Once the Unoccupied Override mode is initiated, it will continue 
until the programmed Unoccupied Override Time Limit is 
reached. The Override mode can not be cancelled by, for 
example, a change of state of the Occupied input to ON 
(occupied) and then back to OFF (unoccupied).

This parameter is adjustable from 0 to 240 minutes. The default 
is 60 minutes.

Fan Delays (ON) & (OFF) -

 Any time the control starts a 

compressor it will load the Fan On Delay for Cool with the 
programmed value. Any time the control turns off all the 
compressors it will load the Fan Off Delay for Cool with the 
programmed value. 

When the control turns on a gas heat stage, it will begin 
monitoring the gas valve and load the Fan On Delay For Heat 
with the programmed value when it senses gas valve voltage. If 
modulating gas heat is installed, then Fan Off Delay in heating 
must be set to Off.

When the thermostat terminates the call for W1 the control will 
turn off H1 output and load the Fan Off Delay for Heat with the 
programmed value.

After the control has turned on heat, it will start monitoring the 
Gas Valve. If at any time the Gas Valve (24 VAC) is not present 
for five minutes while H1 is on, the control will flag an Alarm. 
Anytime GV1/H1 goes off during the fan on delay, the control 
will force the fan on, for the fan off delay period. The control will 
wait for GV1 to be on at least 15 seconds before forcing the fan 
on. If GV1 has been on for at least 15 seconds, and then goes 
away before the Fan On Delay has finished, the fan will turn on 
anyway far a length of time equal to the Fan Off Delay period. 

If the control senses this input along with a Y signal, it will not 
turn on the compressors and it will run the Heating mode. 
Heating takes priority.

Fan ON Mode with the Sensor Option - (ON) -

 When this 

option is turned ON, the supply fan will continue running when 
the zone sensor based temperature control is satisfied. This 
option applies only in systems using a zone sensor and only in 
Occupied mode. With this option turned OFF, or in Unoccupied 
mode, the fan will go off when the zone sensor based 
temperature control is satisfied and will go on only when there is 
a call for heating or cooling. Turning this option ON is an 
equivalent of selecting fan ON (rather than AUTO) in systems 
with a thermostat. In a thermostat system, the fan control follows 
the thermostat's G signal. In sensor systems and in the Occupied 
mode, the fan control follows the Fan ON Mode option.

Space Sensor Enable - (OFF) (INTERNALLY SET) -

 The 

control will use this input if it detects the device.

RAT Sensor Enable - (OFF) (INTERNALLY SET) -

 The control 

will use this input if it detects the device.

Demand Ventilation (ON) -

 Setting this parameter on tells the 

control to expect a signal from a 0-10VDC CO

sensor. The 

default setting for CO

2

 is 1,000 ppm.

Demand Ventilation Setpoint - (1000 ppm) -

 This Setpoint is 

the maximum Indoor Air Quality (IAQ) level that the control will 
allow. It is adjustable from 700 ppm to 1500 ppm.

IAQ Sensor Range - (5,000 ppm) -

 This tells the control what 

the full range is for a specific IAQ sensor. It can be changed 
from 0 to 10,000 ppm.

Cooling Mode Enable (ON) -

 This tells the control if it has 

Cooling Available (Mode Switch). If this option is turned off, 
cooling operation is disabled. Note that this parameter does not 
affect cooling operation in Comfort Ventilation mode.

Heating Mode Enable - (ON) - 

This tells the control if it has 

Heating Available (Mode Switch). If this option is turned off, 
heating operation is disabled. Note that this parameter does not 
affect heating operation in Comfort Ventilation mode.

Space Setpoint Offset - (3 °F) -

 The Space Setpoint Offset is 

the +/- value the control will use to offset the Space Setpoint 
when the slidebar Space Sensor is used. For example, if the 
Space Setpoint Offset value is set to 3.0 °F, shifting the slidebar 
all the way in minus direction will decrease the Space Setpoint 
by 3.0 °F and shifting it all the way in plus direction will increase 
the Space Setpoint by 3.0 °F. It is adjustable from 0 °F to 5 °F.

ASCD Override -

 This is not an option parameter but rather a 

one-time command issued by pressing the Test / Reset / Up 
button pressed and released within five seconds; the ASCD’s 
will be set to zero for one cycle.

Run Test (Commissioning Test) -

 This is not an option 

parameter but rather a one-time command, activated by setting 
parameter 1 ON.

When the Run Test command is issued, the control will shut the 
unit down if it is running and then start a Run test sequence:

1.

Turn on the Fan and then turn on all the compressors, one 
at a time, with a 15-second delay between them. Con-
denser fan #1 turns on with compressor #1, condenser fan 
#2 turns on with compressor #2. After the last compressor 
has been turned on, the control will run the compressors 
for the programmed minimum run time and then turn them 
all off. Condenser fans are also turned off.

2.

The control will then turn on the Heat stages, one at a time, 
with a 15 second delay between them. The control will run 
each Heat stage for three minutes and then turn all the 
Heat off.

3.

The control will then open the Economizer to the 100% 
open position and wait five minutes before closing it to the 
Minimum Position. When the economizer is at 100%, the 
exhaust damper will be open to 100% and the exhaust fan 
runs for 5 minutes, then shuts down.

4.

During this Run Test operation the control will read all the 
installed sensors and verify that their readings are good. If 
any error is detected the control will display the appropriate 
error. During the Run Test, the supply fan continues to be 
monitored via the Air Proving Switch, and a fan failure will 
cause a unit shutdown.

After the control is finished with the Run Test the normal 
operation will resume. This command is a good method to use 
to ensure the control is operating and all input and output points 
are functional.

Summary of Contents for MILLENIUM SIMPLICITY ELITE Series

Page 1: ...ntrols These procedures are the same for all 25 40 Ton Millennium Rooftop units in this series except as noted This manual covers Simplicity controls only for unit installation information please refe...

Page 2: ...ATING WITH W1 W2 AND W3 INPUTS 30 SENSOR OPERATION 30 TYPES OF SPACE SENSORS 31 VAV OPERATION 32 SUPPLY DUCT PRESSURE CONTROL ALGORITHM 34 MORNING WARM UP VAV OCCUPIED HEATING CONTROL ALGORITHM 34 CON...

Page 3: ...e clock function with minimum of ten hours Time of day retention with unit power off The Millennium Simplicity control is resistor configured for Constant Volume CV units or Variable Air Volume VAV un...

Page 4: ...nsed input value s start up ramp time initial start value maximum output control value a status point to initiate the control action i e a fan ON status Direct or Reverse Controlling Action and severa...

Page 5: ...ODBUS communication protocol A communication protocol is simply a set of rules that determine how two systems communicate with each other over some medium such as a pair of wires phone line radio wave...

Page 6: ...C1O 4O Table 1 Acronyms Inputs Description APS Air Proving Switch IAQ Air Quality CO2 Sensor BAS Economizer Passes BAS economizer command through to Economizer output BPS Building Pressure Sensor C1O...

Page 7: ...actor and flash the appropriate flash code This flash code is not an alarm If the control already has contactors pulled in it will monitor the voltage and drop the contactors and shut down if the volt...

Page 8: ...D and Heating water valves Since these outputs are analog they are continuous between 2 and 10 Volts and are proportional to the 0 to 100 drive position of the device ECO Economizer Actuator The modul...

Page 9: ...cuit 2 24 VAC sense LPS3 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 3 24 VAC sense LPS4 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 4 24 VAC sense Limit Switch 1 18 30 VAC On Of...

Page 10: ...ts Heat 1 contactor output Relay Contacts 24 VAC 120 VAC H2 Class 1 Relay Contacts Heat 2 contactor output Relay Contacts 24 VAC 120 VAC H3 Class 1 Relay Contacts Heat 3 contactor output Relay Contact...

Page 11: ...l Also if there are field changes i e a modulating power exhaust option the control configuration will need to be modified for the new option METRIC OPERATION ENGLISH The factory default for this opti...

Page 12: ...cond Stage Setpoint 50 F This tells the control what Supply Air Temperature to maintain for a call for second stage of cooling This is used only during Constant Volume cooling mode with Economizer ope...

Page 13: ...e SAT Setpoint for Cooling 60 F The control will maintain this SAT when operating in VAV mode with a thermostat that is calling for first stage cooling This parameter may be adjusted from 40 F to 70 F...

Page 14: ...is operating the Fan it will close the Economizer fully until the freeze condition is over If the fan is off and the RAT drops below 40 F the Hot Water Valve will turn on 100 Supply AirTemp SAT Alarm...

Page 15: ...1 000 ppm Demand Ventilation Setpoint 1000 ppm This Setpoint is the maximum Indoor Air Quality IAQ level that the control will allow It is adjustable from 700 ppm to 1500 ppm IAQ Sensor Range 5 000 pp...

Page 16: ...80 180 150 21 Hydronic Heating Reverse Actuated Valve ON OFF ON OFF OFF 22 Remote Control ON OFF ON OFF OFF 23 VAV Upper Cooling SAT F 40 70 60 24 VAV Lower Cooling SAT F 40 70 55 25 VAV SAT Reset Set...

Page 17: ...180 Read Only Read Only 66 RAT Return Air Temp F 40 to 180 Read Only Read Only 67 OAT Outside Air Temp F 40 to 180 Read Only Read Only 68 ST Space Temp F 40 to 180 Read Only Read Only 69 OAH Outside A...

Page 18: ...y holidays In addition to the programmed schedule the space sensor allows a single key press to provide up to a 4 hour unoccupied override into the occupied mode OCCUPIED MODE The supply fan operates...

Page 19: ...ops below 180 psi R22 300 psi R410a condenser fan 4 contactor 9M is brought on by PS6 monitoring discharge pressure on compressor 2 4 A control call for Compressor 2 powers contactor 2M through termin...

Page 20: ...s listed below Dry Bulb The control relies on the RAT OAT and SAT readings connected to those terminals on the control Free cooling will be available until the outdoor tempera ture rises above the ind...

Page 21: ...de the duct pres sure controller if that option is installed is activated the optional power exhaust system is activated power is applied to the airflow proving switch APS and to the sup ply fan motor...

Page 22: ...ed The optional power exhaust system is activated In heat mode cooling is disabled and the optional econo mizer outside air dampers are closed This operation is maintained until the space temperature...

Page 23: ...wo stage ignition control For faster heat exchanger warm up the ICB will automatically run each module on high fire for 30 seconds given a low fire only call for heat Because the use of two stage modu...

Page 24: ...65 73 On On On Off On Off 10 426 664 341 331 80 On On On On On Off 11 495 997 396 798 93 On On On Off On On 12 533 330 426 664 100 On On On On On On Gas Heat Module Step Input Output of Total Output L...

Page 25: ...ntrol calculates a 2 10VDC signal to the inlet guide vane actuator 17 Duct Pressure Control VFD Variable Frequency Drive Option The duct pressure controls are powered with a call for the supply fan On...

Page 26: ...ed and are not modulated The BPS signal is proportional with the dif ference between outside ambient pressure and build ing pressure The VFD is set for a minimum speed of 33 and a maximum of 100 The V...

Page 27: ...g and very little peripheral hardware This reduces the costs associated with manufacturing and servicing equipment with this level of interacting features but you can t see the status of interlocked r...

Page 28: ...the ventilation air temperature is trimmed to be within the specified SAT control band Comfort Ventilation mode terminates when there is a call for heating or cooling from the space temperature contro...

Page 29: ...cycling between a satisfied and a heating state under control of a zone thermostat or zone sensor In its OFF state the control algorithm continues monitoring the SAT and performs calculations necessa...

Page 30: ...case G ON The operation of the thermostat s G signal is determined by the thermostat s fan mode switch NOTE During Economizer operation using Economizer First Stage Setpoint for SAT control one or mo...

Page 31: ...zone heating demand of 1 5 F will generate a request for first stage heat A zone heating demand of 2 0 F will generate a request for second stage heat A zone heating demand of 2 5 F will generate a r...

Page 32: ...ne thermostat The setpoint setting should prevent a possibility of cooling turned off while other zone s in the system still have a cooling demand VAV OPERATION WITH A ZONE SENSOR The Space Sensor is...

Page 33: ...the Space Sensor algorithm requests heating no heating all heating stages OFF when the Space Sensor algorithm is satisfied note that in this case the control will use all available heating stages rega...

Page 34: ...ekly schedule MWU Morning Warm Up is initiated upon all transitions from Unoccupied to Occupied mode The system clock is used to identify for the Morning Warm Up a 1 hour period before actual occupanc...

Page 35: ...owing control algorithm OCCUPIED VAV HEATING COOLING CONTROL ALGORITHM WITH A SPACE SENSOR In the occupied mode the control will compare the temperature in a selected VAV zone to the programmed VAV SA...

Page 36: ...ition setting represents the minimum opening of the outdoor air damper open This setting will be maintained any time the unit is in Occupied mode The minimum position setting will be determined by an...

Page 37: ...2 F and 1 BTU LB differentials respectively on both sides of these limits This is similar to the Outside Enthalpy method except instead of a programmed Enthalpy Number an actually sensed return air e...

Page 38: ...for several compressors exists the compressors will turn on with a delay between compressors Economizer Loading Option This is a programmable option The user has the ability to turn this function off...

Page 39: ...heating controls SAT to a fixed temperature deadband of programmed Econo mizer Loading Setpoint in Heating and 5 F below this setpoint the setpoint is programmable between 100 F 195 F default is 160...

Page 40: ...10 open whichever is greater Default Setpoint settings for the EF to turn ON at Economizer 60 open turn OFF at Economizer 20 open The EF has a minimum run time of 10 seconds and a minimum off time of...

Page 41: ...quency drive speed signal Where a unit has both ERV and an economizer the ERV will stop wheel rotation when the economizer dampers open far enough to trigger the user settable switch in the damper act...

Page 42: ...this stage of heating 18 Third stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the contro...

Page 43: ...automatically terminate when the sensor is again detected as reliable If the unit is shut down as a result of a sensor failure the alarm must be reset after the sensor problem has been corrected by re...

Page 44: ...this SAT failure error will be activated The error will be written to the Error History Buffer In networked application the error flag will be readable by the network SUPPLY FAN FAILURE The condition...

Reviews: