...

Page 38: ...for several compressors exists the compressors will turn on with a delay between compressors Economizer Loading Option This is a programmable option The user has the ability to turn this function off...

Page 39: ...heating controls SAT to a fixed temperature deadband of programmed Econo mizer Loading Setpoint in Heating and 5 F below this setpoint the setpoint is programmable between 100 F 195 F default is 160...

Page 40: ...10 open whichever is greater Default Setpoint settings for the EF to turn ON at Economizer 60 open turn OFF at Economizer 20 open The EF has a minimum run time of 10 seconds and a minimum off time of...

Page 41: ...quency drive speed signal Where a unit has both ERV and an economizer the ERV will stop wheel rotation when the economizer dampers open far enough to trigger the user settable switch in the damper act...

Page 42: ...this stage of heating 18 Third stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the contro...

Page 43: ...automatically terminate when the sensor is again detected as reliable If the unit is shut down as a result of a sensor failure the alarm must be reset after the sensor problem has been corrected by re...

Page 44: ...this SAT failure error will be activated The error will be written to the Error History Buffer In networked application the error flag will be readable by the network SUPPLY FAN FAILURE The condition...