background image

INSTALLATION PROCEDURES

The following sequence of installation steps is suggested.
1. Inspect unit and set in place.
2. Check orifice size and replace with correct size if necessary.
3. Route/install the vapor and liquid lines.
4. Connect line and leak test. Evacuate if necessary.
5. Charge system.
6. Make electrical power connections.
7. Make electrical control connections.
8. Instruct owner and operate unit.

UNIT PLACEMENT

1. Provide a base in the pre-determined location.

2. Remove the shipping carton and inspect for possible damage.

3. Compressor tie-down bolts should remain tightened.

CAUTION: Some units may have a shipping block under the

compressor feet. It must be removed before the
unit is started up. Re-tighten tie-down bolts to the
ferrules.

4. Position the unit on the base provided.

5. To reduce noise and to enhance drainage, sit unit on (4)

rubber elevating grommets provided in bulk packed acces-
sory kit model number 1SG0601. Grommets should be
positioned as shown in Figure 2.

6. Make a hole(s) in the structure wall large enough to accom-

modate the insulated vapor line, the liquid line and the wiring.

ORIFICE SELECTION

NOTE:  The proper orifice must be installed in the evaporator

coil liquid connection prior to the connection of the
refrigerant lines.

WARNING: Coil (whether sweat or quick connect) is under 15

PSIG pressure. Use safety glasses and gloves
when handling refrigerants to prevent personal
injury.

Each evaporator coil will have an orifice installed in the fitting
between the liquid line connection and distributor. The orifice
is identified on a label next to the liquid connection as shown.

Sweat coils are shipped with a standard orifice in a plastic bag
attached to the liquid line connection.

The orifice that is shipped with the coil is based on the “most
sold” combination, but it may have to be changed depending
on the capacity and efficiency of the outdoor unit, elevation
differences, and/or long total line lengths. An additional ori-
fice(s) is shipped with most outdoor units in the literature packet
for the most commonly required replacement combinations.
Other sizes must be ordered from the Parts Department if
required.

Table 2 shows the orifice and charge adjustment for approved
system combinations (indoor coil/outdoor unit). See Applica-
tion Data for other piping and orifice considerations for long line
length and elevation differences.

If the orifice sizes match, nothing further is required and the
refrigerant lines may be connected per the outdoor unit instruc-
tion. However, if another orifice should be used, see the coil
instruction for details to change the orifice in the coil. 

LINE INSTALLATION

Sweat-connect systems and systems with stub kits must use field
supplied, clean, dehydrated refrigerant-grade copper tubing.

Unit should be installed only with the specified line sizes for
approved system combinations (indoor coil/outdoor unit) in-
stalled with total line lengths up to 15 feet. See Application Data
for long line lengths and elevation differences.

Using a larger than specified line size could result in oil return

RUBBER
ELEVATING
GROMMETS
(4)

3 - 5
TON
UNIT
BASE
PAN

Note: Do Not  block 
drainage holes with
grommets.

FIGURE 2 - POSITIONING GROMMETS

RUBBER
ELEVATING
GROMMETS
(4)

2 & 2.5
TON
UNIT
BASE
PAN

FIGURE 3 - ORIFICE LABEL 

LABEL

LEFT-HAND THREAD

DISTRIBUTOR

ORIFICE

LIQUID LINE FITTING

WITH #65

ORIFICE

COIL EQUIPPED

550.36-N2Y

Unitary Products Group

3

Summary of Contents for H2DH024S06

Page 1: ...The unit should be installed in accordance with all national and local safety codes Limitations for the indoor unit coil and appropriate accessories must also be observed For piping limitations and a...

Page 2: ...ERHEAD NEC CLASS 2 WIRING Sit unit on rubber elevator grommets to reduce noise and allow for proper drainage FIGURE 1 TYPICAL INSTALLATION MODEL H2DH024 H2DH030 H2DH036 H2DH042 H2DH048 H2DH060 UNIT SU...

Page 3: ...shown Sweat coils are shipped with a standard orifice in a plastic bag attached to the liquid line connection The orifice that is shipped with the coil is based on the most sold combination but it ma...

Page 4: ...The total system refrigerant charge is retained within the outdoor unit during shipping and installation The re usable service valves are provided to evacuate and charge per this instruction Serious s...

Page 5: ...the vapor fitting with a wet rag and braze the vapor line connection The nitrogen flow should be exiting the system from the vapor service port connection After This connection has cooled remove the...

Page 6: ...H2DH060 UNITORIFICE S 61 63 65 75 78 78 81 84 90 93 93 96 FACTORYR 22 CHARGE LBS OZ SWEAT 5 7 5 0 7 12 8 0 11 14 13 0 INDOOR COIL COIL ORIFICE REQUIRED SYSTEM ORIFICE ADDITIONAL CHARGE OZ G3HC G1FC02...

Page 7: ...urate weighing device is available add refrigerant accordingly CAUTION Compressor damage will occurif system is improp erly charged On new system installations charge system per R 22 charge informatio...

Page 8: ...73 75 77 79 79 2 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 82 4 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Saturation Temperature TABLE 5 Temperature and Pressure TEMP F PRESSU...

Page 9: ...re the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at least 8 hours of crankcase heat will damage the com pressor A warning label with an adhesive ba...

Page 10: ...0 60 65 70 75 80 85 90 95 SUCTION PRESSURE PSIG LIQUID PRESSURE PSIG 115 F O D AMBIENT 95 F O D AMBIENT 036 036 036 75 F O D AMBIENT 048 060 042 042 EXAMPLE H2DH036 unit with a 76 PSIG measured suc ti...

Page 11: ...mine if the system is operating properly 1 The outdoor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discha...

Page 12: ...ducts Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rights Reserved RPC 8M 695 66 Code SBY...

Reviews: