background image

ELECTRICAL CONNECTIONS

1. Check the electrical supply to be sure that it meets the

values specified on the unit nameplate and wiring label.

2. Route low voltage wiring into bottom of control box as

shown in Figure 8.  Make low voltage wiring connections
inside the junction box.

3. The complete connection diagram and schematic wiring

label is located on the inside surface of the unit electrical
box cover. Field wiring is also shown previous page.

4. All field wiring to be in accordance with national electrical

codes.

NOTE: Power wiring, disconnect switch, and overcurrent pro-

tection to be supplied by installer. See Physical and
Electric Data Table for proper sizes. Use COPPER
CONDUCTORS ONLY.

WARNING: Unit must be grounded with a separate ground

conductor wire.

5. Install the proper size weatherproof disconnect switch out-

doors and within sight of the unit.

6. Run power wiring from the disconnect switch to the unit.

7. Install the proper size time-delay fuses or circuit

breaker,and make the power supply connections.

8. Energize the crankcase heater to save time by preheating

the compressor oil while the remaining installation is com-
pleted.

CRANKCASE HEAT

The crankcase heater is energized whenever the compressor
is not running. Check for proper operation by feeling for heat
on the compressor where the heater is installed. The heater

should be energized for at least 8 hours before the thermostat
is set to operate the compressor.

CAUTION:  An attempt to start the compressor without at least

8 hours of crankcase heat will damage the com-
pressor.

A warning label with an adhesive back is supplied in the unit
installation instruction packet. This label should be attached to
the field supplied disconnect switch where it will be easily seen.
See below:

SYSTEM PRESSURE REFERENCE

The “system pressure reference charts” (See Figures 11 and
12) should only be used as a quick check of system perform-
ance. It should not be used to determine proper system charge.

1. Operate the unit for a minimum of 15 minutes before

checking system.

2. Measure Pressure at the suction and liquid fitting and

measure the Outdoor Ambient Temperature.

3. Enter the chart at the measured Suction Pressure and

Outdoor Ambient Temperature to determine the expected
Liquid Pressure.

Actual liquid pressure should agree with valves shown plus or
minus 5 psig.

POWER 
WIRING

CONTROL 
WIRING

FIGURE 8 - TYPICAL FIELD WIRING

C

Y

R

G

W

W

G

R

Y

CONTACTOR
TERMINALS

24 VOLT
CONTROL
WIRING

FURNACE OR AIR HANDLER
TERMINAL BLOCK

POWER

CONTROL

FACTORY

ROOM THERMOSTAT

*

* Terminal W is only required on
   systems with heat.

POWER WIRING
   208/230-1-60

COIL

GROUND
SCREW

ALL FIELD WIRING TO BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE (NEC) AND/OR LOCAL CODES

ALL OUTDOOR WIRING MUST BE WEATHERPROOF.     USE COPPER CONDUCTORS ONLY.

IF POWER HAS BEEN OFF FOR 8 HOURS OR LONGER,
DISCONNECT SWITCH MUST BE TURNED ON 8 HOURS
BEFORE THERMOSTAT IS SET TO “HEAT”,"COOL" OR
“AUTO”
                                    035-03095. 

IMPORTANT

550.36-N2Y

Unitary Products Group

9

Summary of Contents for H2DH024S06

Page 1: ...The unit should be installed in accordance with all national and local safety codes Limitations for the indoor unit coil and appropriate accessories must also be observed For piping limitations and a...

Page 2: ...ERHEAD NEC CLASS 2 WIRING Sit unit on rubber elevator grommets to reduce noise and allow for proper drainage FIGURE 1 TYPICAL INSTALLATION MODEL H2DH024 H2DH030 H2DH036 H2DH042 H2DH048 H2DH060 UNIT SU...

Page 3: ...shown Sweat coils are shipped with a standard orifice in a plastic bag attached to the liquid line connection The orifice that is shipped with the coil is based on the most sold combination but it ma...

Page 4: ...The total system refrigerant charge is retained within the outdoor unit during shipping and installation The re usable service valves are provided to evacuate and charge per this instruction Serious s...

Page 5: ...the vapor fitting with a wet rag and braze the vapor line connection The nitrogen flow should be exiting the system from the vapor service port connection After This connection has cooled remove the...

Page 6: ...H2DH060 UNITORIFICE S 61 63 65 75 78 78 81 84 90 93 93 96 FACTORYR 22 CHARGE LBS OZ SWEAT 5 7 5 0 7 12 8 0 11 14 13 0 INDOOR COIL COIL ORIFICE REQUIRED SYSTEM ORIFICE ADDITIONAL CHARGE OZ G3HC G1FC02...

Page 7: ...urate weighing device is available add refrigerant accordingly CAUTION Compressor damage will occurif system is improp erly charged On new system installations charge system per R 22 charge informatio...

Page 8: ...73 75 77 79 79 2 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 82 4 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Saturation Temperature TABLE 5 Temperature and Pressure TEMP F PRESSU...

Page 9: ...re the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at least 8 hours of crankcase heat will damage the com pressor A warning label with an adhesive ba...

Page 10: ...0 60 65 70 75 80 85 90 95 SUCTION PRESSURE PSIG LIQUID PRESSURE PSIG 115 F O D AMBIENT 95 F O D AMBIENT 036 036 036 75 F O D AMBIENT 048 060 042 042 EXAMPLE H2DH036 unit with a 76 PSIG measured suc ti...

Page 11: ...mine if the system is operating properly 1 The outdoor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discha...

Page 12: ...ducts Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rights Reserved RPC 8M 695 66 Code SBY...

Reviews: