To eliminate erratic operation, seal the hole in the wall at the
thermostat with permagum or equivalent to prevent air drafts
affecting the anticipators in the thermostat.
Route the control wiring into the outdoor unit through the hole
provided. Connect the control wiring, per Figure 8.
EVACUATION
It will be necessary to evacuate the system if the unit has
developed a leak during shipment or was, for any other reason,
opened to the atmosphere. If a leak is suspected, leak test to
locate the leak. Repair the leak and test again.
WARNING: Never attempt to repair any brazed connections
while the system is under pressure. Personal injury
could result.
Evacuate the system down to at least 1,000 microns.
To verify if the system has no leaks, simply close the valve to
the vacuum pump suction to isolate the pump and hold the
system under vacuum. Watch the micron gauge for a few
minutes. If the micron gauge indicates a steady and continuous
rise, it’s an indication of a leak.
If the gauge shows a rise, then levels off after a few minutes
and remains fairly constant, its an indication the system is leak
free, but still contains moisture and may require further evacu-
ation if the reading is above 1000 microns.
OUTDOOR UNIT
H2DH024
H2DH030
H2DH036
H2DH042
H2DH048
H2DH060
UNIT ORIFICE(S)**
61,63
65
75,78
78,81,84
90,93
93, 96
FACTORY R-22
CHARGE,LBS. OZ.
SWEAT
5 - 7
5 - 0
7 - 12
8 - 0
11 - 14
13 - 0
INDOOR COIL
COIL
ORIFICE*
REQUIRED SYSTEM O ADDITIONAL CHARGE, OZ.
G3HC / G1FC024
61
61 + 10
-
-
-
-
-
G3HC / G1FC030
69
61 + 23
65+25
-
-
-
-
G3HC / G1FC036
81
-
65+28
78 + 3
-
-
-
G3HC / G1FC042
78
-
-
78 + 8
81 + 16
-
-
G3HC / G1FC048
90
-
-
-
81 + 7
90 + 13
-
G3HC / G1FC060
96
-
-
-
-
90 + 25
96 + 4
G3UA024
59
63 + 0
-
-
-
-
-
G3UA030
65
63 + 2
65+16
-
-
-
-
G3UA036
69
63 + 13
65+32
75 + 9
-
-
-
G3UA037
69
63 + 13
65+32
75 + 9
-
-
-
G3UA048
87
-
-
78 + 17
81 + 16
90 + 14
-
G3UA060
96
-
-
-
84 + 21
90 + 38
96 + 25
G3UA061
96
-
-
-
84 + 21
90 + 29
96 + 25
G2UT048
-
-
-
-
+ 16
-
-
M3CF032
59
61 + 7
65+0
-
-
-
-
M3CF044
69
-
65+0
78 + 2
78 + 3
-
-
M3CF052
84
-
-
-
-
90 + 10
-
G3CN030
65
63 + 2
65+16
-
-
-
-
G3CN042
73
-
-
78 + 8
81 + 7
-
-
G3CN060
87
-
-
-
-
93 + 24
-
M3HD024
59
61 + 6
-
-
-
-
-
M3HD036
69
61 + 9
65+15
78 + 0
-
-
-
M3HD048
84
-
-
78 + 3
81 + 0
90 + 0
-
M3HD060
96
-
-
-
-
90 + 28
93 + 16
M3UF024
53
(59) + 2
-
-
-
-
-
M3UF032
59
61 + 7
65+19
-
-
-
-
M3UF044
69
61 + 14
65+22
73 + 3
78 + 5
-
-
M3UF052
84
-
-
(81) + 9
81 + 1
93 + 0
-
M3UF064
90
-
-
-
-
-
93 + 16
F1SA / F1SF024
61
61 + 2
-
-
-
F1SA / F1SF030
67
61 + 4
-
-
-
F1SA / F1SF036
81
-
-
78 + 3
-
* These orifices are factory-mounted in the flow control device of each indoor coil.
**These orfices are packed in the instruction/warranty packet of each outdoor unit.
NOTE: If orifice required is
not supplied in coil or in the outdoor unit instruction packet, the orifice in ( ) must be ordered from the
Parts Department.
NOTE 2: Due to scroll compressor, hard start components are not required when using coils with TXV or Solenoid Valve kits.
TABLE 2 - ORIFICE SIZES & CHARGE ADD STANDARD COILS
550.36-N2Y
6