background image

SYSTEM CHARGE

The factory charge in the outdoor unit is listed in Table 2 and
includes enough charge for the unit and a most sold matched
evaporator. Some indoor coil matches may require some ad-
ditional charge.

Sweat connect units also include sufficient charge for 15 feet
of lines. Pre-charged line lengths are factory charged with the
correct amount of refrigerant required. Table 3 lists the refrig-
erant line charges.

The “TOTAL SYSTEM CHARGE” must be permanently
stamped on the unit data plate.

Total system charge is determined as follows:

1. Determine the outdoor unit charge from Table 2.

2. Determine indoor coil adjustment from Table 2.

3. Calculate the line charge using Table 3 factors. Calculate

over 15 feet of sweat lines for sweat connect units.

NOTE: For sweat connect lines, the line charge over 15 feet

should be included on the data plate and must be
added to the system.

4. Total system charge = item 1 + item 2 + item 3.

5. Permanently stamp the unit data plate with the total amount

of refrigerant in the system.

Use one of the following charging methods whenever addi-
tional refrigerant is required for the system charge.

CAUTION: Refrigerant charging should only be carried out by

a qualified air conditioning contractor.

Measurement Method

If a calibrated charging cylinder or accurate weighing device is
available, add refrigerant accordingly.

CAUTION: Compressor damage will occur if system is improp-

erly charged. On new system installations charge
system per R-22 charge information label and fol-
low guidelines in this instruction.

Check flare caps on service ports to be sure they are leak tight.
DO NOT OVER TIGHTEN (between 40 and 60 inch - lbs.
maximum).

Superheat Charging Method

NOTE: Use this method only during system maintenace and
repair.

1. Operate system until temperatures and pressures  stabilize

(minimum of 10 minutes).

2. Measure and record indoor wet bulb (WB) temperature

using a sling psychrometer and the outdoor dry bulb (DB)
temperature using a thermometer.

3. Measure and record the suction pressure at the suction

service valve port.

4. Using Table 4, note the superheat value corresponding to

the intersection of the indoor wet bulb and the outdoor dry
bulb.

5. With the superheat value obtained in step 4 and the suction

pressure value from step 3, find the intersection of the
values in Table 5. This is the required suction tube tempera-
ture at the suction service valve.

6.  To bring the tube temperature in line with the required value

from Table 5, add refrigerant to the service port to cause
the tube temperature to fall and reclaim refrigerant to cause
the temperature to rise.

UNIT 

SIZE

LIQUID 

LINE OD

VAPOR

LINE OD

R. CHARGE 

ADDER (OZ / FT)

024 TO 036

3/8

3/4

0.68

042 TO 060

3/8

7/8

0.70

TABLE 3 - REFRIGERANT LINE CHARGES

550.36-N2Y

Unitary Products Group

7

Summary of Contents for H2DH024S06

Page 1: ...The unit should be installed in accordance with all national and local safety codes Limitations for the indoor unit coil and appropriate accessories must also be observed For piping limitations and a...

Page 2: ...ERHEAD NEC CLASS 2 WIRING Sit unit on rubber elevator grommets to reduce noise and allow for proper drainage FIGURE 1 TYPICAL INSTALLATION MODEL H2DH024 H2DH030 H2DH036 H2DH042 H2DH048 H2DH060 UNIT SU...

Page 3: ...shown Sweat coils are shipped with a standard orifice in a plastic bag attached to the liquid line connection The orifice that is shipped with the coil is based on the most sold combination but it ma...

Page 4: ...The total system refrigerant charge is retained within the outdoor unit during shipping and installation The re usable service valves are provided to evacuate and charge per this instruction Serious s...

Page 5: ...the vapor fitting with a wet rag and braze the vapor line connection The nitrogen flow should be exiting the system from the vapor service port connection After This connection has cooled remove the...

Page 6: ...H2DH060 UNITORIFICE S 61 63 65 75 78 78 81 84 90 93 93 96 FACTORYR 22 CHARGE LBS OZ SWEAT 5 7 5 0 7 12 8 0 11 14 13 0 INDOOR COIL COIL ORIFICE REQUIRED SYSTEM ORIFICE ADDITIONAL CHARGE OZ G3HC G1FC02...

Page 7: ...urate weighing device is available add refrigerant accordingly CAUTION Compressor damage will occurif system is improp erly charged On new system installations charge system per R 22 charge informatio...

Page 8: ...73 75 77 79 79 2 47 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 82 4 49 51 53 55 57 59 61 63 65 67 69 71 73 75 77 79 81 83 Saturation Temperature TABLE 5 Temperature and Pressure TEMP F PRESSU...

Page 9: ...re the thermostat is set to operate the compressor CAUTION An attempt to start the compressor without at least 8 hours of crankcase heat will damage the com pressor A warning label with an adhesive ba...

Page 10: ...0 60 65 70 75 80 85 90 95 SUCTION PRESSURE PSIG LIQUID PRESSURE PSIG 115 F O D AMBIENT 95 F O D AMBIENT 036 036 036 75 F O D AMBIENT 048 060 042 042 EXAMPLE H2DH036 unit with a 76 PSIG measured suc ti...

Page 11: ...mine if the system is operating properly 1 The outdoor fan should be running with warm air being discharged from the top of the unit 2 The indoor blower furnace or air handler will be operating discha...

Page 12: ...ducts Group P O Box 1592 York Pennsylvania USA 17405 1592 Subject to change without notice Printed in U S A Copyright by York International Corporation 1995 All Rights Reserved RPC 8M 695 66 Code SBY...

Reviews: