Turning on compressors #2 through #4:

If the economizer controller is saturated High (i.e. the 
economizer is 100% open while one or more compressors are 
running and the control can no longer maintain the active SAT 
setpoint requested by the zone control),

• Temporarily override SAT setpoint to increase it by 5 °F
• When the SAT is within 0.5 °F of this temporary setpoint, 

turn on the next compressor

• Resume SAT control at active setpoint

NOTE:

The pre-staging SAT increase must be done “proac-
tively”, by a temporary override of the active SAT set-
point, rather than by allowing the SAT to “drift” up by 5 °F
out of control. The time it would take for the SAT to “drift”
up could be fairly long, mostly dependent on the outdoor
air temperature change and in the meantime, the zone
temperature may go out of control as the additional
needed cooling is not being delivered.

NOTE:

The standard 5 minute delay before monitoring SAT
after a compressor is turned on, or off, and the check-
ing against a stored, predicted SAT temperature drop,
applies here also.

Turning compressors off:

A highest numbered running compressor is turned off when the 
economizer controller is saturated Low.

This method of turning compressor off is considered better than 
using the Excessive SAT Control - turning a compressor OFF 
only if SAT reaches its specified trip point. If that method was 
used and the Excessive SAT Control was not selected, there 
would be no means for turning compressors off.

NOTE:

The compressors also will be turned off in CV systems
with zone thermostat, or zone sensor temperature
control, when the zone temperature control is satis-
fied. For the case of zone sensor, the compressor
destaging is described in section “CV Operation”,
paragraph “Control Algorithm for Cooling with the Sen-
sor Option, with Economizer”. For the case of zone
thermostat, the compressor destaging is described in
section “CV Operation”, paragraph “Thermostat Oper-
ation for Cooling with Y1 and Y2 inputs”, subpara-
graph “Economizer Mode”.

Compressor control when exiting Cooling Lockout on OAT:

A situation may arise when in Economizer Mode and one or 
more compressors are required in addition to full available free 
cooling in order to maintain the SAT setpoint, but Cooling 
Lockout on OAT prevents the compressors use. This situation 
may arise when the SAT setpoint is set very close to, or even 
below the temperature set for Cooling Lockout on OAT - a 
relatively unusual case. If the OAT then increases above the 
lockout setting while the call for several compressors exists, the 
compressors will turn on with a delay between compressors.

Economizer Loading Option

This is a programmable option. The user has the ability to turn 
this function off. It is automatically disabled if the unit does not 
use an economizer. The on/off programming choice is common 
to both cooling and heating. The default setting is ON. This 
programmable “Economizer Loading” function is used only 
outside the normal Economizer operation.

During the Economizer operation, the “Loading” function is 
always used and is an integral part of the Economizer control 
algorithm.

Economizer loading option in cooling:

In cooling, this function causes changes in mixed air 
temperature (as modulated by the economizer dampers) in 
order to change SAT and keep it at SAT setpoint when only 
compressor #1 is running. This makes a trade-off between 
energy and compressor cycling and minimizes cycling of 
compressor #1. The loading is done by the same type of control 
algorithm (PI) as used in the normal Economizer operation. 

The algorithm will be activated to do this function in following 
conditions:

• Economizer is “not suitable” (i.e. we are not in a normal 

Economizer mode)

• The programmable option “Economizer Loading to Control 

SAT” is ON

• Only compressor #1 is running

The PI control algorithm in this case has a capability to 
automatically change from direct to reverse acting in response 
to difference between OAT and RAT. When OAT is less than 
RAT, the algorithm is direct acting, for OAT 

RAT, the algorithm 

changes to reverse acting. This way, the “loading” of the DX coil 
is correctly done with return, or outdoor air, as appropriate, and 
there is no need to activate this “loading” function only at higher 
outdoor air temperatures (e.g. OAT > 60 °F).

The algorithm controls SAT to its specified setpoint (when 
applicable, e.g. in VAV operation), or, in control modes where no 
SAT setpoint is specified (such as in Excessive SAT control state 
in cooling), to a fixed temperature deadband of 50 °F to 55 °F.

NOTE:

As opposed to the PI algorithm used in economizer
control, the PI algorithm used here for economizer
loading function does not need to utilize the High satu-
ration state for any additional control functions. There-
fore no complications arise when switching between
direct and reverse acting modes.

Economizer loading option in heating:

In heating, this function uses additional outside air (as 
modulated by the economizer dampers) in order to decrease 
SAT when only the first stage of heating is running and keep the 
SAT below the programmed “Economizer Loading Setpoint in 
Heating”. This prevents heating stage from cycling on its 
internal temperature limit safety switch (which is typically set 
about 10 °F

 

above the Economizer Loading Setpoint). A need 

Summary of Contents for MILLENIUM SIMPLICITY ELITE Series

Page 1: ...ntrols These procedures are the same for all 25 40 Ton Millennium Rooftop units in this series except as noted This manual covers Simplicity controls only for unit installation information please refe...

Page 2: ...ATING WITH W1 W2 AND W3 INPUTS 30 SENSOR OPERATION 30 TYPES OF SPACE SENSORS 31 VAV OPERATION 32 SUPPLY DUCT PRESSURE CONTROL ALGORITHM 34 MORNING WARM UP VAV OCCUPIED HEATING CONTROL ALGORITHM 34 CON...

Page 3: ...e clock function with minimum of ten hours Time of day retention with unit power off The Millennium Simplicity control is resistor configured for Constant Volume CV units or Variable Air Volume VAV un...

Page 4: ...nsed input value s start up ramp time initial start value maximum output control value a status point to initiate the control action i e a fan ON status Direct or Reverse Controlling Action and severa...

Page 5: ...ODBUS communication protocol A communication protocol is simply a set of rules that determine how two systems communicate with each other over some medium such as a pair of wires phone line radio wave...

Page 6: ...C1O 4O Table 1 Acronyms Inputs Description APS Air Proving Switch IAQ Air Quality CO2 Sensor BAS Economizer Passes BAS economizer command through to Economizer output BPS Building Pressure Sensor C1O...

Page 7: ...actor and flash the appropriate flash code This flash code is not an alarm If the control already has contactors pulled in it will monitor the voltage and drop the contactors and shut down if the volt...

Page 8: ...D and Heating water valves Since these outputs are analog they are continuous between 2 and 10 Volts and are proportional to the 0 to 100 drive position of the device ECO Economizer Actuator The modul...

Page 9: ...cuit 2 24 VAC sense LPS3 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 3 24 VAC sense LPS4 18 30 VAC On Off 5 VAC Low Pressure Switch for Circuit 4 24 VAC sense Limit Switch 1 18 30 VAC On Of...

Page 10: ...ts Heat 1 contactor output Relay Contacts 24 VAC 120 VAC H2 Class 1 Relay Contacts Heat 2 contactor output Relay Contacts 24 VAC 120 VAC H3 Class 1 Relay Contacts Heat 3 contactor output Relay Contact...

Page 11: ...l Also if there are field changes i e a modulating power exhaust option the control configuration will need to be modified for the new option METRIC OPERATION ENGLISH The factory default for this opti...

Page 12: ...cond Stage Setpoint 50 F This tells the control what Supply Air Temperature to maintain for a call for second stage of cooling This is used only during Constant Volume cooling mode with Economizer ope...

Page 13: ...e SAT Setpoint for Cooling 60 F The control will maintain this SAT when operating in VAV mode with a thermostat that is calling for first stage cooling This parameter may be adjusted from 40 F to 70 F...

Page 14: ...is operating the Fan it will close the Economizer fully until the freeze condition is over If the fan is off and the RAT drops below 40 F the Hot Water Valve will turn on 100 Supply AirTemp SAT Alarm...

Page 15: ...1 000 ppm Demand Ventilation Setpoint 1000 ppm This Setpoint is the maximum Indoor Air Quality IAQ level that the control will allow It is adjustable from 700 ppm to 1500 ppm IAQ Sensor Range 5 000 pp...

Page 16: ...80 180 150 21 Hydronic Heating Reverse Actuated Valve ON OFF ON OFF OFF 22 Remote Control ON OFF ON OFF OFF 23 VAV Upper Cooling SAT F 40 70 60 24 VAV Lower Cooling SAT F 40 70 55 25 VAV SAT Reset Set...

Page 17: ...180 Read Only Read Only 66 RAT Return Air Temp F 40 to 180 Read Only Read Only 67 OAT Outside Air Temp F 40 to 180 Read Only Read Only 68 ST Space Temp F 40 to 180 Read Only Read Only 69 OAH Outside A...

Page 18: ...y holidays In addition to the programmed schedule the space sensor allows a single key press to provide up to a 4 hour unoccupied override into the occupied mode OCCUPIED MODE The supply fan operates...

Page 19: ...ops below 180 psi R22 300 psi R410a condenser fan 4 contactor 9M is brought on by PS6 monitoring discharge pressure on compressor 2 4 A control call for Compressor 2 powers contactor 2M through termin...

Page 20: ...s listed below Dry Bulb The control relies on the RAT OAT and SAT readings connected to those terminals on the control Free cooling will be available until the outdoor tempera ture rises above the ind...

Page 21: ...de the duct pres sure controller if that option is installed is activated the optional power exhaust system is activated power is applied to the airflow proving switch APS and to the sup ply fan motor...

Page 22: ...ed The optional power exhaust system is activated In heat mode cooling is disabled and the optional econo mizer outside air dampers are closed This operation is maintained until the space temperature...

Page 23: ...wo stage ignition control For faster heat exchanger warm up the ICB will automatically run each module on high fire for 30 seconds given a low fire only call for heat Because the use of two stage modu...

Page 24: ...65 73 On On On Off On Off 10 426 664 341 331 80 On On On On On Off 11 495 997 396 798 93 On On On Off On On 12 533 330 426 664 100 On On On On On On Gas Heat Module Step Input Output of Total Output L...

Page 25: ...ntrol calculates a 2 10VDC signal to the inlet guide vane actuator 17 Duct Pressure Control VFD Variable Frequency Drive Option The duct pressure controls are powered with a call for the supply fan On...

Page 26: ...ed and are not modulated The BPS signal is proportional with the dif ference between outside ambient pressure and build ing pressure The VFD is set for a minimum speed of 33 and a maximum of 100 The V...

Page 27: ...g and very little peripheral hardware This reduces the costs associated with manufacturing and servicing equipment with this level of interacting features but you can t see the status of interlocked r...

Page 28: ...the ventilation air temperature is trimmed to be within the specified SAT control band Comfort Ventilation mode terminates when there is a call for heating or cooling from the space temperature contro...

Page 29: ...cycling between a satisfied and a heating state under control of a zone thermostat or zone sensor In its OFF state the control algorithm continues monitoring the SAT and performs calculations necessa...

Page 30: ...case G ON The operation of the thermostat s G signal is determined by the thermostat s fan mode switch NOTE During Economizer operation using Economizer First Stage Setpoint for SAT control one or mo...

Page 31: ...zone heating demand of 1 5 F will generate a request for first stage heat A zone heating demand of 2 0 F will generate a request for second stage heat A zone heating demand of 2 5 F will generate a r...

Page 32: ...ne thermostat The setpoint setting should prevent a possibility of cooling turned off while other zone s in the system still have a cooling demand VAV OPERATION WITH A ZONE SENSOR The Space Sensor is...

Page 33: ...the Space Sensor algorithm requests heating no heating all heating stages OFF when the Space Sensor algorithm is satisfied note that in this case the control will use all available heating stages rega...

Page 34: ...ekly schedule MWU Morning Warm Up is initiated upon all transitions from Unoccupied to Occupied mode The system clock is used to identify for the Morning Warm Up a 1 hour period before actual occupanc...

Page 35: ...owing control algorithm OCCUPIED VAV HEATING COOLING CONTROL ALGORITHM WITH A SPACE SENSOR In the occupied mode the control will compare the temperature in a selected VAV zone to the programmed VAV SA...

Page 36: ...ition setting represents the minimum opening of the outdoor air damper open This setting will be maintained any time the unit is in Occupied mode The minimum position setting will be determined by an...

Page 37: ...2 F and 1 BTU LB differentials respectively on both sides of these limits This is similar to the Outside Enthalpy method except instead of a programmed Enthalpy Number an actually sensed return air e...

Page 38: ...for several compressors exists the compressors will turn on with a delay between compressors Economizer Loading Option This is a programmable option The user has the ability to turn this function off...

Page 39: ...heating controls SAT to a fixed temperature deadband of programmed Econo mizer Loading Setpoint in Heating and 5 F below this setpoint the setpoint is programmable between 100 F 195 F default is 160...

Page 40: ...10 open whichever is greater Default Setpoint settings for the EF to turn ON at Economizer 60 open turn OFF at Economizer 20 open The EF has a minimum run time of 10 seconds and a minimum off time of...

Page 41: ...quency drive speed signal Where a unit has both ERV and an economizer the ERV will stop wheel rotation when the economizer dampers open far enough to trigger the user settable switch in the damper act...

Page 42: ...this stage of heating 18 Third stage of heating is locked out because the ignition board failed to turn on the gas valve after 5 minutes of operation or the gas valve has voltage on it and the contro...

Page 43: ...automatically terminate when the sensor is again detected as reliable If the unit is shut down as a result of a sensor failure the alarm must be reset after the sensor problem has been corrected by re...

Page 44: ...this SAT failure error will be activated The error will be written to the Error History Buffer In networked application the error flag will be readable by the network SUPPLY FAN FAILURE The condition...

Reviews: