351579-YTS-B-0608

Johnson Controls Unitary Products

23

Pressure Switch

 - The pressure switch closes on a 

drop below a specific pressure. On a call for heat, the 
ICB checks the pressure switch for open state before it 
energizes the draft motor. If it is closed, then the ICB will 
lock out the furnace and flash a code (Table 7). If open, 
then the ICB will energize the draft motor and verify that 
the switch closes before initiating the purging and igni-
tion sequence. If at any time during furnace operation 
the pressure switch opens, then the ICB will de-energize 
the gas valve and monitor the pressure switch. If the 
pressure switch closes and the call for heat still exists, 
then the ICB will retry the purging and ignition sequence.

Rollout Switch

 - This temperature sensitive switch is 

mounted on the burner assembly top shield. In the event 
of the flame spilling out into the burner assembly area 
and the rollout switch opens, the ICB will close the gas 
valve and flash a code (Table 7). The ICB cannot be 
reset automatically as the roll out switch is of the manual 
reset type.

Flame Sense Circuit

 - The flame sensor is mounted on 

the left hand side of the burner assembly and is posi-
tioned such that the flame from the first burner from the 
left side surrounds the tip of the sensor. On a call for 
heat the ICB checks for the flame sense circuit to be 
open. If open, then the ICB initiates the purging and igni-
tion sequence. Once the flame is present, the ICB moni-
tors the flame sense circuit for flame stability. If the flame 
is unstable or lost completely, then the ICB will immedi-
ately close the gas valve. The ICB will retry the purging 
and ignition sequence. If the flame is unstable or lost 
more than 5 times during the same call for heat, then the 
ICB will lock out that module and flash the appropriate 
code.

Flash Codes

 - The ICB will initiate a flash code associ-

ated with errors within the ignition and gas control sys-
tem. See Table 7 for the list of codes for the ICB.

12.

Gas Heat Two-Stage Module

: The arrangement and oper-

ation for two stage modules is similar to the single stage 
modules except that the gas valve and the ignition control 
are replaced with a two stage gas valve and a two stage 
ignition control. For faster heat exchanger warm up, the 
ICB will automatically run each module on high fire for 30 
seconds given a low fire only call for heat. Because the use 
of two stage modules is restricted to modulating gas heat, 
there is a Modulating Furnace Control (MFC) with a dedi-
cated discharge air temperature sensor added between the 
UCB and the two stage ignition control for each installed 
module.

13.

Gas Heat Modulating Module

: The modulating module is 

significantly different from the single and two stage mod-
ules. It consists of one module broken into two systems. 
Each system has its own complement of gas valve, ignition 
control, draft motor and safety devices. The burner orifice 
manifold is internally sealed such that the left three burners 
are supplied with fuel from one two stage gas valve while 
the right two burners are supplied with fuel by a second two 
stage gas valve. This modulating module is always present 
on a modulating furnace with additional two stage modules 
installed as required by the application.

Modulating Furnace Control

 - The Modulating Furnace 

Control (MFC) is designed to accept a W1 and W2 call 
for heat and then control up to 8 stages of gas heat for 
up to 17 steps of gas heat input rates. It is configurable 
for air tempering in free cooling mode without any input 
from the UCB when in constant volume air flow that is at 
or above the minimum air flow for heating. It uses config-
urable values and sensor input to determine the amount 
of heat that is required to meet the heating load up to the 
maximum heat output that is installed. Below is the 
sequence of steps for the three different systems avail-
able. The LF and HF designations represent the low fire 
and high fire gas valve signal for each system, See 
Table 8. Modulating Gas Furnace control board failure 
codes are found in Table 9.

Table 7: Ignition Control Board Flash Codes

Flash Code

Description

Heart Beat

Normal Operation

1 Flash

Not Applicable

2 Flashes

Pressure / Centrifugal Switch Open with Inducer On

3 Flashes

Pressure / Centrifugal Switch Closed with Inducer 
Off

4 Flashes

Lock Out From Too Many Failed Ignition Tries

5 Flashes

Lock Out From Too Many Flame Losses

6 Flashes

High Temperature Switch Open

7 Flashes

Rollout Switch Open

8 Flashes

Flame Present With Gas Off

9 Flashes

Exceeded Max Limit Trips In One Call For Heat (5)

10 Flashes

Gas Valve Stuck Off or On

Summary of Contents for MILLENIUM SIMPLICITY ELITE Series

Page 1: ...ntrols These procedures are the same for all 25 40 Ton Millennium Rooftop units in this series except as noted This manual covers Simplicity controls only for unit installation information please refe...

Page 2: ...ATING WITH W1 W2 AND W3 INPUTS 30 SENSOR OPERATION 30 TYPES OF SPACE SENSORS 31 VAV OPERATION 32 SUPPLY DUCT PRESSURE CONTROL ALGORITHM 34 MORNING WARM UP VAV OCCUPIED HEATING CONTROL ALGORITHM 34 CON...

Page 3: ...e clock function with minimum of ten hours Time of day retention with unit power off The Millennium Simplicity control is resistor configured for Constant Volume CV units or Variable Air Volume VAV un...

Page 4: ...nsed input value s start up ramp time initial start value maximum output control value a status point to initiate the control action i e a fan ON status Direct or Reverse Controlling Action and severa...

Page 5: ...ODBUS communication protocol A communication protocol is simply a set of rules that determine how two systems communicate with each other over some medium such as a pair of wires phone line radio wave...

Page 6: ...C1O 4O Table 1 Acronyms Inputs Description APS Air Proving Switch IAQ Air Quality CO2 Sensor BAS Economizer Passes BAS economizer command through to Economizer output BPS Building Pressure Sensor C1O...

Page 7: ...actor and flash the appropriate flash code This flash code is not an alarm If the control already has contactors pulled in it will monitor the voltage and drop the contactors and shut down if the volt...

Page 8: ...D and Heating water valves Since these outputs are analog they are continuous between 2 and 10 Volts and are proportional to the 0 to 100 drive position of the device ECO Economizer Actuator The modul...

Page 9: ...cuit 2 24 VAC sense LPS3 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 3 24 VAC sense LPS4 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 4 24 VAC sense Limit Switch 1 18 30 VAC On Of...

Page 10: ...ts Heat 1 contactor output Relay Contacts 24 VAC 120 VAC H2 Class 1 Relay Contacts Heat 2 contactor output Relay Contacts 24 VAC 120 VAC H3 Class 1 Relay Contacts Heat 3 contactor output Relay Contact...

Page 11: ...l Also if there are field changes i e a modulating power exhaust option the control configuration will need to be modified for the new option METRIC OPERATION ENGLISH The factory default for this opti...

Page 12: ...cond Stage Setpoint 50 F This tells the control what Supply Air Temperature to maintain for a call for second stage of cooling This is used only during Constant Volume cooling mode with Economizer ope...

Page 13: ...e SAT Setpoint for Cooling 60 F The control will maintain this SAT when operating in VAV mode with a thermostat that is calling for first stage cooling This parameter may be adjusted from 40 F to 70 F...

Page 14: ...is operating the Fan it will close the Economizer fully until the freeze condition is over If the fan is off and the RAT drops below 40 F the Hot Water Valve will turn on 100 Supply AirTemp SAT Alarm...

Page 15: ...1 000 ppm Demand Ventilation Setpoint 1000 ppm This Setpoint is the maximum Indoor Air Quality IAQ level that the control will allow It is adjustable from 700 ppm to 1500 ppm IAQ Sensor Range 5 000 pp...

Page 16: ...80 180 150 21 Hydronic Heating Reverse Actuated Valve ON OFF ON OFF OFF 22 Remote Control ON OFF ON OFF OFF 23 VAV Upper Cooling SAT F 40 70 60 24 VAV Lower Cooling SAT F 40 70 55 25 VAV SAT Reset Set...

Page 17: ...180 Read Only Read Only 66 RAT Return Air Temp F 40 to 180 Read Only Read Only 67 OAT Outside Air Temp F 40 to 180 Read Only Read Only 68 ST Space Temp F 40 to 180 Read Only Read Only 69 OAH Outside A...

Page 18: ...y holidays In addition to the programmed schedule the space sensor allows a single key press to provide up to a 4 hour unoccupied override into the occupied mode OCCUPIED MODE The supply fan operates...

Page 19: ...ops below 180 psi R22 300 psi R410a condenser fan 4 contactor 9M is brought on by PS6 monitoring discharge pressure on compressor 2 4 A control call for Compressor 2 powers contactor 2M through termin...

Page 20: ...s listed below Dry Bulb The control relies on the RAT OAT and SAT readings connected to those terminals on the control Free cooling will be available until the outdoor tempera ture rises above the ind...

Page 21: ...de the duct pres sure controller if that option is installed is activated the optional power exhaust system is activated power is applied to the airflow proving switch APS and to the sup ply fan motor...

Page 22: ...ed The optional power exhaust system is activated In heat mode cooling is disabled and the optional econo mizer outside air dampers are closed This operation is maintained until the space temperature...

Page 23: ...wo stage ignition control For faster heat exchanger warm up the ICB will automatically run each module on high fire for 30 seconds given a low fire only call for heat Because the use of two stage modu...

Page 24: ...65 73 On On On Off On Off 10 426 664 341 331 80 On On On On On Off 11 495 997 396 798 93 On On On Off On On 12 533 330 426 664 100 On On On On On On Gas Heat Module Step Input Output of Total Output L...

Page 25: ...ntrol calculates a 2 10VDC signal to the inlet guide vane actuator 17 Duct Pressure Control VFD Variable Frequency Drive Option The duct pressure controls are powered with a call for the supply fan On...

Page 26: ...ed and are not modulated The BPS signal is proportional with the dif ference between outside ambient pressure and build ing pressure The VFD is set for a minimum speed of 33 and a maximum of 100 The V...

Page 27: ...g and very little peripheral hardware This reduces the costs associated with manufacturing and servicing equipment with this level of interacting features but you can t see the status of interlocked r...

Page 28: ...the ventilation air temperature is trimmed to be within the specified SAT control band Comfort Ventilation mode terminates when there is a call for heating or cooling from the space temperature contro...

Page 29: ...cycling between a satisfied and a heating state under control of a zone thermostat or zone sensor In its OFF state the control algorithm continues monitoring the SAT and performs calculations necessa...

Page 30: ...case G ON The operation of the thermostat s G signal is determined by the thermostat s fan mode switch NOTE During Economizer operation using Economizer First Stage Setpoint for SAT control one or mo...

Page 31: ...zone heating demand of 1 5 F will generate a request for first stage heat A zone heating demand of 2 0 F will generate a request for second stage heat A zone heating demand of 2 5 F will generate a r...

Page 32: ...ne thermostat The setpoint setting should prevent a possibility of cooling turned off while other zone s in the system still have a cooling demand VAV OPERATION WITH A ZONE SENSOR The Space Sensor is...

Page 33: ...the Space Sensor algorithm requests heating no heating all heating stages OFF when the Space Sensor algorithm is satisfied note that in this case the control will use all available heating stages rega...

Page 34: ...ekly schedule MWU Morning Warm Up is initiated upon all transitions from Unoccupied to Occupied mode The system clock is used to identify for the Morning Warm Up a 1 hour period before actual occupanc...

Page 35: ...owing control algorithm OCCUPIED VAV HEATING COOLING CONTROL ALGORITHM WITH A SPACE SENSOR In the occupied mode the control will compare the temperature in a selected VAV zone to the programmed VAV SA...

Page 36: ...ition setting represents the minimum opening of the outdoor air damper open This setting will be maintained any time the unit is in Occupied mode The minimum position setting will be determined by an...

Page 37: ...2 F and 1 BTU LB differentials respectively on both sides of these limits This is similar to the Outside Enthalpy method except instead of a programmed Enthalpy Number an actually sensed return air e...

Page 38: ...for several compressors exists the compressors will turn on with a delay between compressors Economizer Loading Option This is a programmable option The user has the ability to turn this function off...

Page 39: ...heating controls SAT to a fixed temperature deadband of programmed Econo mizer Loading Setpoint in Heating and 5 F below this setpoint the setpoint is programmable between 100 F 195 F default is 160...

Page 40: ...10 open whichever is greater Default Setpoint settings for the EF to turn ON at Economizer 60 open turn OFF at Economizer 20 open The EF has a minimum run time of 10 seconds and a minimum off time of...

Page 41: ...quency drive speed signal Where a unit has both ERV and an economizer the ERV will stop wheel rotation when the economizer dampers open far enough to trigger the user settable switch in the damper act...

Page 42: ...this stage of heating 18 Third stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the contro...

Page 43: ...automatically terminate when the sensor is again detected as reliable If the unit is shut down as a result of a sensor failure the alarm must be reset after the sensor problem has been corrected by re...

Page 44: ...this SAT failure error will be activated The error will be written to the Error History Buffer In networked application the error flag will be readable by the network SUPPLY FAN FAILURE The condition...

Reviews: